Overview
Siemens SIMATIC STEP 7 V5.7 SP2 is the current maintenance release of the classic STEP 7 engineering environment used to program, commission, and diagnose the SIMATIC S7-300, S7-400, ET 200, WinAC, and C7 controller families. A 21-day trial is available to registered Siemens Industry Online Support users, providing full functional access (subject to trial-license activation) without purchasing a license key. This article covers the supported download path, the relationship to legacy STEP 7 V5.4 SP3 trial packages, MLFB numbers for ordering physical trial licenses, and the commissioning steps required to bring an offline engineering station up against live PLC hardware.
Engineers evaluating STEP 7 for the first time should note that classic STEP 7 (V5.x) is distinct from TIA Portal (V13..V20). The V5.x line is the only environment that natively programs the S7-300, S7-400, and the older C7-6xx controllers using the SIMATIC Manager shell. TIA Portal is the recommended path for S7-1200, S7-1500, and ET 200SP CPU firmware. If the target hardware is an S7-1500, this V5.7 trial is not applicable — install TIA Portal V20 trial instead.
Prerequisites
Before starting the download and trial activation, verify the following on the engineering workstation.
| Item | Specification | Notes |
|---|---|---|
| OS | Windows 10 Pro/Enterprise (64-bit) or Windows Server 2016/2019/2022 | STEP 7 V5.7 officially supports Windows 10 LTSC; LTSC 2019 / 2021 recommended for industrial use |
| CPU | x64 multi-core, 2 GHz or higher | Single-core is not officially supported |
| RAM | 8 GB minimum, 16 GB recommended | Large S7-400 projects with many FB/FC instances need ≥16 GB |
| Free disk | ≥12 GB for STEP 7 V5.7 SP2 + Service Pack | NTFS partition, separate OS disk recommended |
| Display | 1024 × 768 minimum, 1920 × 1080 recommended | Multi-monitor supported via standard Windows scaling |
| Siemens Online Support account | Registered user with valid e-mail | Free registration; required to access download ID 109820861 |
| Active Internet connection | Required for download and license activation | Offline trial activation via MLFB is a separate flow |
| User account | Local administrator rights during install | Required for PG/PC interface and AS-i driver setup |
Do not install STEP 7 V5.7 side-by-side with TIA Portal on the same image unless both are explicitly co-installed through the TIA Portal setup. Parallel installation of STEP 7 V5.5/V5.6 and V5.7 on the same OS is supported, but mixed SP levels of the same major version can corrupt the S7WIN directory.
STEP 7 V5.x Version Map and Trial Availability
Classic STEP 7 V5.x has been updated several times since its original release. The supported trial packages differ by major version and country support policy.
| Version | Latest Service Pack | Trial Download | Trial Period | Status |
|---|---|---|---|---|
| STEP 7 V5.4 | SP3 | Yes — see entry 26578452 (free, no license) | 14 days | Legacy, replaced |
| STEP 7 V5.5 | SP4 / SP4 HF7 | Limited availability | 14 days | Legacy |
| STEP 7 V5.6 | SP2 | Limited availability | 14 days | Maintenance |
| STEP 7 V5.7 | SP2 | Yes — entry 109820861 | 21 days | Current |
For most current evaluation work, use the V5.7 SP2 trial. The legacy V5.4 SP3 download is still useful when replicating an existing customer project that was last edited on a V5.4 PG.
Downloading the STEP 7 V5.7 SP2 Trial
Siemens distributes trial packages through the Industry Online Support portal. The exact entry for V5.7 SP2 is entry ID 109820861.
- Open a browser and navigate to STEP 7 V5.7 SP2 Trial Download (Entry 109820861).
- Sign in with a registered Siemens Industry Online Support account. If you do not have an account, click Register and complete the e-mail confirmation.
- Locate the Downloads tab of the entry and select the
STEP7_V57_SP2_Trial.exeimage. The file is approximately 4.6 GB. - Use a download manager or browser resume. Verify the SHA-256 checksum shown on the entry's download tab matches the downloaded file before installing.
- Save the installer to a local path with at least 12 GB of free space; the self-extracting archive requires temporary scratch space during unpack.
Notes on the legacy V5.4 SP3 path
The classic V5.4 SP3 package referenced in older documentation is entry ID 26578452 in the Siemens support portal. The full installer is provided as a free download with no license, and a 14-day automatic trial license is generated on first launch of the SIMATIC Manager. Engineers still maintaining very old S7-300 / S7-400 projects originally built on V5.4 should match the project environment to V5.4 SP3 to avoid offline block-time-stamp mismatches.
Installation Procedure
- Right-click
STEP7_V57_SP2_Trial.exeand choose Run as administrator. Accept the UAC prompt. - Select the destination language (English, German, French, Italian, Spanish, Chinese Simplified are bundled).
- Choose Complete for a full STEP 7 + S7-PLCSIM + S7-Graph + S7-SCL + S7-CFC installation, or Custom to add only the optional packages you require. Recommended selections for an evaluation workstation:
- STEP 7
- S7-PLCSIM V5.4 (for offline simulation)
- S7-GRAPH
- S7-SCL
- S7-CFC (only if you program S7-400 / PCS 7)
- Driver: TCP/IP RFC1006; ISO-on-TCP; MPI/DP via PC Adapter USB
- Wait for file copy. The setup logs are written to
%TEMP%\Siemens\Setup.logandC:\Program Files\Siemens\Automation\STEP7\S7BIN\instlog.txt. - Reboot when prompted. STEP 7 installs a kernel-mode service (SIMATIC NET S7DOS Help) that must be initialized before the first project is opened.
Trial License Activation
STEP 7 enforces licensing at three layers: the SIMATIC Manager shell, the optional packages (PLCSIM, GRAPH, SCL, CFC), and the AS-i / PROFIBUS / PROFINET interface drivers. A trial license is generated automatically the first time the SIMATIC Manager is launched, valid for 21 calendar days from that first launch for V5.7 SP2 and 14 days for V5.4 SP3.
| License Mechanism | V5.4 SP3 | V5.7 SP2 |
|---|---|---|
| Automatic trial on first launch | 14 days | 21 days |
| Re-armable after uninstall/reinstall | Yes, on the same PC | Yes, on the same PC; clock-rollback is detected |
| MLFB for ordered trial license (STEP 7 Professional) | 6ES7 810-4CC08-0YA8 | 6ES7 810-4CC11-0YA8 |
| MLFB for ordered trial license (STEP 7 base) | 6ES7 810-4CC07-0YA8 | 6ES7 810-4CC10-0YA8 |
To check the current license state, open SIMATIC Manager → Options → License Management. The Automation License Manager window lists every license key on the system with its expiry date and the host fingerprint.
To request a physical trial license from Siemens (which provides 21 days, identical to the auto trial, but can be transferred between PCs and is preferred for offline or air-gapped sites), use the MLFB numbers shown above. The order entry pages are:
After receiving the license USB stick or the e-mailed license file, double-click the *.zip package containing the *.LIC key file and follow the Automation License Manager prompts to install the key locally.
STEP 7 Lite (study / training alternative)
STEP 7 Lite is a functionally restricted, freely distributable variant of STEP 7 V5.x intended for self-study and training. Restrictions compared with the full STEP 7:
- No support for S7-400 / WinAC / C7 / ET 200S (IM151 CPU).
- Maximum of 1 S7-300 station per project.
- Limited to a single programming language subset (no GRAPH / SCL / CFC).
- PG/PC interface is restricted to TCP/IP RFC1006 only — no MPI, no PROFIBUS DP.
STEP 7 Lite is the correct choice if you are learning the SIMATIC Manager UI and need to build small ladder/FBD exercises against a single S7-300 PLC or the S7-PLCSIM emulator. It is not the correct choice for evaluation of a production engineering workflow.
Engineering Station Verification
After install and license activation, perform the following checks before connecting to a live PLC.
- Open SIMATIC Manager → File → New Project. Create a
Trial_Testproject. Verify that the license watermark is absent and that the status bar shows License OK. - Open the PG/PC interface applet (Start → Set PG/PC Interface). Select the appropriate access point:
S7ONLINEfor TCP/IP RFC1006, orPC Adapter (MPI)/PC Adapter (PROFIBUS)when using a USB PC Adapter. - Open Accessible Nodes. With a live S7-300/S7-400 connected on the same subnet, the CPU's MPI / IP address should be listed with its diagnostic buffer entry count.
- Open S7-PLCSIM and start a simulated S7-300 station. Download a minimal OB1 with
SET/SAVEinstructions. Verify a green RUN LED on the simulated CPU. - Confirm the Automation License Manager lists the trial key with the expected 21-day countdown.
Connecting to a Live S7-300 / S7-400 CPU
When the trial workstation is on the same physical or routed network as the target CPU, the connection workflow is:
- Confirm the CPU's IP / MPI / PROFIBUS address from the existing project, from the CPU's display (S7-300 with display panel), or via the assignment / DCP / NCM diagnostics tools.
- Open Set PG/PC Interface and set the active access path. For TCP/IP RFC1006 the access point is
S7ONLINEwith the parameterTCP/IP (Auto) -> Network card. - In SIMATIC Manager, choose PLC → Download after the project is online-compared. The trial license does not restrict download or online operations.
- Watch the Online → Online View window for the CPU's operating mode (STOP / RUN / RUN-P), diagnostic buffer, and module status.
A trial license does not include the runtime license for S7-PLCSIM, S7-Graph, S7-SCL, or S7-CFC when these optional packages are installed standalone. The auto-trial bundle covers the entire STEP 7 product, but moving the trial key between PCs requires the ordered physical trial key shown in the table above.
Service Pack and Hotfix Strategy
Siemens periodically releases hotfix bundles addressing USB PC Adapter stability, Windows 10 LTSC compatibility, and CPU firmware interoperability regressions. Subscribe to the entry's My Notifications feature to receive an e-mail when a new SP or HF is posted. For V5.7, the SP1 and SP2 packages are cumulative — install the highest SP available rather than each intermediate step.
Migration Considerations to TIA Portal
Projects created in STEP 7 V5.7 can be ported to TIA Portal V20 using the Migrate Project wizard. Items that do not migrate cleanly:
- Custom SDB container structures in S7-400H configurations
- S7-CFC charts with library references not present in the TIA Portal S7-CFC library
- Old S7-300 IM 178-4 / IM 359 module parameterizations predating V5.5
After migration, the original STEP 7 V5.7 project is preserved unchanged; the TIA Portal version is a sibling copy with all blocks re-typed to the TIA Portal data types.
Troubleshooting Matrix
| Symptom | Likely Cause | Remediation |
|---|---|---|
| SIMATIC Manager shows License not found after install | Automation License Manager service not started | Run services.msc, start ALM service, re-launch SIMATIC Manager |
| Trial expired after only 14 days on V5.7 | V5.4 SP3 trial was used by mistake | Verify installed version in Help → About; reinstall V5.7 SP2 entry 109820861 |
| Accessible Nodes does not list CPU | Wrong PG/PC access point, firewall blocking TCP/102 | Set S7ONLINE access point to the active NIC; open Windows Defender firewall rule for S7WIN
|
| Setup aborts with Error 1905 — Module C:\...\S7WTRSFX.DLL failed to register | Missing C++ runtime or pending reboot | Install Visual C++ 2015-2022 Redistributable x64; reboot; rerun setup |
| Online download stops at Compile / Consistency check | Project contains F-blocks that require S7-FCT add-on | Install optional F-configuration package or remove F-blocks from scope of download |
| S7-PLCSIM cannot start — port 102 already in use | Another S7 service or Wireshark remote capture binds TCP/102 | Stop offending service or change PLCSIM port via PLCSIM → Set PG/PC Interface → Properties |
Field-Proven Caveats
- Clock rollback detection: the trial license is bound to the PC fingerprint plus a monotonic time counter. Rolling the system clock back to extend the 21-day trial will lock the license and require re-installation.
- Virtual machines: running STEP 7 V5.7 inside a VM is supported on VMware Workstation 17+ and Hyper-V Gen 2, but the trial license is bound to the VM's UUID; cloning a VM with a running trial is detected and the key is invalidated.
- Windows 11 24H2: the current V5.7 SP2 build is tested against Windows 11 22H2 and 23H2. Windows 11 24H2 has known issues with the SIMATIC NET S7DOS Help service that are resolved by installing SP2 plus the latest hotfix bundle.
-
Antivirus interference: exclude
C:\Program Files\Siemens\AutomationandC:\ProgramData\Siemensfrom real-time scanning to avoid slow project-open behavior and corrupted S7PKZ archive files.
Related Siemens Support Entries
- STEP 7 V5.7 SP2 Trial Download — Entry 109820861
- Trial License STEP 7 Professional — Entry 29746989
- Trial License STEP 7 base — Entry 22445076
- STEP 7 V5.4 Service Pack 3 — Entry 26578452
How long is the STEP 7 V5.7 SP2 trial license valid?
21 calendar days from the first launch of the SIMATIC Manager. The countdown is shown in Options → License Management. After expiry, the workstation runs in view-only mode until a paid license or a newly requested trial key is installed.
Can I get a free STEP 7 V5.4 SP3 download today?
Yes, the legacy V5.4 SP3 full installer is distributed as a free download via Siemens entry 26578452, but it comes with no license. The first launch automatically generates a 14-day trial license. For new evaluation work, use V5.7 SP2 (entry 109820861) instead.
What is the difference between STEP 7 Lite and the V5.7 trial?
STEP 7 Lite is a permanently free, functionally restricted variant limited to a single S7-300 station with TCP/IP RFC1006 only, suitable for self-study. The V5.7 trial is a fully featured 21-day copy of the professional engineering environment, equivalent to a paid license during the trial window.
Which MLFB do I order for a physical trial license USB stick?
Order 6ES7810-4CC11-0YA8 for a STEP 7 Professional trial license or 6ES7810-4CC10-0YA8 for the STEP 7 base trial. Both are processed via the standard Siemens catalog and ship with a 21-day valid key.
Will the trial version program an S7-1500?
No. Classic STEP 7 V5.x targets S7-300, S7-400, ET 200 (older generations), WinAC, and C7 only. S7-1200 and S7-1500 require TIA Portal V20 or newer, which has a separate trial download in the same Industry Online Support portal.