MP277 to CPU 315T-2 DP: Resolving Duplicate Access Point Error

David Krause12 min read
HMI / SCADASiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

1. Problem Description

When configuring a SIMATIC MP277 (WinCC flexible 2008 SPx project) against a SIMATIC S7-300 CPU 315T-2 DP (6ES7 315-6TH13-0AB0 or compatible variant), engineers frequently add the first connection to the CPU and then attempt to add a second connection over the remaining physical interface. The first connection compiles cleanly, but as soon as the second connection is created and the project is rebuilt, both connections turn orange in the WinCC flexible "Connections" editor and in STEP 7 NetPro.

The orange state is WinCC flexible's signal that the connection definition is plausible (right PLC family, right rack/slot convention) but is not fully resolvable in the engineering database. It does not mean runtime communication is impossible, but it does mean the project will not download or will only partially download, and online diagnostics cannot be opened from the panel until the conflict is cleared.

Field note: The orange indicator in WinCC flexible is functionally equivalent to a yellow "warning" symbol in STEP 7 / NetPro. It does not block editing, but it blocks the Transfer > Compile & Download operation. A red icon, by contrast, indicates an invalid configuration (wrong slot, unreachable address) and must be fixed before any transfer.

2. Root Cause Analysis

The conflict is generated by the Access Point of the Application assignment on the connection object. Every WinCC flexible / STEP 7 connection carries a hidden parameter that names the Windows-side logical access point the engineering tool will use to reach the target when compiling, downloading, or performing online diagnostics. The default name is:

Access Point = S7ONLINE

This name is the same string used by:

  • STEP 7 V5.x "Set PG/PC Interface" dialog
  • WinCC flexible Transfer channel
  • SIMATIC Manager "Accessible Nodes" lookup
  • Any PC-side application that follows the S7ONLINE convention (ProSave, S7-PCT, etc.)

When two WinCC flexible connections to the same target CPU both reference S7ONLINE, the engineering database cannot decide which physical interface (TCP/IP or PROFIBUS) the S7ONLINE access point should bind to for that specific connection. WinCC flexible therefore reports both connections as unresolved and turns them orange.

The relationship between the access point string and the physical hardware is defined in the Windows control panel Set PG/PC Interface application (entry point: Control Panel → Set PG/PC Interface on a classic WinCC flexible engineering station). The mapping is one-to-many: a single access point can be assigned to one physical interface at a time, but multiple distinct access point names can each point to a different interface.

3. CPU 315T-2 DP Communication Architecture and Connection Resources

Per the official SIMATIC S7-300 CPU 31xT manual (entry ID 21362915), the CPU 315T-2 DP provides:

CPU 315T-2 DP interface and resource summary (6ES7 315-6TH13-0AB0)
Parameter Value
Order number (last released variant) 6ES7 315-6TH13-0AB0
Firmware range covered by manual V2.7 and higher
Work memory (integrated) 256 KB code / 128 KB data (varies by FW)
Interface X1 (MPI/DP combined) MPI or PROFIBUS DP master/slave, 12 Mbps max
Interface X2 PROFINET (2-port switch), 100 Mbps
Max S7 connection resources 14 (for S7 communication; further reduced if OP/TP/PG/Profinet IO are active)
Reserved connection resources (PG/OP) 1 PG + 1 OP reserved; remaining available for S7 / S7-HMI / PtP / etc.
Technology objects Yes (motion / T-CPU)

The 14 connection resources are shared across:

  • PG (programming device) online
  • OP/TP (HMI panels, including the MP277)
  • S7 connections defined in NetPro (PUT/GET, USEND, BSEND, etc.)
  • PROFINET IO controller / device relationships
  • Time synchronization (where configured)

The CPU 315T-2 DP reserves one resource for PG and one for OP by default. Adding the MP277 twice (once over PROFINET, once over PROFIBUS) consumes two OP resources, leaving the engineer with the full 14 minus 2 minus any NetPro-defined S7 connections. For a typical 2-connection HMI configuration, the 14-resource ceiling is not the proximate problem; the access point naming is.

4. MP277 Interface and Connection Model

The MP277 8" and 10" panels (e.g., 6AV6 643-0CB01-1AX1 Touch, 6AV6 643-0BA01-1AX1 Key) provide two physical interfaces relevant to this configuration:

MP277 interface Connector Function
IF 1B (PROFINET) RJ45 Engineering transfer, runtime S7 communication over TCP/IP
IF 2 (PROFIBUS DP/MPI) Sub-D 9-pin Engineering transfer, runtime S7 communication over PROFIBUS

A single MP277 can run two S7 connections to the same CPU simultaneously, one per interface, and WinCC flexible supports this with the connection type S7 300/400. Each connection is an independent PLC integration with its own tag namespace, its own area pointers, and its own error-status tag (or "connection-status" bit) used by the runtime to flag a loss of the partner.

The two connections must each declare which physical interface of the MP277 they ride on, and the engineering transfer channel of WinCC flexible must know which interface to use during download. This is exactly where the access point parameter takes over.

5. Prerequisites

Before applying the fix, confirm the following:

  1. STEP 7 V5.5 (or V5.4 + SP5) is installed with the CPU 315T-2 DP support package (HSP ready).
  2. WinCC flexible 2008 SP5 (or 2008 SP3 with HF13 or higher) is installed.
  3. Either the WinCC flexible project is integrated into STEP 7 (recommended) or it is a standalone project with the connection partners correctly typed.
  4. The MP277 is reachable on at least one interface (green Transfer LED behavior, or Control Panel > Transfer > accessible).
  5. Windows "Set PG/PC Interface" shows at least one valid access point assignment for the physical interface currently in use.
Compatibility note: WinCC flexible 2008 is the last major release that supports the MP277 as a target device. Later TIA Portal versions require migration to a Comfort Panel (MTP/Comfort) for parallel Ethernet and PROFIBUS configurations. The fix described here applies to the classic STEP 7 + WinCC flexible toolchain only.

6. Step-by-Step Resolution

  1. Open the WinCC flexible project (or the STEP 7 project with the integrated WinCC flexible station).
  2. In the project tree, open Connections under the MP277 station.
  3. Confirm you have two connection objects, both targeting the CPU 315T-2 DP rack/slot, e.g., Connection_1 (PROFINET) and Connection_2 (PROFIBUS). Both will show the orange icon.
  4. Select Connection_1. In the Properties inspector, switch to the Parameter tab.
  5. Locate the Access Point field. It will show the default value S7ONLINE.
  6. Leave Connection_1 set to S7ONLINE.
  7. Select Connection_2. Open its Parameter tab.
  8. Change the Access Point field from S7ONLINE to a new unique name, for example S7ONLINE1.
  9. Open Windows Control Panel → Set PG/PC Interface. In the Access Point of the Application dropdown, select S7ONLINE1 and assign it to the interface that is NOT used by S7ONLINE (typically PROFIBUS MPI if S7ONLINE is already TCP/IP). Click OK.
  10. Return to the WinCC flexible project. From the menu choose Project → Rebuild All (or right-click the station → Rebuild All). The orange indicators should clear on both connections.
  11. Save the project (Ctrl+S).
  12. Transfer the project to the MP277 using whichever interface the user intends to be the primary transfer channel. The panel's Transfer dialog (under Control Panel) must be set to allow transfers on the matching interface.

6.1 STEP 7 NetPro Alternative

If the WinCC flexible station is integrated into STEP 7, the same parameter is exposed in NetPro:

  1. Open SIMATIC Manager → Project → Open NetPro.
  2. Right-click the connection line between the MP277 and CPU 315T-2 DP. Choose Object Properties.
  3. Open the connection's Special / Parameter tab. Find the Access Point property.
  4. Rename the second connection's access point to S7ONLINE1.
  5. Save and close NetPro. Reopen WinCC flexible and run Rebuild All.

7. Matching the Transfer Mode and Baud Rate

A second, independent cause of "both connections orange" or "transfer fails after the first download" is mismatched transfer settings between the panel and the CPU. After fixing the access point, verify these on both ends:

Parameter MP277 (Control Panel → Transfer) CPU 315T-2 DP (STEP 7 HW Config)
Transfer mode PROFIBUS / MPI / Ethernet (auto or fixed) Interface X1: MPI or DP; Interface X2: PROFINET
Baud rate (PROFIBUS) 19.2 kbps / 187.5 kbps / 1.5 Mbps / 3 Mbps / 6 Mbps / 12 Mbps Must match (set in CPU Properties → Interface → MPI/DP)
Highest station address (HSA) n/a (panel is the master in transfer) Must be ≥ panel's PROFIBUS address
PROFIBUS address (panel) 1 (default) Address space must include the panel's address
IP / Subnet (PROFINET) Static or DHCP, must be in same subnet as CPU X2 port Configured under CPU Properties → PROFINET interface

If the user changed S7ONLINE to point at PROFIBUS for the second connection, the panel's PROFIBUS transfer channel and the CPU's MPI/DP interface must both operate at the same baud rate and both must agree on the panel's DP/MPI address. Mismatched baud rate is the most common cause of "transfer starts, then fails partway through" errors after the access point fix is applied.

8. Rebuild and Transfer Procedure

After the access point is renamed and the PG/PC interface is re-assigned:

  1. In WinCC flexible, choose Project → Compiler → Rebuild All. Confirm no warnings or errors are reported in the output window.
  2. Power-cycle the MP277 (or soft-restart from the Control Panel).
  3. On the panel, navigate to Control Panel → Transfer → Settings. Enable Transfer on the interface that matches the access point S7ONLINE (typically Ethernet/PROFINET) and, if needed, on the interface that matches S7ONLINE1 (typically PROFIBUS).
  4. From the engineering PC, run Transfer → Download → Target → Ethernet or PROFIBUS as appropriate. WinCC flexible will resolve the S7ONLINE / S7ONLINE1 binding through the Set PG/PC Interface configuration.
  5. After the first transfer completes successfully, the panel restarts into runtime and both connection status indicators in the project (under Connections → Status) should show green.

9. Verification

To confirm both connections are alive at runtime:

  • On the MP277, open the configured connection-status area pointer (default tag name: <Connection>_Status or the user-defined name). The bit should report connection established for both connections within 5–15 seconds after panel start.
  • In STEP 7, select the CPU and choose PLC → Accessible Nodes with the panel's PROFINET IP. The panel should appear as an OP partner on the active connection list.
  • Open the CPU's diagnostic buffer (PLC → Diagnostic Buffer). Look for entries referencing the MP277's MPI/DP and PROFINET addresses. Each connection establishment logs an "S7 connection established" event with the partner's TSAP and address.
  • Watch the MP277's mode LEDs during startup: the bottom-row LED cluster should show Transfer blinking during download, then Run steady once runtime is active and both connections are up.

10. Troubleshooting Matrix

Symptom Probable cause Corrective action
Both connections orange after creating the second Access point collision (S7ONLINE used twice) Rename second connection's access point to S7ONLINE1; reassign in Set PG/PC Interface
Connection goes green after Rebuild All, transfer fails Baud rate mismatch on PROFIBUS Set the same baud rate in panel Control Panel → Transfer and CPU Properties → MPI/DP
PROFINET connection green, PROFIBUS red at runtime PROFIBUS address conflict or bus termination missing Verify the panel's PROFIBUS address is unique on the segment; check terminating resistors on first/last node
Both connections red at runtime, no diagnostic entries CPU has run out of S7 connection resources (14 max for CPU 315T-2 DP) Reduce the number of S7 connections in NetPro; ensure reserved OP/PG resources are not over-allocated
Only one connection visible, cannot add a second Project version of WinCC flexible too old for dual connection (need 2008 SP3 HF13 or SP5) Update WinCC flexible to 2008 SP5 and re-create the connection
Orange reappears after PG download of STEP 7 project STEP 7 NetPro overwrites the access point on rebuild Re-apply the access point rename in NetPro and run Save and Compile; transfer the WinCC flexible subproject afterwards
Resource warning: The CPU 315T-2 DP's 14 connection resources are shared. If the project also uses a third-party OPC server, a PROFINET IO controller relationship to a remote I/O station, and S7 PUT/GET pairs, the resource ceiling can be reached quickly. Each MP277 connection counts as one OP resource. If you see "no more connection resources available" in the CPU diagnostic buffer, prune NetPro connections before continuing.

11. Field-Proven Notes

  • Always rename the access point on the second connection, not the first. The S7ONLINE name is referenced by ProSave and by STEP 7 — changing it on the primary connection breaks the engineering transfer channel.
  • If the panel is later re-flashed with a different WinCC flexible project, the access point assignment in Set PG/PC Interface persists, but the connection objects are re-evaluated. Re-validate both connections after a clean install.
  • Some older service packs of WinCC flexible 2008 (SP1 / SP2) do not surface the access point parameter in the connection editor at all. In that case, the only workaround is to define the second connection on a separate WinCC flexible station (a different MP277 device in NetPro) targeting the same CPU, then merge the area pointers manually. Upgrading to SP5 removes the limitation.
  • Do not rename S7ONLINE itself in the registry. The name is hard-coded in many SIMATIC tools. Use only the Set PG/PC Interface dialog to add S7ONLINE1 as a new logical access point.

12. Related Documentation

Why do both MP277 connections to the same CPU 315T-2 DP turn orange in WinCC flexible?

Both connections default to the same Windows-side access point string S7ONLINE, so the engineering database cannot resolve which physical interface (PROFINET vs PROFIBUS) the S7ONLINE binding should use for the second connection. Renaming the second connection's access point to S7ONLINE1 and reassigning it via Set PG/PC Interface clears the orange state.

How many S7 connection resources does the CPU 315T-2 DP have?

The CPU 315T-2 DP provides a maximum of 14 S7 connection resources in total, including those reserved for PG (1) and OP (1). Each MP277 connection consumes one OP resource. Other S7 connections defined in NetPro (PUT/GET, BSEND/USEND, etc.) and PROFINET IO relationships also draw from the same pool.

Do I have to change the baud rate on the MP277 to match the CPU 315T-2 DP for PROFIBUS transfer?

Yes. The MP277's transfer baud rate (set in Control Panel → Transfer → Settings) must match the baud rate configured for the CPU's MPI/DP interface (X1) in STEP 7 Hardware Configuration. Typical transfer rates are 187.5 kbps or 1.5 Mbps. Mismatched baud rates produce partial download failures and re-trigger the orange indicator after a rebuild.

Can I have two MP277 connections to the same CPU, one over PROFINET and one over PROFIBUS, in WinCC flexible 2008?

Yes, WinCC flexible 2008 SP3 (with HF13 or higher) or SP5 supports two simultaneous S7 connections from a single MP277 to the same CPU, one per physical interface. Each connection gets its own tag namespace, its own area pointer set, and its own status bit. The access point workaround is required for the engineering tool, not for the runtime.

Will renaming the access point in NetPro get overwritten after a STEP 7 rebuild?

Yes, NetPro can reset the access point parameter on the WinCC flexible station to the default S7ONLINE during a STEP 7 "Save and Compile" pass. To keep the rename permanent, re-apply the S7ONLINE1 name in NetPro, save, and then rebuild the WinCC flexible subproject before transferring to the panel.

Back to blog