Configuring SIMOTION D HMI Tag Addressing in WinCC Flexible

David Krause13 min read
HMI / SCADASiemensTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Configuring SIMOTION D HMI Tag Addressing in WinCC Flexible Runtime

SIMOTION D controllers (D425, D435, D445, D455) integrate a SIMOTION runtime with a SINAMICS S120 drive control unit on a common hardware platform. Integrating these controllers with an HMI such as the MP277 8" Touch using WinCC Flexible requires a different tag-addressing philosophy than a SIMATIC S7 PLC. The most common integration error is treating SIMOTION D the same as a SINAMICS CU320 and trying to reach drive parameters through absolute DB offsets such as DB35 DBD 4096. That pattern applies to a free-standing SINAMICS S120 with a CU320, not to a SIMOTION D425, where the SINAMICS subsystem is addressed symbolically through the SIMOTION connection driver.

This reference explains the correct path: building the HMI connection, exposing SIMOTION variables symbolically, displaying technological and Alarm_S messages, and verifying runtime data exchange between the controller and the panel.

1. SIMOTION D HMI Integration Architecture

SIMOTION D controllers support HMI integration through three primary communication paths:

  • PROFINET – typical for newer D4x5-2 variants using the integrated PROFINET interface or a CBE30 communication board.
  • PROFIBUS DP – used on legacy D4x5-1 hardware and on installations that retain a PROFIBUS-only HMI fleet.
  • S7 routing / Ethernet – used when the HMI must reach the SIMOTION D through a SIMATIC router or through the S7-300 backplane bus of the D4x5.

WinCC Flexible 2008 SP3 and later ship a dedicated SIMOTION connection driver. This driver uses the SIMOTION OPC-XML or the SIMOTION S7 communication protocol depending on the panel's firmware and the configured interface. With this driver in place, all SIMOTION device-level tags, user-defined variables, and I/O variables are exposed in the WinCC Flexible tag editor as symbolic names. Absolute DB addressing is not used and is not the correct path for SIMOTION D.

Per the official Siemens documentation, the HMI device must explicitly support SIMOTION CPUs in its connection list, and both the SIMOTION device and the HMI must exist as devices in the TIA Portal or SIMOTION SCOUT hardware configuration before a connection can be created. See the SIMOTION SCOUT TIA HMI connection entry for the prerequisite list.

2. Prerequisites

Before starting tag configuration, confirm the following:

  1. SIMOTION SCOUT version – V4.4 SP1 or later for the D4x5-2 DP/PN variants. SCOUT V4.3 HF1 or later supports the older D4x5-1 hardware.
  2. WinCC Flexible – 2008 SP3 or later for the MP277 8" Touch (order number 6AV6 643-0CD01-1AX1 or successor). WinCC Flexible 2007 supports basic variable exchange but not Alarm_S subscriptions.
  3. Connection license – The MP277 must be configured for at least 16 SIMOTION connections if Alarm_S and technological alarms are required.
  4. Hardware configuration – Both the SIMOTION D4x5 and the HMI panel must be inserted as devices in the SCOUT project navigator. The HMI is added through Insert > HMI device, and the SIMOTION D is added through Insert > SIMOTION device.
  5. Network configuration – IP addresses, subnet masks, and device names (PROFINET) or PROFIBUS node addresses must be assigned and match across both devices.
  6. Firmware – SIMOTION D firmware V4.3 or later, and CBE30 firmware V2.6 or later when used for PROFINET.
The MP277 8" Touch PN variant (6AV6 643-0CD01-1AX2) is the only MP277 model that supports PROFINET. The DP variant supports PROFIBUS only. Confirm the order suffix before commissioning.

3. Building the SIMOTION Connection in WinCC Flexible

The connection between the HMI panel and the SIMOTION D is the foundation of all tag and alarm exchange. Configure it in this order.

3.1 Insert the connection

  1. Open the WinCC Flexible project in the project tree.
  2. Right-click Connections under the HMI device and select New connection.
  3. In the connection wizard, choose SIMOTION as the communication driver. Do not choose SIMATIC S7 300/400; that driver uses absolute DB addressing and is the source of most SIMOTION integration errors.
  4. Assign a connection name (e.g., HMI_SIMOTION_D445).
  5. Select the interface:
Panel model Interface option Hardware path
MP277 8" Touch PN PROFINET Integrated PROFINET port on the panel backplane
MP277 8" Touch DP PROFIBUS PROFIBUS DP port on the panel backplane
WinCC Flexible Runtime on PC PROFINET or PROFIBUS CP5611, CP5613, or standard Ethernet adapter

3.2 Configure the SIMOTION partner

  1. Open the connection properties and select the SIMOTION tab.
  2. Enter the IP address of the SIMOTION D PROFINET interface (or PROFIBUS node number for DP).
  3. Set the rack and slot to match the SIMOTION D slot in HWCN. For D4x5 the slot is typically 0; for D4x5-2 with CBE30 it is 0 or 2 depending on how the CBE30 is mapped.
  4. For PROFINET, enter the PROFINET device name exactly as configured in SCOUT. Mismatched device names prevent connection establishment.

3.3 Verify the connection

Compile the project and transfer it to the panel. On the panel, open Start > Settings > WinCC Flexible Internet Settings > Connection status (or use the Connection indicator on a configured screen). A green status confirms that the SIMOTION driver has negotiated a live symbolic connection. A red status typically indicates a wrong IP, wrong device name, or a firewall blocking UDP port 34964 (PROFINET discovery) and TCP port 102 (S7 communication).

4. Symbolic vs. Absolute Tag Addressing

This is the single most important concept in SIMOTION HMI integration, and it is the source of the original question in the support thread.

4.1 Why absolute DB offsets do not work for SIMOTION D

The address pattern DB35 DBD 4096 is the SINAMICS S120 parameter access scheme. In a free-standing S120, parameter r35 of drive object 1 is mapped to a fixed data block offset in the CU320 memory image. The mapping is documented in the SINAMICS S120 List Manual and is consistent across projects because the CU320 firmware controls the layout.

SIMOTION D425, D435, D445, and D455 integrate the SIMOTION runtime and the SINAMICS drive control on a single piece of hardware. The SIMOTION runtime owns the memory map, and the SINAMICS subsystem is exposed to user code as a configured axis, not as a free-standing CU320. The memory layout in the SIMOTION D image is not the same as the CU320 image, and DB35 DBD 4096 does not point at parameter r35 of the integrated drive. This is why the pattern "works" in the field engineer narrative for free CU320s but fails when applied verbatim to a SIMOTION D.

4.2 Symbolic selection in WinCC Flexible

The correct method is to expose SIMOTION variables symbolically. Two routes exist:

  1. Unit variables – declared in the SIMOTION program as VAR_GLOBAL with optional VAR_GLOBAL RETAIN for retained values. These are visible to the HMI by name.
  2. I/O variables – linked to drive parameters through the technology object configuration (TO axis, TO external encoder, etc.) and exposed via the SIMOTION variable model.

In the WinCC Flexible tag editor:

  1. Open Tags > Add tag.
  2. In the connection field, select the SIMOTION connection created in Section 3.
  3. Click the Symbol column header to display the Symbol field.
  4. Click Browse (the ... button). The SIMOTION connection driver queries the SCOUT project and returns a tree of all globally exposed SIMOTION variables, including motor.temperature, axis1.actualVelocity, and any custom unit variable.
  5. Select the desired variable. WinCC Flexible automatically populates the data type, length, and access method.

Because the variable is selected by name, no DB or byte offset is required. If the SIMOTION program is renamed or re-tasked, the HMI tag follows the new name automatically on the next compile.

5. Exposing Drive Parameters to the HMI

To read or write a drive parameter from the HMI on a SIMOTION D, route it through a SIMOTION variable rather than a direct DB offset. The recommended pattern is:

  1. In the SIMOTION program, declare a unit variable, e.g., VAR_GLOBAL motor_temp : REAL; END_VAR.
  2. Read the drive parameter in a SIMOTION task (typically IPO2 or a cyclic background task) using the system function _getDriveParameter() or by reading the axis system variable.
  3. Assign the read value to motor_temp each cycle.
  4. In WinCC Flexible, symbolically select motor_temp as a tag and bind it to an I/O field on a screen.

For bi-directional parameters (setpoints, control words), assign the HMI tag to a unit variable and write the value to the drive parameter in the SIMOTION program. Direct binding of an HMI tag to a drive parameter through the SIMOTION driver is not part of the public API and is not supported across firmware revisions.

5.1 Common drive parameters frequently exposed to the HMI

Parameter Meaning Typical SIMOTION access path
r0021 Actual speed smoothed Axis system variable actualVelocity
r0022 Actual speed unsmoothed Axis system variable actualVelocityUnfiltered
r0035 Motor temperature _getDriveParameter(DO, 35)
r0722 Digital input status (CU) Read from cu.ioState or system variable
p0840 OFF1 / ON command Set through axis enable command
p1155 Speed setpoint source Configured in axis configuration; not normally changed at runtime

Refer to the SIMOTION Motion Control Communication manual for the full list of system functions for drive parameter exchange.

6. Alarm_S and Technological Alarm Configuration

SIMOTION generates three alarm classes that can be displayed on WinCC Flexible:

  • Technological alarms – from the technology objects (axis, path, cam).
  • Alarm_S messages – from the SIMOTION runtime, mapped to the S7 Alarm_S protocol.
  • User-defined alarms – generated through _alarm() system calls in the SIMOTION program.

6.1 SCOUT configuration

  1. Open the SIMOTION device configuration and select the HMI connection.
  2. Enable Send alarm messages to HMI on the connection properties.
  3. For Alarm_S, ensure that the message configuration in SCOUT is compiled and downloaded to the SIMOTION D. SCOUT generates an S7-compatible message DB automatically when the Generate Alarm_S option is enabled.
  4. For technological alarms, the technology objects must be configured with at least one alarm that has a user-defined category. The default categories are Information, Warning, and Fault.

6.2 WinCC Flexible alarm configuration

  1. In the project tree, open Alarms > Alarm settings.
  2. Confirm that the Alarm_S bit number is mapped to a SIMOTION alarm class. The default mapping works for most projects.
  3. Enable Acknowledgeable for any alarm that requires operator acknowledgement.
  4. Configure the alarm view on a screen and bind it to the Alarm_S buffer.

When a SIMOTION technological alarm fires, the message appears in the WinCC Flexible alarm view within the configured update cycle (typically 500 ms for PROFINET, 1 s for PROFIBUS at 12 Mbit/s).

7. Communication to WinCC Flexible Runtime on a PC

When the HMI is WinCC Flexible Runtime on a PC rather than a panel, the configuration is identical except for the interface binding. The PC must be equipped with a CP5611 (PROFIBUS) or a standard Ethernet adapter (PROFINET). The IP address in the SIMOTION connection on the PC side is the address of the SIMOTION D, not the PC.

For routed scenarios where the PC reaches the SIMOTION D through a SIMATIC router, configure the SIMOTION connection in WinCC Flexible with the S7 routing option and define the route in the PG/PC interface. The CBE30 on the D4x5 supports S7 routing only on firmware V2.6.6 and later; verify before commissioning.

Some versions of WinCC Flexible Runtime on Windows 7 and later ship with the firewall enabled by default. Allow ports TCP 102, TCP 34964, UDP 34964, and UDP 49152-65535 in the Windows Firewall inbound rules before commissioning. Without these, the symbolic connection fails with status Error 7000: Connection failed even when the network is correct.

8. Verification Procedure

After configuration, verify the system with the following steps:

  1. Connection test – From the panel, open Start > Settings > Transfer > Connection status and confirm that the SIMOTION connection is green.
  2. Tag value test – Add a temporary I/O field bound to a known SIMOTION variable, such as a counter incremented once per second in the SIMOTION program. Verify the value updates on the HMI every cycle.
  3. Bidirectional test – Bind a button to a write tag (e.g., cmd_start : BOOL). Toggle the bit from the HMI and confirm the SIMOTION program sees the change in the next IPO cycle.
  4. Alarm test – Trigger a SIMOTION technological alarm by issuing an axis stop with an active follow-up error. Confirm the message appears on the HMI with the correct timestamp and category.
  5. Diagnostic buffer – Open SCOUT > Target system > Diagnostics and confirm that the HMI is listed in the active connections.

9. Troubleshooting Matrix

Symptom Likely cause Resolution
Connection status red on panel Wrong IP or device name Verify the SIMOTION D IP and PROFINET device name match the SCOUT configuration; check Windows Firewall on the panel
Tag list empty in WinCC Flexible Wrong connection driver chosen Confirm SIMOTION driver is selected, not SIMATIC S7 300/400
Tag reads zero, does not update Variable not exposed in SIMOTION Confirm the variable is declared as VAR_GLOBAL and the program is compiled and downloaded
Drive parameter reads as zero Absolute DB offset used (e.g., DB35 DBD 4096) Replace with symbolic tag through a SIMOTION unit variable populated by _getDriveParameter()
Alarms do not appear Alarm_S subscription not enabled Enable Send alarm messages to HMI on the connection and recompile the message configuration in SCOUT
HMI displays 7000 error code Firewall on panel or PC blocking TCP 102 Open the inbound ports listed in Section 7
Variable renamed in SCOUT breaks HMI Symbolic tag selection not used Re-browse the SIMOTION connection in WinCC Flexible and re-select the renamed variable
Slow update cycle on PROFIBUS Baud rate at 1.5 Mbit/s Raise to 12 Mbit/s or migrate to PROFINET for sub-100 ms updates

10. Common Pitfalls and Field-Proven Notes

  • Do not assume the memory layout of a SIMOTION D matches a free-standing CU320. Even though both run SINAMICS firmware, the host platform (SIMOTION runtime vs. S7 CPU) controls the memory map.
  • Symbolic selection in WinCC Flexible requires the SCOUT project to be the active offline project. If the panel is connected to a different SIMOTION project than the one open in SCOUT, the browse dialog may show stale or empty variable lists.
  • When migrating from WinCC Flexible to TIA Portal WinCC, recreate the connections through the TIA Portal HMI wizard. Symbolic selection works identically in both, but the connection driver identifier changes from SIMOTION (WinCC Flexible) to SIMOTION device (TIA Portal).
  • For D4x5-2 DP/PN variants, the CBE30 PROFINET interface and the integrated PROFINET interface are separate network devices. The SIMOTION connection to the HMI must bind to one of them explicitly; the default in SCOUT is the integrated interface.
  • Retain variables are accessible symbolically but require that the Retain option is enabled on the SIMOTON project properties. Without it, the variable resets on every controller restart and the HMI reads the initial value.

11. Standards and Reference Documents

The following official Siemens documents and resources support the procedures described in this article:

Why does the address pattern DB35 DBD 4096 not work on a SIMOTION D425?

That pattern is the SINAMICS S120 parameter access scheme for a free-standing CU320, where drive parameters are mapped to fixed DB offsets. SIMOTION D425 integrates the SINAMICS subsystem on the same hardware as the SIMOTION runtime, and the memory map is owned by the SIMOTION runtime. Use symbolic tag selection through the SIMOTION connection driver instead.

How do I read drive parameter r0035 (motor temperature) on a SIMOTION D445 from a WinCC Flexible panel?

Declare a unit variable in the SIMOTION program (e.g., motor_temp : REAL), read the parameter each cycle using _getDriveParameter(DO_id, 35, motor_temp), and symbolically select motor_temp from the WinCC Flexible tag editor. Do not bind a tag directly to a drive parameter.

Which WinCC Flexible connection driver should I select for a SIMOTION D?

Select the SIMOTION connection driver, not SIMATIC S7 300/400. The SIMOTION driver exposes variables symbolically and supports Alarm_S and technological alarm subscription. The S7 driver uses absolute DB addressing and is not designed for SIMOTION runtime variables.

Can WinCC Flexible Runtime on a PC connect to a SIMOTION D?

Yes. The configuration is the same as for a panel. The PC requires either a CP5611 card for PROFIBUS or a standard Ethernet adapter for PROFINET, and the SIMOTION connection must be configured with the IP address of the SIMOTION D. Allow TCP 102 and UDP 34964 through the Windows Firewall on the PC.

What causes WinCC Flexible to show error 7000 on a SIMOTION connection?

Error 7000 indicates that the connection cannot be established. The most common causes are a wrong IP address, a mismatched PROFINET device name, or a firewall blocking TCP 102 or UDP 34964. Verify the network parameters and open the required ports on both the panel and the PC.

Back to blog