Yaskawa Drive OV Fault Troubleshooting on Uncoilers: GPD 515/G5

Jason IP14 min read
TroubleshootingVFD / DrivesYaskawa
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Overview: OV Fault on Yaskawa GPD 515/G5 Driving an Uncoiler

An OV (Overvoltage) trip on a Yaskawa GPD 515/G5 series drive used on an uncoiler / payoff reel is one of the most common field faults. The drive is typically rated for a 575/600 V class supply and feeds a three-phase induction motor coupled directly (no encoder) to the coil. When the operator commands full speed reference from the speed pot, the drive accelerates the motor, reaches the commanded frequency, and then trips with OV on the keypad. Reducing the speed-pot reference allows the drive to run indefinitely.

The fault is almost never a defective drive. It is a symptom of one or more of the following physical conditions:

  • Regenerative energy from the load being pumped back into the DC bus faster than the bus capacitors and braking resistor can absorb it.
  • A dynamic braking resistor that is undersized, open, or incorrectly wired to terminals B1 and B2.
  • Input (line) voltage that is too high, reducing the available headroom between nominal bus voltage and the OV trip threshold.
  • Deceleration ramp (C1-02) set too aggressive for the inertia of the coil, or b1-03 set to Ramp to Stop while the load naturally wants to coast in less time than the ramp.
  • An incorrect voltage-class jumper (460 V vs 575/600 V) on the drive's input rating selection.

Because uncoilers carry very high stored rotational energy (steel coil plus reel), the load is always trying to drive the motor, not the other way around, once the strip tension is established. Any disturbance that momentarily unloads the motor, or any commanded decel that is faster than the load's natural coast time, results in the motor acting as a generator. That regenerated current flows back through the drive's rectifier in reverse, charges the DC bus capacitors, and pushes the bus voltage up toward the OV trip level.

Safety: Before opening any cabinet or touching terminals, lock out and tag out the disconnect upstream of the drive, wait a minimum of five minutes after power removal for the bus capacitors to discharge, and verify zero DC bus volts at terminals +1 and - with a properly rated meter. The DC bus on a 575 V class drive can exceed 1000 VDC while energized.

How the Yaskawa G5 Detects Overvoltage

The GPD 515/G5 samples the DC bus voltage directly and compares it against a fixed hardware threshold that is not user-adjustable. Understanding these thresholds is essential when sizing braking or interpreting trace data:

Drive Class Motor Voltage Nominal DC Bus (no load) OV Trip Threshold (approx.) Headroom
230 V class 208 / 230 VAC ~ 325 VDC ~ 400 VDC ~ 75 V
460 V class 380 / 400 / 460 VAC ~ 650 - 680 VDC ~ 710 - 720 VDC ~ 30 - 60 V
575 / 600 V class 575 / 600 VAC ~ 950 - 1000 VDC ~ 1030 - 1050 VDC ~ 30 - 80 V

On a 575 V uncoiler installation the bus sits around 1000 VDC during normal motoring at full speed. Any regeneration event of more than about 30 V of bus rise will trip the drive. This is why a 460 V drive mistakenly installed on a 575 V supply, or a 460 V voltage-class jumper left in place on a 575 V drive, will trip almost immediately on any regen event.

Why the Fault Disappears at Reduced Speed

Speed-pot reduction lowers the commanded output frequency. Below the speed at which the strip tension is fully developed, the motor is not yet back-driving the load, so the net energy flow is from the drive to the motor. As speed reference is raised, the uncoiler's dancer / tension loop demands more holding torque. If the strip is being pulled by a downstream process, the uncoiler motor is effectively motoring in reverse rotation relative to its commanded direction (the motor is acting as a brake). The faster the line, the more regenerative current is produced.

The trip threshold is hit when this regenerative current multiplied by the deceleration ramp (or by strip-tension-induced negative slip) exceeds the drive's ability to dissipate it. Below the critical speed, the energy is small enough to be absorbed by the DC bus capacitors and the modest internal braking transistor's on-resistance path.

Diagnostic Procedure: Confirming the Root Cause

Step 1 - Inspect the Voltage-Class Jumper

Locate the input voltage selection jumper on the GPD 515/G5 control board. Verify it is set to the 575/600 V position. A 460 V jumper on a 575 V drive will cause the drive to under-rate its OV threshold and trip early.

Step 2 - Measure the DC Bus on the Keypad

The G5 keypad does not display DC bus voltage directly on the main screen by default, but it is available in monitor parameter U1-07 (DC Bus Voltage). Navigate to the Monitor menu (U1 group) on the digital operator and scroll to U1-07. The displayed value is in VDC. With the drive in Run at no load, record the steady-state value. Then accelerate to full speed and record the value again. Any reading above the trip threshold listed in the table above confirms an OV event.

If a digital operator with LED display is in use and the value cannot be found, an external DMM connected between terminals +1 (positive) and - (negative) on the power board will read the same DC bus voltage directly. Use a 1000 V (CAT III 600 V or better) rated meter with isolated probes.

Step 3 - Review the Fault Trace

The GPD 515/G5 retains the last four faults plus a fault trace (output frequency, output current, bus voltage, and run status at the moment of trip) in the U2 and U3 parameter groups. Read U2-01 through U2-04 for the fault history, and U3-01 through U3-10 for the trace snapshot. A U3-07 value above the OV trip threshold at the moment of the trip is definitive proof of a DC bus overvoltage.

Refer to the Yaskawa GPD 506/P5 and GPD 515/G5 Unit Troubleshooting Manual for the complete fault-trace decoding tables.

Step 4 - Inspect the Braking Resistor

If a dynamic braking resistor is fitted, verify the following:

  1. The resistor is wired between terminals B1 and B2 on the drive. Polarity is not observed for a resistive element, but the wiring must land on the correct terminals and not on the DC bus studs.
  2. The resistor's ohm value matches the drive's minimum allowable resistance. The G5 internal braking transistor will fault on its own overcurrent if the resistor is below the minimum.
  3. Measure the resistor cold with the drive de-energized and locked out. An open resistor reads infinite ohms and is the single most common cause of persistent OV faults after a long service interval.
  4. Verify the wiring is not daisy-chained through a contactor or interlock that drops out during run.

Step 5 - Verify Supply Voltage at the Drive Input

Use a true-RMS meter at the drive's input terminals L1, L2, L3. Compare to the drive's nameplate. A 575 V supply that is actually running at 600 - 615 V (common on lightly loaded industrial feeders) reduces the available headroom for braking. The drive cannot absorb regen energy above the OV threshold regardless of resistor sizing if the bus is already sitting at 1020 VDC before any braking occurs.

Parameter Settings That Influence OV Behavior on the GPD 515/G5

The following parameters from the GPD 515/G5 menu are most often involved in OV trips on uncoiler duty. Refer to Yaskawa GPD 515/G5 Troubleshooting Manual Section Three for the full list.

Parameter Name Factory Setting Effect on OV Fault
b1-03 Stopping Method Selection 0 (Ramp to Stop) Setting 1 (Coast to Stop) eliminates forced decel and the OV it can produce; trade-off is uncontrolled stop.
b2-01 DC Injection Braking Start Frequency 0.5 Hz If b1-03 = 0 this determines at what frequency DC injection begins and indirectly affects stop energy.
b2-02 / b2-03 DC Injection Current / Time 50 % / 0.0 s Excessive DC injection after stop heats the motor and does not solve regen during ramp.
b3-11 Overvoltage Suppression (OV Stall Prevention) 0 (Disabled) Enabling this function allows the drive to automatically lengthen the decel ramp when bus voltage rises, preventing OV trip at the cost of slightly longer stop time. Set to 1 (Enabled) on uncoilers with significant inertia.
C1-01 Acceleration Time 1 10.0 s If acceleration is so fast that the motor overshoots mechanical resonance and back-EMF, OV can appear on accel as well as decel.
C1-02 Deceleration Time 1 10.0 s The single most common tuning fix: lengthen to give the bus time to dump energy into the resistor.
E1-01 Input Voltage Setting Drive class dependent Must match actual line-to-line supply voltage. A 460 V setting on a 575 V supply causes immediate OV.
E2-01 Motor Rated Current Drive class dependent If motor FLA is wrong, autotune miscalculates slip compensation and regen current spike on decel grows.

Recommended Solution Sequence

  1. Confirm root cause. Use the U1-07 monitor or an external meter to observe the DC bus at steady state and at the moment of trip. Capture the U3 trace after every trip.
  2. Correct the input-voltage setting. Set E1-01 to the actual measured line-to-line voltage (575 or 600). Set the hardware jumper to match.
  3. Verify and repair the braking resistor. Confirm continuity, confirm ohm value is above the drive's minimum, confirm wiring is on B1/B2.
  4. Enable OV suppression. Set b3-11 = 1. This is the safest first software fix because it limits the decel rate automatically and prevents nuisance trips without changing the operator's stop behavior.
  5. Lengthen deceleration ramp. Increase C1-02 in 2 - 5 second increments until the OV fault clears. Typical uncoiler values run 15 - 30 s for a full speed-to-zero ramp.
  6. Re-tune the motor. Run a rotational autotune with the motor uncoupled if possible (or static autotune if coupled). Verify E2-01, E2-02, and E2-03 are written correctly afterward.
  7. Re-size the braking resistor if steps 1 - 6 do not hold. Calculate the peak regen power from the load inertia and decel time, and select a resistor rated for at least 125 % of that peak for the full decel duration.
Field-proven caveat: Setting b3-11 = 1 on a process that cannot tolerate variable deceleration (for example, a winder whose tension loop is closed across the drive) can produce strip tension disturbances. Validate with the process engineer before deploying on a production line.

Dynamic Braking Resistor Sizing for Uncoiler Duty

The peak regenerative power the resistor must absorb is approximated by:

P_regen (W) = 0.5 x J_total x (ω_final^2 - ω_initial^2) / t_decel

Where:

  • J_total = total inertia at the motor shaft in kg·m² (motor rotor + gearbox + reel + coil), all reflected to motor rpm.
  • ω = angular velocity in rad/s at start and end of decel.
  • t_decel = deceleration time in seconds.

For a typical uncoiler with motor rotor inertia of 0.5 kg·m², reel + coil combined of 8 kg·m² (reflected), full speed at 1750 rpm (183 rad/s), and a target decel of 15 s, the peak regen power is:

P_regen = 0.5 x 8.5 x (183^2 - 0) / 15 ≈ 9,490 W

At a 575 V class bus of approximately 1000 VDC, the resistor ohm value is then approximately R = V^2 / P = 1000^2 / 9,490 ≈ 105 Ω. Always consult the Yaskawa G5 braking resistor selection table for the drive's specific horsepower before substituting values, because the drive's internal braking transistor has a minimum allowable resistance it will switch.

Related Fault Codes to Rule Out

While OV is the reported fault, two other Yaskawa G5 fault codes can appear in similar circumstances and should be ruled out during diagnostics:

  • LF (Output Open Phase) — Indicates an open phase on the inverter output side; loose terminal screws at T1, T2, or T3, or programmed parameters set incorrectly. Reference: Yaskawa LF Fault FAQ. On uncoilers, a momentary phase loss from a loose pull-on terminal can drop one phase, causing the other two to over-flux and the bus to spike.
  • PF (Input Phase Loss) — Indicates a missing input phase or severe input imbalance. Reference: Yaskawa PF Fault FAQ. A lost input phase causes the DC bus to ripple heavily and can fool the OV detector or trip the PF protection first.

Always clear and read the actual fault code displayed (not assumed). The G5 stores the most recent four faults; if the OV entry is preceded by an LF or PF in the trace, treat those as the primary fault and the OV as a downstream consequence.

Verification After Repair

  1. Reset the fault (Reset key on the digital operator, terminal S5 closed if programmed, or cycle power). Confirm the drive returns to Ready with no remaining fault in U2.
  2. Run the drive at 25 %, 50 %, 75 %, and 100 % of speed reference with no coil loaded. Monitor U1-07 (DC bus voltage) and U1-03 (output current) at each step. Bus voltage should remain within ±5 % of nominal.
  3. Load a coil. Run from zero to full speed and back to zero using the operator's standard command sequence. Confirm the bus voltage does not approach the OV threshold.
  4. Force a worst-case stop (full speed to zero in the operator's standard stop mode). Watch the bus voltage on the meter. If the bus peaks above 95 % of the trip threshold, the resistor is still undersized — repeat step 7 of the solution sequence.
  5. Document final parameter set: b1-03, b3-11, C1-01, C1-02, E1-01, E2-01, and braking resistor part number. Save the trace to a maintenance record.

Preventive Maintenance Recommendations

  • Measure DC bus voltage monthly under load and trend it. A creeping upward trend indicates a degrading bus capacitor or a slowly failing resistor.
  • Measure braking resistor resistance cold every six months. Resistor values drift upward as they age; an open resistor means OV trips return.
  • Torque-check power terminals (L1, L2, L3, T1, T2, T3, B1, B2, +1, -) annually. Loose terminals at T1/T2/T3 on uncoilers are a documented cause of LF and downstream OV events.
  • Verify the input voltage-class jumper during every commissioning or after any board replacement. This is a single jumper, easily missed after service.
  • Keep a printed copy of the G5 fault code list at the cabinet — fault code OV versus OV1 (overvoltage during accel) versus OV2 (overvoltage during decel) versus OV3 (overvoltage during constant speed) all have different root causes.

FAQ

What DC bus voltage trip threshold applies to a Yaskawa GPD 515/G5 575 V drive?

The OV trip threshold on a 575 / 600 V class GPD 515/G5 is approximately 1030 - 1050 VDC, hardware-fixed and not user-adjustable. Nominal bus voltage at full load is 950 - 1000 VDC, leaving only 30 - 80 V of headroom. Always confirm with the U1-07 monitor reading during the trip trace.

Which parameter enables automatic overvoltage suppression on the G5?

Set b3-11 = 1 to enable the overvoltage suppression (OV stall prevention) function. The drive will then automatically lengthen the active deceleration ramp when the DC bus approaches the OV threshold, eliminating nuisance trips without operator intervention. Confirm trade-offs with the process engineer on tension-critical winders.

How do I view DC bus voltage on the Yaskawa G5 keypad?

Navigate to the Monitor menu (parameter group U1) on the digital operator and scroll to U1-07. The value is shown directly in VDC. If the digital operator only displays the basic run screen, use a CAT III 1000 V meter between the +1 and - power terminals with the drive in run mode.

Why does the OV fault only appear at full speed reference?

At low reference the uncoiler's motor is not yet back-driving the load and the net energy flow is from drive to motor. As speed rises, dancer/tension control demands increasing holding torque; if the strip is being pulled by a downstream process the motor is forced into regen. Below the critical speed the regen energy is small enough to be absorbed by the bus capacitors; above it the bus exceeds the OV threshold.

Where do I connect a dynamic braking resistor on a Yaskawa GPD 515/G5?

Connect the braking resistor between terminals B1 and B2 on the drive's power terminal block. Polarity is not observed for a pure resistive element, but the wiring must terminate on B1/B2 and not on the +1 and - DC bus studs. The resistor's ohm value must meet or exceed the minimum specified in the G5 manual for the drive's horsepower rating; lower values will damage the internal braking transistor.

Can a 460 V drive mistakenly installed on a 575 V supply cause an OV fault?

Yes. A 460 V class G5 has a nominal bus of 650 - 680 VDC and an OV threshold around 710 - 720 VDC. On a 575 V supply the bus sits well above the OV threshold and the drive trips immediately on any regen event or even at no load under heavy input voltage. Always verify both the hardware jumper and parameter E1-01 against the actual measured line-to-line voltage.

Back to blog