CPU 315T-2DP I/O Addressing: Troubleshooting SM323 Output Wiring

David Krause13 min read
S7-300SiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Overview

The CPU 315T-2DP is a Siemens Technology-CPU from the SIMATIC S7-300 family that combines standard PLC functionality with integrated motion-control technology objects. A common field failure involves an engineer attempting to drive a digital output on a separately-racked SM 323 digital input/output module while observing that Q0.0 remains at 0 V despite the logic program setting the bit to 1. The same symptom appears when the on-board 4DI/8DO of the Technology-CPU is addressed as a standard I/O point (for example QB66) because that address space is reserved for the technology firmware and is invisible to the standard user program.

This reference covers both failure modes:

  1. SM 323 outputs are logically true but physically 0 V — root cause is the missing 24 VDC / ground reference at the front connector of the digital module.
  2. On-board I/O of the CPU 315T-2DP cannot be set or read from OB1 — root cause is that the I/O area starting at byte 66 is owned by the technology objects and is not part of the standard process image.

Both problems are resolved by correct wiring and correct interpretation of the STEP 7 hardware configuration. A working configuration and a non-working configuration differ by as little as two jumpers on the front connector of the SM 323.

Hardware Identification

Before any address decision is made, confirm the exact MLFB (Siemens order number) of every device. The 6ES7 315-2xxx and 6ES7 315-6xxx families are not interchangeable.

MLFB (example) Designation On-board DI/DO Reserved For
6ES7 315-2AG10-0AB0 CPU 315-2 DP none Standard user program
6ES7 315-2EH13-0AB0 CPU 315-2 PN/DP none Standard user program
6ES7 315-6TH13-0AB0 CPU 315T-2 DP (Technology) 4 DI / 8 DO (byte 66+) Technology objects — not OB1
6ES7 315-6FF04-0AB0 CPU 315F-2 DP (Failsafe) none Standard + F-runtime
Critical: If the front cover of the module is labelled "315T-2 DP" and the integrated PROFIBUS DP interface is the only fieldbus on the CPU, you are working with a Technology-CPU. The 4DI/8DO brought out on the front connector are not general-purpose. They are wired to dedicated technology I/O and are mapped into the technology data block. They cannot be addressed with A I 66.0 or S Q 66.0 from the cyclic user program.

Verify the on-board I/O count in HW Config: open the CPU 315T-2 DP station, double-click slot 2, and inspect the dialog "Properties — CPU 315T-2 DP". If addresses are listed starting at byte 66, the I/O is owned by the technology firmware. For a standard CPU 315-2 DP the same slot will show "no integrated I/O".

SM 323 Digital Module — Pin Map and Power Requirements

The SM 323 is a 16-channel digital input / 16-channel digital output module that occupies one slot in the S7-300 rack. It is delivered in several variants; the most common for the 16DI/16DO configuration is 6ES7 323-1BL00-0AA0. The front connector is a 40-pin screw or spring-type connector. The two halves of the module — inputs and outputs — each require their own 24 VDC supply.

Front Connector Pin Signal Required? If Open
1 Output byte 0 — channel 0 (Q0.0) Load side Output never energises
20 Output byte 0 ground reference (0 V for DO) Yes All 16 outputs stuck at 0 V
21 24 VDC sensor / load supply #1 Yes Outputs 0.0 – 0.7 cannot switch
30 Ground (M) for supply #1 Yes Outputs 0.0 – 0.7 cannot switch, sensor supply collapses
31 24 VDC sensor / load supply #2 Yes Outputs 1.0 – 1.7 cannot switch
40 Ground (M) for supply #2 Yes Outputs 1.0 – 1.7 cannot switch, sensor supply collapses

The two supplies (pins 21/30 and 31/40) are galvanically isolated on the module and can be fed from separate 24 VDC circuits. Many cabinet builders place a single 24 VDC terminal and bridge 21–31 and 30–40 with a short jumper — this is acceptable as long as the wire gauge supports the cumulative load (0.5 A nominal per group, 1.0 A peak).

Front Connector Wiring Diagram

SM 323 6ES7 323-1BL00 Front Connector (40-pin) OUTPUT SIDE INPUT SIDE / SUPPLY 1 20 21 30 31 40 Q0.0 load (e.g. relay coil) 0 V load return +24 VDC supply #1 (pin 21) M / 0 V ground (pin 30)  

Root Cause Analysis

Two distinct root causes produce the symptom "logic says 1, terminal says 0 V":

Symptom Likely Root Cause Verification
SM 323 output stuck at 0 V, all 16 channels Front connector pins 21, 31 (24 VDC) or 30, 40 (M) are not wired Measure 24 VDC between pin 21 and pin 30 with a multimeter
SM 323 output stuck at 0 V, only one channel Field wiring broken / load > 0.5 A channel limit / short circuit Disconnect load, measure channel terminal to M
LED on output does not illuminate Process image not refreshed (OB1 PI not assigned) OR module in STOP Monitor Q0.0 in VAT online
CPU 315T-2DP on-board I/O (byte 66+) does not respond Address space reserved for technology objects Inspect HW Config, technology object configuration
SF (group fault) LED on SM 323 lit Missing supply, parameterisation error, or backplane fault Read diagnostic buffer with STEP 7 — PLC — Module Information

The reported case on the field — a CPU 315T-2DP with an SM 323 and outputs that would not drive despite S Q 0.0 in OB1 — was caused by the missing ground reference on the front connector of the SM 323. The 24 VDC load supply must have a 0 V return path; without it the output transistors cannot complete a circuit and the channel reads 0 V even though the logic state is true.

Step-by-Step Resolution

Step 1 — Inspect Hardware Configuration in STEP 7

  1. Open SIMATIC Manager and load the offline / online project for the station.
  2. Open HW Config and double-click the SM 323 in slot 4 (or wherever it is racked).
  3. Confirm the starting address matches the address you are using in the program. The default is 0 for both input and output bytes, giving IW0 / QW0 and bit access I0.0 / Q0.0.
  4. Open the Addresses tab. Note the entry under Process image: "OB1 PI" means the module is part of the OB1 process image update (automatic I/O refresh each cycle). "----" means the module must be read/written using SFCs (SFC 14/15 for consistent access, or direct load/transfer for non-consistent access).
  5. Repeat for the CPU slot to identify the on-board I/O starting address of the CPU 315T-2 DP (typically IB 66 / QB 66).

Step 2 — Wire the SM 323 Front Connector

  1. Power down the rack (PS 307 24 VDC) before touching the front connector.
  2. Open the front cover and remove the connector from the SM 323.
  3. Strip and crimp the conductors for the following pins:
      • Pin 20 — load ground return (0 V, output side)
      • Pin 21 — +24 VDC supply group 1
      • Pin 30 — M (0 V) of supply group 1
      • Pin 31 — +24 VDC supply group 2
      • Pin 40 — M (0 V) of supply group 2
  4. Re-seat the connector and torque the mounting screw.
  5. Restore 24 VDC to the PS 307 and verify with a multimeter: 24 VDC must be present between pins 21 and 30, and between pins 31 and 40.
  6. Check the SF LED on the SM 323. It must be off.

Step 3 — Download and Test the Logic

  1. In OB1, add the segment:
    SET     // sets RLO = 1
    = Q 0.0     // assign to first SM 323 output
  2. Download the program to the CPU (PLC — Download).
  3. Switch the CPU to RUN. The status LED for channel 0 of the SM 323 must illuminate and the terminal voltage must rise to 24 VDC (less 0.5 V drop on the output transistor).
  4. Open a Variable Table (VAT) and monitor Q0.0 in online view. The value must toggle between TRUE and FALSE as the program executes.

Step 4 — Address the On-Board I/O of the CPU 315T-2 DP (if required)

If the application needs to read the technology inputs or override a technology output from the user program, do not attempt a direct bit access. Use the technology function blocks and SFCs provided by the "S7-Technology" option package.

Task Mechanism Notes
Read digital cam / probe input on a technology axis Technology DB (instance DB) — configured in S7T Config / Technology objects Bit-mapped in technology DB
Force a technology output for commissioning Technology object — Commissioning dialog in S7T Config Force-mode only — removed at restart
Access via standard program (read-only) Read technology DB with L DBWx Do not write — interferes with motion control
Distributed I/O on the integrated DP port Configure in HW Config — addresses assigned in the DP slave properties See Siemens support entry 42413
Warning: Addresses that lie above the standard process-image boundary of the CPU, or that are reserved for technology, cannot be read with the simple load/transfer commands. Attempting to do so returns undefined values and may corrupt the technology state. Always consult the CPU's "Technical Data" table in the S7-300 manual to confirm the maximum address range per organisation block.

Process Image OB1 PI — What It Means

The "process image" (German: Prozessabbild) is a memory area in the CPU that holds a copy of all input and output signals at the start of every OB1 cycle. The benefit is that the user program reads a consistent snapshot of all inputs at the same instant, eliminating race conditions that would occur if inputs were read directly from the bus multiple times within one cycle.

In HW Config, each digital module shows one of two settings for the process image:

  • OB1 PI — the module is automatically refreshed at the beginning (inputs) and end (outputs) of every OB1 cycle. Access with A I 0.0 or = Q 0.0 from the user program. This is the default and the recommended setting for modules with a small number of bytes.
  • None (----) — the module is not part of the OB1 process image. Access is only possible with SFC 14 (DPRD_DAT) for consistent reading and SFC 15 (DPWR_DAT) for consistent writing. This is mandatory for modules that exceed the maximum process-image size of the CPU and is also required for some distributed I/O where consistent data is needed (e.g. analogue modules or complex slaves).

For a 16DI/16DO SM 323 the setting should always be OB1 PI. If STEP 7 has marked the module as "----", the user program cannot set the output with = Q 0.0; the SFC 15 call must be inserted in OB1 with the correct record length and the start address of the output area on the slave.

Verification Procedure

Run the following checklist after any wiring or configuration change:

  1. CPU in RUN — the green RUN LED is steady.
  2. SM 323 SF LED off — no group fault.
  3. SM 323 24 V LED on — the supply is present (where fitted on the module variant).
  4. Channel status LED on when the bit is set in the program.
  5. Terminal voltage between the output terminal and M measures 24 VDC ± 3 V under load.
  6. Diagnostic buffer clean — STEP 7 — PLC — Module Information — Diagnostic Buffer — shows no entries.
  7. Force test — temporarily force Q0.0 in VAT, observe the channel LED, then remove the force and confirm the program can still toggle it.

Troubleshooting Matrix

Fault Probable Cause Action
Output 0 V, channel LED off Logic bit is 0 OR module not in process image Monitor Q0.0 in VAT, check HW Config — Addresses
Output 0 V, channel LED on Missing load ground (pin 20 / 30 / 40) Re-wire front connector ground reference
Output 0 V, SF LED on Parameter error or backplane fault Read diagnostic buffer; correct slot or parameter mismatch
Output 0 V, channel LED on, supply present Overload / short on field side Disconnect load; check cable for short to M or 24 V
Outputs flicker randomly Inductive load without free-wheeling diode Add flyback diode across relay / solenoid coil
CPU 315T-2DP on-board output bit does not respond Address reserved for technology Use technology object DB or S7T Config — do not use S Q 66.0
Distributed I/O on integrated DP port: addresses above 1023 not readable CPU address area exceeded See Siemens support entry 42413 for the address rules of the CPU 315-2 DP

Field Commissioning Notes

  • Wire the front connector of every digital output module before applying 24 VDC. A floating ground is the single most common cause of "logic true / physical 0 V" on a Siemens S7-300 digital output.
  • Use a common 24 VDC busbar (or a fused distribution terminal) so that the cabinet has one defined 0 V reference. Multiple independent 24 VDC supplies without a shared 0 V return can produce mystery faults that change when cabinet doors are opened or closed.
  • For the CPU 315T-2DP, never place general-purpose I/O on the front connector of the CPU. Wire all standard digital I/O to an SM 321 / SM 322 / SM 323 in the rack. The on-board I/O is reserved for the technology package.
  • If the technology functions are not used, the on-board I/O area is still mapped in HW Config but cannot be read or written by the user program. To save debugging time, place a comment in OB1 indicating that addresses IB66 / QB66 are owned by the technology firmware.
  • When extending a station, remember that the maximum process image of the CPU 315-2 DP is 128 bytes for inputs and 128 bytes for outputs. Anything beyond that must be read with SFCs (SFC 14 / SFC 15) and is not part of the OB1 PI.

Related Configuration Checks

Three additional checks are worth performing in HW Config before declaring a station healthy:

  1. Slot rule: the SM 323 can occupy slots 4 to 11 in the S7-300 rack. Slot 3 is reserved for interface modules (IM 360/361) when used in a multi-rack configuration.
  2. Diagnostic interrupt: leave the default "Diagnostic interrupt" enabled. A blown fuse or missing supply generates a diagnostic entry that points directly to the channel.
  3. Substitution value: in the CPU properties — "Behaviour when CPU starts up" — define a substitution value of 0 for the output bytes so that the SM 323 outputs are forced to a defined state on STOP-to-RUN transitions.

FAQ

Why does Q0.0 stay at 0 V on my SM 323 even though the program sets it to 1?

The most common cause is a missing 24 VDC supply or missing ground return on the front connector. Measure 24 VDC between pin 21 and pin 30 of the SM 323. If the supply is absent, the output transistors have no power rail and the channel reads 0 V regardless of the logic state. Re-wire pins 20, 21, 30, 31 and 40 and re-test.

Can I access the on-board 4DI/8DO of the CPU 315T-2DP from OB1?

No. The on-board I/O of the CPU 315T-2DP (addressed from byte 66 upward) is reserved for the technology objects and the S7-Technology option package. Standard load/transfer commands cannot reach it. Use the technology DBs created by S7T Config, or use the S7T Config commissioning dialog, to read or override the technology I/O.

What does "OB1 PI" mean in the SM 323 properties dialog?

OB1 PI means the module is part of the OB1 process image. The CPU refreshes the input bytes at the start of every OB1 cycle and writes the output bytes at the end. The user program can then read inputs and write outputs with simple bit instructions such as A I 0.0 and = Q 0.0. If the property shows "----" the module is excluded from the process image and must be accessed using SFC 14 (DPRD_DAT) and SFC 15 (DPWR_DAT).

What is the maximum I/O address I can use on a CPU 315-2 DP?

The standard process image of the CPU 315-2 DP is 128 bytes for inputs and 128 bytes for outputs. Beyond that, the address area exists but is not part of the OB1 process image. Addresses greater than the CPU's address area cannot be addressed with load/transfer commands at all. For the exact limits, refer to Siemens support entry 42413.

My SM 323 shows the SF (group fault) LED — what should I check first?

Open STEP 7, connect online, and use PLC — Module Information — Diagnostic Buffer to read the most recent diagnostic entries. The two highest-probability causes on a 6ES7 323-1BL00 are missing 24 VDC load supply and a parameterisation mismatch between HW Config and the inserted module. Correct the supply wiring or align the order number in HW Config with the physical module.

Back to blog