Resolving Siemens G150 Fatal Error: AOP Stopped on Startup

David Krause16 min read
SiemensTroubleshootingVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Siemens SINAMICS G150: Resolving "Fatal Error in Drive: AOP Stopped"

The Siemens SINAMICS G150 cabinet drive is a high-power, air-cooled AC drive family widely deployed in pumps, fans, compressors, mills, and extruders. Although mechanically robust, G150 systems depend on a healthy control platform consisting of a CU320-2 (or CU320) Control Unit, an AOP30 Advanced Operator Panel, and a CompactFlash (CF) card loaded with firmware, parameters, and option licensing. When the CF card develops bad sectors, the CU320-2 enters an unrecoverable state and raises the alarm "Fatal error in drive: AOP stopped" on the AOP30, which then locks and prevents normal operation. This reference explains the root cause, the diagnostic verification path, the field-proven fix (CF card replacement with part 6SL3054-1CE00-1AA0), and the recommissioning workflow that restores a 250 kW G150 cabinet to service.

Severity: This is a hard-stop fault. The drive enters a non-operational state, all control commands are inhibited, and a power-cycle does not clear the message. The drive will not respond to ON/OFF, RUN/STOP, or fault-acknowledge commands until the underlying control hardware or media has been repaired.

1. Affected Product Range and Hardware Stack

The "Fatal error in drive: AOP stopped" message is observed on SINAMICS G150 chassis (order code 6SL3710-1LE4x-xxxx, 6SL3710-2LE4x-xxxx, 6SL3710-1LG4x-xxxx) populated with the following components:

Component Siemens Designation Order Number Function in Fault
Control Unit CU320-2 DP / CU320-2 PN 6SL3040-1MA01-0AA0 / 6SL3040-1MA02-0AA0 Boot loader, runtime, parameter storage host
CompactFlash card CF card (firmware/license) 6SL3054-1CE00-1AA0 (FW ≥ 4.x) or 6SL3054-1CE00-1BA0 (FW 2.x/3.x) Boot media, parameter persistence, license key container
Operator Panel AOP30 (or BOP20) 6SL3055-0AA00-4BA0 (AOP30) HMI display that surfaces the message
Power Module interface DRIVE-CLiQ to TM31, SMC/SME 6SL3040-0LA0x-0AAx Not implicated in this fault

The compact drive described in the field case is rated at 250 kW, which corresponds to a 6SL3710-1LE41-0AA0 chassis (400 V, 50/60 Hz, 460 A nominal). At this power class the G150 ships with a CU320-2 DP control unit, a type-30 AOP30 operator panel, and a single 6SL3054-1CE00-1AA0 CompactFlash card pre-imaged with the matching firmware build (typically V4.6, V4.7, or V5.x depending on commissioning era).

2. The "Fatal Error in Drive: AOP Stopped" Message: What It Means

The string "Fatal error in drive: AOP stopped" is generated by the CU320-2 firmware's boot-time exception handler when one of the following conditions occurs before the runtime firmware is fully initialized:

  • The CF card returns a read or seek error during firmware load, preventing the operating image from being copied to volatile memory.
  • The CF card's file system structure is corrupted to the point that the boot loader cannot locate fwu/ firmware images or the user/ parameter directory.
  • The license signature blob on the CF card fails cryptographic verification, leaving the drive in a fail-secure state.
  • The CU320-2 has an internal memory fault (much rarer) and references the CF card as the boot media of last resort.

When any of these conditions occur, the firmware aborts the boot sequence, halts the internal RT scheduler, and reports a single non-acknowledgeable fault to the AOP30. Because the AOP30 talks to the CU320-2 over a serial RS-232 PPI link, the AOP itself shows "AOP stopped" as a secondary indicator that the control unit is no longer transmitting heartbeats. The drive's main contactor (line contactor, K1) will not pull in, and the display will not respond to the RUN, STOP, or FAULT-ACK keys.

Important: The message does not indicate an AOP30 hardware failure. The AOP is functioning correctly; it is simply displaying what the CU320-2 told it before the CU320-2 went into a fatal halt. Do not replace the AOP30 first - replace the CF card.

3. Root Cause: CompactFlash Card Degradation

In the reported field case, the root cause was conclusively traced to a faulty CompactFlash card, order number 6SL3054-1CE00-1AA0. CF cards used in industrial cabinets from the early 2010s onward are typically consumer-grade industrial-temperature SLC or pSLC NAND modules in a CFA-compliant form factor. They share a wear-leveling issue: while the average read/write duty of a CU320-2 is low (parameters are written primarily during commissioning and on parameter set save), the following stressors accelerate wear:

  • Cabinet ambient temperature above 40 °C, with the CF card slot located close to the rectifier heat sink.
  • Frequent parameter save/load cycles (e.g., recipe handling via p0804/p0805 on a process line).
  • Uncontrolled power-downs that leave the FAT directory in an inconsistent state.
  • High humidity / dust that contaminates the card-edge connector.
  • Age: most industrial CF cards begin to develop read-disturb and bit-rot defects after 8-10 years in service.

When the CF card reaches end-of-life, the CU320-2 boot loader, which expects to read fwu/ and user/ partition images in a specific sequence, fails on the first read. The CU's internal watchdog triggers a fatal exception, and the user-visible message is produced.

3.1 Confirming the CF Card as the Suspect

Before replacing the card, perform these confirmatory steps. They save time when a less common cause is involved:

  1. Power-cycle the cabinet with the line supply removed for at least 30 s. The CF card slot is hot-pluggable on the CU320-2, but for safety always remove the supply. Power-up again. If the same message returns, the fault is persistent (not a transient glitch).
  2. Inspect the CF card by ejecting the ejector button on the CU320-2 front panel. Examine the card-edge connector for oxidation, dust, or bent pins. Reinsert firmly. Power up. If the fault returns, proceed to replacement.
  3. Check the CU320-2 LEDs: RDY (green) should be steady on; COM (yellow) blinks on DRIVE-CLiQ traffic; OPT (red) is the option-fault LED. If RDY is off or flashing red, the CU is in fault - confirms the AOP message originates in the CU, not the panel.
  4. Read the diagnostic buffer via STARTER or SIMOTION SCOUT if the project is still on a PG/PC. Connect via Ethernet (PROFINET) or PROFIBUS to X126 / X136. Read r0947 (fault code) and r0949 (fault value). Common codes associated with this scenario are F01000 (internal software error), F01002 (internal software error - boot), and F01300 (invalid firmware on the CF card).
  5. Substitute the CF card with a known-good 6SL3054-1CE00-1AA0 from a healthy sister drive. If the drive boots, the original card is the confirmed root cause.

4. Solution: CompactFlash Card Replacement Procedure

Replacing the CF card on a SINAMICS G150 is a field serviceable operation, but it requires a controlled power-down and a recommissioning step. The new card must be loaded with firmware and parameters before the drive will operate.

4.1 Prerequisites

  • Replacement CF card: 6SL3054-1CE00-1AA0 (for firmware ≥ 4.6) or 6SL3054-1CE00-1BA0 (for older firmware). The two are not interchangeable - match the firmware branch that was in service.
  • STARTER commissioning tool (current version, e.g., V5.4 SP3 or later) or Startdrive for TIA Portal (V15.1 or later).
  • Backup of the existing project on a programming device (PG/PC) - if available. If the original card is unreadable, this is the only way to restore parameters.
  • Firmware image files (downloadable from Siemens Product Support under entry ID 109763072 for SINAMICS S120/G150 firmware).
  • Access to the CU320-2 front panel and the ability to remove cabinet doors per local EHS rules.
  • Personal protective equipment rated for the cabinet's line voltage (typically 400 V or 690 V).

4.2 Replacement Steps

  1. Lockout-tagout (LOTO) the main line supply. Verify absence of voltage at the line terminals with a CAT IV 1000 V tester. Wait the prescribed 5 minutes for DC bus capacitors to self-discharge. Open the cabinet front door.
  2. Locate the CU320-2 module in the cabinet door, typically bottom-right. Identify the CF card slot with the orange/yellow ejector button.
  3. Press the ejector button. The old CF card will partially eject. Pull it straight out - do not angle.
  4. Insert the new 6SL3054-1CE00-1AA0 card with the label facing the same direction as the original. Push firmly until the ejector button clicks back into flush position.
  5. Close and latch the cabinet door. Restore line supply. Power up the cabinet.
  6. The CU320-2 will boot from a blank CF card into a safe state with default parameters and a "Commissioning required" prompt on the AOP30.
Warning: At this point the drive will not run the motor. It is in factory-default state. Do not attempt to start the motor until parameters have been restored.

4.3 Loading Firmware and Parameters

Use one of the following methods to put the new card back into service.

4.3.1 Method A: Restore from PG/PC Project Backup (preferred)

  1. Connect a PG/PC to the CU320-2 X127 service port or to X126 (PROFINET) on the cabinet. Set the PG to the same subnet (e.g., 169.254.11.22 with mask 255.255.0.0).
  2. Open STARTER. Open the project archive (.zap) that was backed up from the original drive.
  3. Go online to the CU320-2. Right-click the drive object and select Download to Target System. STARTER will push the project (parameters, BICO interconnections, fault settings) to the CU.
  4. Save the parameters to non-volatile memory with p0977 = 1 (or by clicking Copy RAM to ROM). This writes the parameter set to the new CF card.
  5. Cycle power one more time. The drive will boot with the restored parameters.

4.3.2 Method B: Card-to-Card Image Restore (if backup is on another identical card)

  1. If a sister drive's CF card is available and is the same firmware version, remove that card and use a CF card reader/writer to clone it with a tool such as Win32 Disk Imager or dd on Linux. Write the image to the new 6SL3054-1CE00-1AA0.
  2. Insert the cloned card into the G150 CU320-2. Power up. The drive will boot with the cloned parameters.
  3. Verify all parameters - especially license-dependent features (e.g., Safety Integrated, performance extensions) and the AOP30 layout block (p0700, p2051, etc.).

4.3.3 Method C: Re-commission from Default Parameters

If no project backup exists, the drive must be re-commissioned from scratch. Follow the G150 operating instructions in the SINAMICS G150 Operating Instructions manual entry on Siemens Product Support.

  1. Use the AOP30 to walk through quick commissioning: p0010 = 1, set motor data (p0300, p0301, p0304, p0305, p0307), encoder data if present, and application macro (p0500 or P1300). Verify with p3900 = 1 (calculate motor data and reset to factory).
  2. Save with p0977 = 1.
  3. Test in jog mode (p0010 = 0, then use the AOP jog key or STARTER control panel).

5. Verification Checklist After Replacement

After the new CF card is in service and parameters are restored, perform the following verification sequence before returning the drive to the process.

  1. Power-up the cabinet. Confirm the AOP30 displays normal operating screen - not the "Fatal error in drive: AOP stopped" message.
  2. Check the CU320-2 LEDs: RDY green steady, COM green/yellow blinking, OPT off.
  3. Read the diagnostic buffer (r0945[0..7]). Confirm no F01000/F01002/F01300 entries are present after the new card boot.
  4. Verify the firmware version displayed on the AOP30 startup screen matches the expected version (e.g., V5.2.3 HF1).
  5. Close the line contactor from the AOP30 (press RUN or the green ON key). Verify the contactor pulls in and the drive is in "Ready to Run" state (r899.0 / r899.1 indicators).
  6. Run a no-load motor test in jog mode at low frequency (5-10 Hz) for 30 s. Listen for abnormal noise; check motor rotation direction.
  7. Apply a closed-loop speed reference from the process controller. Ramp from 0 to 50 Hz over 30 s. Monitor output current and DC bus voltage on the AOP30 or STARTER trace.
  8. Trigger a controlled emergency stop (OFF1 / OFF3) and verify the drive decelerates and the line contactor opens as designed.
  9. Re-archive the project to the PG/PC with a timestamped filename (e.g., G150_S15037_2024-04-12_postCFreplace.zap). This protects against future media failure.
Critical step: Always re-archive the project after a CF card replacement. The new card's parameter set is the only surviving copy - lose it and the next fault will require a full re-commission.

6. Why This Fault Pattern Emerges in 250 kW Class Drives

The 250 kW class G150 is a common capacity point for process-line drives in cement, water, and metals handling. These installations share characteristics that accelerate CF card wear:

  • Cabinet ambient of 35-45 °C with limited HVAC conditioning.
  • Long mean-time-between-maintenance intervals (typically 12-24 months).
  • Frequent recipe changes (p0804 / p0805 parameter set switch) on batch processes, which trigger periodic parameter saves.
  • Use of a single CU320-2 with no redundant control, so the CF card is a single point of failure.

For new builds, Siemens has moved to SINAMICS G150 with CU320-2 PN and newer CF cards (6SL3054-1CE00-1AA0, 6SL3054-1CG00-2AA0) with higher-grade NAND and extended operating temperature. For existing fleets, a preventive replacement interval of 7-10 years is a reasonable benchmark.

7. Diagnostics and Fault Code Cross-Reference

The following table maps the most common fault codes that surface on the AOP30 in the "Fatal error in drive: AOP stopped" scenario, with the recommended action. All codes are read from r0947/r0949 in STARTER or the AOP30 fault history.

Fault Code (r0947) Meaning Typical Cause Recommended Action
F01000 Internal software error CU RAM error or corrupted boot image on CF Replace CF card 6SL3054-1CE00-1AA0
F01002 Internal software error during boot CF read failure on firmware load Replace CF card; verify with known-good card first
F01300 Invalid firmware on memory card CF card blank or wrong firmware branch Re-image CF card with correct firmware
F01018 Power-up aborted by user Power cycled during parameter save Power-cycle cleanly; check p0971 if persists
A05000 / A05001 Power unit overtemperature / warning Cabinet cooling failure, not CF related Check fans, filters, ambient temperature
F30611 DRIVE-CLiQ component defect Sensor Module or SMC failure, not CF Check DRIVE-CLiQ wiring; replace SMC/SME

For the specific case documented here, the G150 returned a single non-acknowledgeable fatal entry equivalent to F01000/F01002. A known-good CF card swap confirmed the original media as defective.

8. Preventive Maintenance Recommendations

To avoid recurrence of this fault, incorporate the following items into the site's PM program:

  1. Annual parameter archive: Back up the project to a managed PG/PC and to a network share. Compare r0954 (operating hours) and r0046 (missing enable signals) trend over the year to detect anomalies before they become faults.
  2. Cabinet environmental monitoring: Install a small temperature/humidity logger inside the cabinet. Keep ambient below 40 °C, humidity below 85 % non-condensing.
  3. Proactive CF card replacement at 7-10 years: Order a fresh 6SL3054-1CE00-1AA0 in advance. Schedule a 30-minute swap during a planned downtime window. Use the swap to verify the project archive and to re-tighten CU320-2 connections.
  4. Avoid forced power-downs during parameter save: After p0977 = 1, the CU320-2 writes to the CF card for 5-30 s. A power loss in this window can corrupt the file system. Add a UPS or a programmed delay between save and shutdown.
  5. Keep a spare CF card on the spares shelf, pre-imaged with the current firmware, so that a swap can be performed in <15 min without waiting on a parts order.

9. Related Components Worth Inspecting

When the CF card swap is complete, use the same maintenance window to inspect components that share the same root-cause theme (age, temperature, vibration):

  • CU320-2 backup battery: if present (some variants), a CR2032 lithium cell. Replace every 5 years to retain real-time clock through power-off.
  • AOP30 cable and connector: the RS-232 cable to the CU is a frequent point of intermittent fault. Inspect for kinks and pin oxidation.
  • Cabinet fans: confirm airflow is nominal. A failing fan raises the CF card's local temperature and accelerates media wear.
  • DRIVE-CLiQ cables: check that all connectors to TM31, SMC, and the Power Module are fully seated. A loose DRIVE-CLiQ connector can produce related but distinct symptoms (F30611).

10. Quick Reference: Part Numbers and Tools

Item Order Number / Version Notes
Replacement CF card (FW ≥ 4.6) 6SL3054-1CE00-1AA0 Primary recommended part
Replacement CF card (FW 2.x / 3.x) 6SL3054-1CE00-1BA0 For legacy G150 builds
CU320-2 DP Control Unit 6SL3040-1MA01-0AA0 PROFIBUS variant
CU320-2 PN Control Unit 6SL3040-1MA02-0AA0 PROFINET variant
AOP30 Advanced Operator Panel 6SL3055-0AA00-4BA0 Color display, multi-language
BOP20 Basic Operator Panel 6SL3055-0AA00-4HA0 2-line, lower cost option
STARTER commissioning tool V5.4 SP3 or later PC-side tool, supports G150/S120
Startdrive (TIA Portal) V15.1 or later Alternative to STARTER for TIA users
SIMOTION SCOUT (optional) V5.4 or later For motion/coordination projects

11. Field-Proven Caveats from the Source Case

The original 250 kW G150 took several days to resolve because the "Fatal error in drive: AOP stopped" message does not appear in the standard SINAMICS G150 fault list published in the operating instructions. Service technicians and even Siemens regional support had to reason by elimination. The key learning points from that case are reproduced here for future engineers:

  • The fault is not generated by the AOP30. The AOP is the messenger, not the cause. Replacing the AOP30 first wastes time and budget.
  • The fault is not a parameter issue. Acknowledging the fault with the AOP or with STARTER has no effect. The CU is in a permanent halt.
  • The fault is not cleared by a power-cycle. Only a media change brings the CU320-2 back to a bootable state.
  • The most efficient diagnostic path is to substitute a known-good CF card as the first step. If the drive boots with a spare, the diagnosis is complete in 5 minutes.
  • After the swap, treat the new card's parameter set as the only surviving copy until a project archive is re-created. Lose the archive and the next fault requires a full re-commission.
Bottom line for the field engineer: When a SINAMICS G150 shows "Fatal error in drive: AOP stopped" and the AOP is locked, the fix is almost always a CompactFlash card replacement with 6SL3054-1CE00-1AA0. Plan for a 30-60 minute total repair window, with the bulk of that time spent on parameter restoration rather than the card swap itself.

12. FAQ

What does "Fatal error in drive: AOP stopped" mean on a Siemens G150?

It means the CU320-2 Control Unit has hit a non-recoverable fault during boot, typically because it cannot read firmware or parameters from the CompactFlash card. The AOP30 is just displaying what the CU320-2 reported; the AOP itself is not the cause. The drive is locked and non-operational until the CU can complete a normal boot.

Which CompactFlash card part number is correct for a 250 kW G150?

For firmware versions ≥ 4.6, the recommended replacement is order number 6SL3054-1CE00-1AA0. For older G150 builds still on firmware 2.x or 3.x, use 6SL3054-1CE00-1BA0. Confirm the firmware version on the AOP30 startup screen or in STARTER before ordering the card - the two part numbers are not interchangeable.

Can I clear the fault with a power-cycle or with the FAULT-ACK key on the AOP30?

No. The fault is set by the CU320-2's boot-time exception handler and is not stored in the standard fault buffer. A power-cycle will re-attempt the boot and will fail again on the same error. The fault cannot be acknowledged from the AOP30 or from STARTER. Only replacing the underlying media (CF card) restores operation.

Do I need to re-commission the entire drive after replacing the CF card?

Not if you have a project archive (.zap file in STARTER) or a sister drive's CF card to clone. Push the project back to the CU320-2 via STARTER, then save with p0977 = 1. If no archive exists, you must walk through quick commissioning again - set motor data in p0300-p0307, run p3900 = 1, save with p0977 = 1, and verify direction and current draw.

How long should a CompactFlash card last in a SINAMICS G150 before preventive replacement?

Industrial CF cards in well-cooled cabinets typically last 8-10 years. Sites with cabinet ambient above 40 °C, frequent parameter saves (recipe handling via p0804), or uncontrolled power-downs should plan replacement at 7 years. Always keep a pre-imaged spare on the spares shelf so a swap can be done in <15 minutes during a planned downtime window.

Back to blog