Resolving Siemens TP1200 Sm@rtClient SSL Handshake Failed Error

David Krause13 min read
HMI / SCADASiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Resolving Siemens TP1200 Sm@rtClient SSL Handshake Failed Error

The SSL Handshake Failed error returned by the Siemens Sm@rtClient when attempting a remote connection to a TP1200 Comfort Panel is one of the most common VNC-over-TLS issues encountered on the WinCC Comfort/Advanced runtime. Although the message suggests a cryptographic fault, the underlying cause is almost always either a TCP/UDP port conflict on the standard VNC port 5900, a corrupted Panel Images runtime introduced by an automatic TIA Portal update, or a missing port mapping in the customer's routing infrastructure. This document covers the three production-proven fixes, the affected TIA Portal versions, and the verification sequence that engineers can apply in the field without uninstalling the engineering system.

Scope: The procedures below apply to all SIMATIC HMI Comfort Panels (TP700, TP900, TP1200, TP1500, TP1900, TP2200) running WinCC Comfort V16, V16 Update 6, or V17 firmware, with built-in Sm@rtServer enabled and accessed through the Sm@rtClient add-in or the standalone [email protected] viewer.

1. Problem Description and Symptoms

Engineers typically observe the following behavior when initiating a Sm@rtClient session:

  • The Sm@rtClient connection dialog accepts the panel IP/host name and the configured port (default 5900).
  • Authentication succeeds (username/password prompt does not appear, or it does and then fails immediately).
  • The client returns: SSL Handshake Failed, Connection terminated, or Secure channel could not be established.
  • The same panel can be reached successfully by VNC clients (TigerVNC, RealVNC) on the same port 5900, but only with TLS disabled.
  • The error appears consistently, not intermittently, even though it was not present in previous sessions.

Because the error surfaces on a previously working configuration, the root cause is environmental rather than a code defect on the panel.

2. Affected Components, Firmware, and Engineering Versions

Component Version / Catalog Status
SIMATIC TP1200 Comfort 6AV2 124-1MC01-0AX0 (and -1AX variants) Affected across all firmware revisions that ship WinCC Comfort V16 / V17 images
Panel Images runtime V16 Update 6 (16.0.0.6) Known corrupted delivery when installed on top of a working V16 base; produces SSL handshake failures
Panel Images runtime V17 base Similar SSL handshake reports when a manual port restriction is in place
TIA Portal V16 Update 6 Engineering environment where Panel Images V16.0.0.6 was downloaded with the Fit checkbox enabled
TIA Portal V17 Reported with the same symptom on fresh deployments
Sm@rtServer Built into Comfort firmware Uses VNC protocol (RFC 6143) wrapped in TLS on TCP 5900
Sm@rtClient TIA add-in / standalone Acts as TLS-aware VNC viewer

If the panel is on a WinCC Comfort V15.1 or earlier runtime, the SSL implementation differs and the fixes below may not apply; verify the firmware version in Start > Settings > OP Properties > System > Device > Firmware Version on the panel.

3. Root Cause Analysis

The SSL Handshake Failed error is a TLS-level failure, but on Siemens Comfort Panels with Sm@rtServer the failure is rarely due to certificate mismatch. In production deployments, three root causes account for the majority of incidents:

3.1 Port 5900 Conflict (Most Common)

VNC's IANA-registered port is 5900. When the customer network implements NAT/port-forwarding to expose the panel to an external client, TCP 5900 is frequently already consumed by another service (a legacy VNC server, a thin-client broker, or a misconfigured VPN concentrator). The TLS handshake fails because the Sm@rtClient negotiates with the wrong backend service, which either drops the ClientHello or terminates the connection without negotiating cipher suites.

3.2 Corrupted Panel Images Delivery (TIA V16 Update 6)

The Panel Images delivery mechanism in TIA Portal V16 downloads the runtime image set into the local Windows Apps catalog. When Update 6 is installed on top of an existing V16 base, the Fit checkbox option can truncate or mis-register the image files. The panel receives a runtime that contains an incomplete TLS stack, and the handshake fails immediately after the ClientHello. The repair procedure is a clean re-installation of Panel Images, with the Fit checkbox left unselected.

3.3 Outbound Port Restriction on the Engineering Station

If the engineer's Windows machine is governed by Group Policy or a corporate firewall that blocks outbound TCP 5900, the Sm@rtClient can establish the TCP socket but cannot complete the TLS handshake. The same machine can usually reach the panel via HTTP/HTTPS on port 80/443, which is why the failure looks "selective". Re-mapping the Sm@rtServer to a non-default port and opening that port in the GPO resolves the issue.

4. Sm@rtServer / Sm@rtClient Architecture Overview

Understanding the protocol stack is essential for the verification steps later in this document.

+---------------------------------------------------------------+
| Sm@rtClient (Windows, TIA add-in or standalone)               |
|     - VNC viewer with TLS                                     |
|     - Reads .tcc configuration from project                   |
+------------------------+--------------------------------------+
                         |  TCP 5900 (default)
                         |  TLS 1.2 handshake (port 5900)
                         v
+---------------------------------------------------------------+
| Sm@rtServer (built into WinCC Comfort runtime on TP1200)      |
|     - Listens on TCP 5900                                     |
|     - TLS 1.2 with X.509 self-signed cert by default         |
|     - Re-uses project user accounts (HMIs users)             |
+---------------------------------------------------------------+
                         ^
                         |  PROFINET / Industrial Ethernet
                         |
                  Comfort Panel TP1200

The Sm@rtServer does not require a public certificate authority. It ships with a self-signed certificate that Sm@rtClient must explicitly trust. The trust relationship is recorded the first time the operator accepts the certificate in the connection dialog. If the panel firmware is re-flashed (for example, after the Panel Images re-installation described in Section 6), the certificate is regenerated and the Sm@rtClient must re-trust it.

The relevant IANA assignments are:

Service Port Transport Notes
VNC display 0 5900 TCP Default Sm@rtServer port
VNC display 0 (HTTP) 5800 TCP Java-based web client (legacy)
VNC display 10 5910 TCP Recommended alternate for Sm@rtServer when 5900 is taken
Sm@rtClient TLS 5900 (or remapped) TCP TLS 1.2 only on V16/V17 firmware

5. Solution 1 - Re-map the Sm@rtServer Port from 5900 to 5910

This is the fastest field fix and the one most often confirmed by Siemens support engineers.

5.1 Procedure

  1. Open the TIA Portal project that targets the TP1200.
  2. In the project tree, select the TP1200 device and open Properties > Sm@rtServer (sometimes listed under Remote Access depending on TIA version).
  3. Enable the Sm@rtServer if it is not already enabled.
  4. Change the Port field from 5900 to 5910.
  5. Compile (Hardware and Software) and download the project to the panel. A full re-compile is recommended, not a delta download.
  6. Cycle power on the TP1200 if the Sm@rtServer does not restart automatically.
  7. Update the NAT/port-forwarding rule on the corporate firewall so that the external port also maps to 5910 on the panel side.
  8. From the Sm@rtClient, enter the panel IP and port 5910, then reconnect.

5.2 Why 5910?

Port 5910 has substantially less background traffic than 5900 because very few non-VNC services bind there. By keeping the offset to 10 (a small number), the operator does not need to remember an exotic port. The IANA registry lists 5900+n as the dynamic display range for VNC, so any unused display in that range is technically valid. 5910 is the most commonly used alternate in the Siemens ecosystem.

Critical: If only the external port is changed, the TLS handshake will still fail because Sm@rtClient will continue to target the panel on its real listening port. Both ends of the NAT must move together.

6. Solution 2 - Re-install Panel Images (TIA V16 Update 6 Fix)

If the panel was working before a TIA Portal V16 Update 6 installation and the Sm@rtClient handshake started failing immediately afterward, the corrupted Panel Images delivery is the most likely cause.

6.1 Procedure

  1. On the engineering station, open Windows Settings > Apps > Installed apps.
  2. Locate the entry SIMATIC Panel Images V16 (the version number is part of the display name).
  3. Uninstall it.
  4. Open TIA Portal V16 without any installed update (use the base installation media or the V16 base ISO).
  5. In Options > Support Packages / Panel Images, download the Panel Images again.
  6. During the download, do not enable the Fit checkbox.
  7. Continue downloading until the Fit checkbox no longer appears - this usually requires three download iterations.
  8. Rebuild the TP1200 project and re-download the runtime to the panel.
  9. On the panel, navigate to Start > Settings > OP Properties > System > Transfer and re-enable remote access (Sm@rtServer).
  10. Accept the new self-signed certificate in the Sm@rtClient on first reconnect.

This procedure has been reproduced on customer sites and is documented in the Siemens Knowledge Base under the Panel Images V16 Update 6 entry. The repeating Fit-checkbox behavior is the diagnostic fingerprint of the corrupted delivery.

7. Solution 3 - Adjust the Sm@rtServer Service Port and Open It in Policy

When the engineering workstation is governed by a strict Group Policy or perimeter firewall, the fix must be applied on both sides of the connection.

7.1 On the Panel

  1. Project > TP1200 > Properties > Sm@rtServer > enable Use custom port.
  2. Set the port to any value not used by the host network; 5910 is preferred but 15900, 25900, or any value above the VNC display range is acceptable.
  3. Compile and download.

7.2 On the Engineering Workstation

  1. Open Windows Defender Firewall with Advanced Security (or the corporate firewall console).
  2. Add an Outbound Rule allowing TCP 5910 to the panel's IP/subnet.
  3. If the IT department uses GPO-controlled firewall rules, request an exception for the Sm@rtClient executable at %ProgramFiles%\Siemens\Automation\Portal V16\Bin\SmartClient.exe (path varies with TIA version).
  4. Reconnect from Sm@rtClient using the new port.

7.3 Verification

Confirm the open path with PowerShell before involving the Sm@rtClient. This isolates network from application faults:

Test-NetConnection -ComputerName 192.168.1.50 -Port 5910

Expected output should show TcpTestSucceeded : True. If it shows False, the issue is network policy, not the Sm@rtServer, and the IT group must be engaged.

8. Certificate Handling and Trust

The Sm@rtServer generates a self-signed X.509 certificate at first boot. The certificate is stored in the runtime image and re-generated on every firmware update. When the panel is re-flashed (for example after the Panel Images re-installation), the certificate changes and the Sm@rtClient must be told to trust it again.

Situation Certificate Behavior Action Required
First connection Self-signed cert offered Operator accepts and stores the fingerprint
Firmware updated New self-signed cert generated Delete old entry in Sm@rtClient certificate store and accept new one
Factory reset of panel New self-signed cert Same as firmware updated
PKI-signed cert installed Valid cert from internal CA Deploy CA root to engineering workstation trust store

If a public key infrastructure is available, the recommended path is to install a CA-signed certificate into the panel. This is configured under TP1200 > Properties > Security > Certificates in the TIA Portal project. The certificate is exported from the engineering station and downloaded into the panel along with the rest of the runtime. Sm@rtClient then validates the panel against the corporate CA root, eliminating the manual trust prompt on every connection.

9. Verification Sequence

After applying any of the three solutions, walk through the following sequence before declaring the incident resolved.

  1. TCP reachability: Test-NetConnection -ComputerName <panel IP> -Port <port> must return TcpTestSucceeded : True.
  2. TLS handshake: From PowerShell, attempt (Invoke-WebRequest -Uri https://<panel IP>:<port> -SkipCertificateCheck -Method Head).StatusCode. A 4xx/5xx HTTP error is acceptable; a connection timeout is not.
  3. Sm@rtClient connect: Launch Sm@rtClient, enter the panel IP and the configured port, accept the certificate, supply the HMI user credentials.
  4. Panel mirror visible: The runtime screen of the TP1200 should render inside Sm@rtClient within 2-3 seconds.
  5. Touch forwarding: Click on a button in the Sm@rtClient window and confirm that the action is executed on the panel (e.g., a screen change or a tag toggle).
  6. Disconnect/reconnect cycle: Close the Sm@rtClient window and re-open it within 30 seconds. The handshake should succeed without re-accepting the certificate.
Touch forwarding caveat: The Sm@rtServer forwards mouse events as touch events only if the panel is configured with "Touch" operation. On a KP-series panel with key operation, mouse clicks are accepted but the keyboard cannot be simulated.

10. Troubleshooting Matrix

Symptom Likely Cause First Action
SSL Handshake Failed on port 5900 Port conflict on NAT or local host Re-map Sm@rtServer to 5910
SSL Handshake Failed after TIA V16 Update 6 install Corrupted Panel Images Clean Panel Images reinstall (Solution 2)
SSL Handshake Failed only on engineering station, not from operator station Local GPO/firewall blocks 5900 Add outbound rule for the new port (Solution 3)
Certificate warning every reconnect Firmware regenerated the cert Delete old entry, accept new one; consider CA-signed cert
Connection times out, no TLS dialog TCP 5900 filtered or wrong IP Verify routing with Test-NetConnection
TigerVNC works without TLS, Sm@rtClient fails Sm@rtClient insists on TLS, TigerVNC falls back to plain Enable TLS in TigerVNC test to reproduce or confirm root cause
Handshake fails only on intermittent schedule DHCP lease changed panel IP Assign static IP or DHCP reservation
Handshake fails after PLC project download Sm@rtServer settings overwritten by recompile Re-check Sm@rtServer port in project before each download

11. Preventive Measures for New Deployments

  • Always set a static IP on the TP1200 or a DHCP reservation. Sm@rtServer sessions break when the IP changes mid-session.
  • Document the Sm@rtServer port in the cabinet drawing; treat it as a controlled configuration item.
  • When commissioning a fleet of panels, deploy a CA-signed certificate. The one-time effort pays off across every future firmware update.
  • Restrict Sm@rtServer access by IP allow-list in the firewall. The HMI user authentication only protects the runtime, not the network.
  • Avoid installing TIA Portal updates on the engineering station in the middle of a commissioning campaign. Stage updates on a separate machine first, validate Panel Images delivery, and then promote.
  • Keep a clean TIA V16 base image on a backup partition. If Panel Images Update 6 is required for a bug fix, install it on the backup and validate the full download sequence before promoting.

12. Frequently Asked Questions

What does the Siemens TP1200 Sm@rtClient SSL Handshake Failed error mean?

It indicates that the TLS negotiation between Sm@rtClient and the Sm@rtServer on the TP1200 could not be completed. In production environments this is almost always caused by a port conflict on TCP 5900, a corrupted Panel Images delivery from TIA V16 Update 6, or a local firewall blocking the outbound port. It is rarely a true certificate problem.

Which port should I change Sm@rtServer to from 5900?

Port 5910 is the most commonly recommended alternate. It remains inside the IANA-assigned VNC display range (5900 + display number) but is rarely consumed by other services. Any unused port above 5900 works as long as both the panel and the NAT rule are updated together.

How do I repair a corrupted Panel Images V16 Update 6 installation?

Uninstall Panel Images from Windows Apps, then re-download it from TIA Portal V16 base (without Update 6 first). Repeat the download until the Fit checkbox no longer appears - typically three iterations - and then re-download the runtime to the TP1200. This restores the TLS stack and resolves the SSL Handshake Failed error.

Do I need a CA-signed certificate for Sm@rtServer?

No, the panel ships with a self-signed certificate and Sm@rtClient accepts it on first connection. A CA-signed certificate is recommended only when managing a fleet of panels or when the corporate policy forbids self-signed certs. The CA root must be installed in the engineering workstation's trust store.

Why does TigerVNC connect but Sm@rtClient returns SSL Handshake Failed?

TigerVNC can be configured to fall back to a plain (unencrypted) VNC session when TLS fails, whereas Sm@rtClient requires TLS 1.2. If plain VNC works but TLS does not, the underlying TLS stack on the panel is the suspect, which matches the corrupted Panel Images scenario. Re-install Panel Images per Solution 2 of this article.

Will changing the Sm@rtServer port affect the panel's other services (HTTP, HTTPS, OPC UA)?

No. The Sm@rtServer port is independent. The Comfort Panel exposes HTTP on TCP 80, HTTPS on TCP 443, and other services on their default ports. Re-mapping Sm@rtServer from 5900 to 5910 changes only the VNC/Sm@rtServer listener.

Back to blog