1. Problem Overview
On PCS 7 V8.2 systems (including V8.2 SPx updates) running a single AS (Automation Station) with a single OS (Operator Station) server, the WinCC Runtime periodically displays a "Simatic Net License" dialog at OS startup or when a connection is established. The same symptom appears on OS Single Station installations that combine the engineering and runtime role on one PC. The popup blocks the OS taskbar and may force the operator to acknowledge the dialog every reboot. Two architectural patterns trigger the issue most often:
- A single OS server with one AS and one or more S7 named connections.
- An OS Single Station (ES + OS) with a single AS and standard Ethernet interface.
2. Root Cause Analysis
The dialog is generated when the S7DOS / OPC / Named Connection service on the OS station requests a license that the ALM cannot resolve. The underlying reasons observed in field installations are:
- Wrong license type installed. The OS PC is using a Standard Ethernet interface (Intel/Broadcom/Realtek onboard NIC) but a SIMATIC NET IE HARDNET S7 or SOFTNET-S7 LEAN license is allocated. The correct license for a standard NIC is SIMATIC NET IE S7 Basic Communication Engine (BCE).
- No SIMATIC NET license transferred at all. Only the WinCC RT license is present in ALM, while S7 communication requires an explicit SIMATIC NET license.
- OS-RT Single Station license is not in ALM. The OS Runtime license must be transferred onto the same physical drive on which WinCC Explorer was started, otherwise the OS server cannot authenticate against the ALM during startup.
- Connection count exceeds the bundled limit. BCE and SOFTNET-S7 LEAN carry a cap (typically 8 S7 connections); additional named connections force the S7DOS to ask for an upgraded license key.
- License version mismatch. The license key on the ALM was generated for a different SIMATIC NET version (for example, a V13 key while the installed SIMATIC NET is V14) — the version stamp on the license does not match the runtime binary and the ALM rejects it.
- ALM service is not started. The Windows service "ALM" or "SLM" (older naming) is disabled, or its startup account lacks the local "Siemens TIA Engineer" or "SIMATIC HMI" group rights.
3. License Types and When to Use Each
Siemens bundles three license families for S7 communication from a PC station. Selecting the wrong family is the single most common root cause for the popup.
| License Name | Order Number (MLFB) | Required Hardware | Connection Limit | Typical Use Case |
|---|---|---|---|---|
| SIMATIC NET IE S7 BCE (Basic Communication Engine) | 6GK1 716-1CB00-0AA0 (BCE) and variants | Standard onboard Ethernet (any vendor NIC exposed as Windows adapter "IG_General") | Up to 8 S7 connections (bundle-dependent) | OS Single Station, single-server PCS 7 with standard NIC |
| SIMATIC NET IE SOFTNET-S7 LEAN | 6GK1 704-1LW00-0AA0 | Any standard Ethernet NIC (special adapters included) | Up to 8 S7 connections | OS server with non-Siemens, non-Intel server-grade NIC; small single-server plants |
| SIMATIC NET IE SOFTNET-S7 | 6GK1 704-1SW00-0AA0 | Standard Ethernet NIC | Up to 64 S7 connections | Mid-size OS server with multiple AS stations |
| SIMATIC NET IE HARDNET S7 | 6GK1 716-1EX01-0AA0 (single) / H variants for redundancy | CP 1613 / CP 1623 / CP 1628 (Siemens PCIe cards) | Up to 64 / 128 / H-redundant | H-system OS servers, redundant connection paths via "Redconnect" |
| SIMATIC NET IE HARDNET S7 REDCONNECT | 6GK1 716-1EX11-0AA0 (H variant) | Two CP 1623 or CP 1628 cards in redundant pair | Up to 128 redundant | PCS 7 H-station OS server with AS 410 H redundancy |
4. Network Adapter Classification
Open SIMATIC NET Configuration Console (Start » Siemens Automation » SIMATIC » SIMATIC NET » Configuration Console). The "Network adapters" tab lists every Windows NIC as one of the following:
- General IE — refers to a standard Windows NIC. Use BCE or SOFTNET-S7 LEAN.
- IE SOFTNET — Siemens Softnet driver binding. Requires SOFTNET-S7 LEAN or higher.
- IE HARDNET — Siemens CP 16xx PCIe card with HARDNET driver. Requires HARDNET-S7.
Misreading "General IE" as a Siemens hardware interface is a frequent commissioning mistake. Verify the adapter type before ordering a license.
5. Verifying the Automation License Manager (ALM)
ALM is the single source of truth for license allocation. Inspect it on the OS server:
- Start Automation License Manager from the desktop icon or
C:\Program Files\Siemens\Automation\License Manager\alm.exe. - Right-click the system drive (usually
C:\) and choose Connect target system » Local computer. - Expand the drive. Verify the following keys are present and unexpired:
-
WinCC RT (Single Station)orWinCC RT Server— depending on architecture -
SIMATIC NET IE S7 BCEorSIMATIC NET IE SOFTNET-S7 LEANorSIMATIC NET IE HARDNET S7 -
PCS 7 OS RTV8.2 license (matches the installed software version)
-
- Check the version stamp column. The version on the license key (for example "V14.0") must match the SIMATIC NET version installed. If the installed SIMATIC NET is V14.0 SP1 but the key says V13, the ALM cannot assign the key.
D:\PlantDocumentation\Licenses\ with timestamp. A red exclamation mark icon on a key indicates the ALM cannot validate the key for the current software — this is the exact icon shown when the popup appears.6. Checking the SIMATIC NET and ALM Windows Services
Both services must be running before WinCC starts the S7 channel:
-
ALM (Automation License Manager Service)— Startup type: Automatic, Status: Started -
SIMATIC NET Configuration Service— Startup type: Automatic, Status: Started -
S7DOS Help Service(S7DOS / S7-DOS) — Startup type: Automatic, Status: Started -
WinCC License Service— Startup type: Automatic, Status: Started
To restart safely from an elevated command prompt:
net stop "ALM"
net start "ALM"
net stop "SIMATIC NET Configuration Service"
net start "SIMATIC NET Configuration Service"
net stop "S7DOS"
net start "S7DOS"
7. Inspecting WinCC Named Connections
The number of S7 named connections in the WinCC project directly drives the SIMATIC NET licensing demand.
- Open WinCC Explorer on the OS server (or via remote ES).
- Right-click Tag Management and select the SIMATIC S7 PROTOCOL SUITE channel.
- Expand TCP/IP » Named Connections.
- Count the connections. If the count exceeds 8 and the installed license is BCE or SOFTNET-S7 LEAN, the S7DOS will demand an upgrade license (popup).
For a single-AS, single-OS PCS 7 V8.2 plant, one named connection is the typical minimum. Each redundant partner AS or each secondary AS adds another connection entry and consumes one connection slot from the bundle.
8. Resolving the Version Mismatch (V14 vs V13 License)
When the popup specifically requests a "v14 license" while the ALM only shows a "v13 license", the version stamp on the key is older than the installed SIMATIC NET runtime.
Resolution path:
- Confirm installed version: Help » About in the SIMATIC NET Configuration Console, or inspect
C:\Program Files\Siemens\Automation\SimaticNet\snetsns.inifor the build tag. - Request an upgrade license from Siemens via the License Key Generator (LKG) portal using the License Key Request form. The existing V13 key can be rehosted to the new V14 fingerprint.
- Alternatively, install the matching SIMATIC NET version (V13 SPx) that matches the available key. This is acceptable on PCS 7 V8.2 because SIMATIC NET V13 is still compatible as a downgrade path.
9. Step-by-Step Resolution Procedure
- Identify the OS station architecture: PC Station with BCE, PC Station with SOFTNET, or PC Station with HARDNET. Use the SIMATIC NET Configuration Console to confirm.
- Open ALM. Confirm an unexpired
SIMATIC NET IE S7 BCE(or higher) key is present and that the version stamp matches the SIMATIC NET runtime major version. - Confirm the
OS RT(orWinCC RT Single Station) license is present and on the same drive as the WinCC installation. - Count named connections in WinCC Explorer. If ≤ 8 and BCE is present, the popup should clear after the next OS reboot.
- If connections > 8, replace BCE with SOFTNET-S7 (up to 64 connections) or HARDNET-S7 (CP 16xx required).
- Restart the ALM service, the S7DOS service, and the WinCC Runtime in that order.
- Trigger a WinCC Runtime restart from WinCC Explorer: Computer » Properties » Start WinCC Runtime. Observe whether the popup reappears.
- If the popup persists, re-export the license key from the ALM, re-import it on the same drive, and reboot the OS server.
10. Verification Checklist
| Check | Expected State | Command / Path |
|---|---|---|
| ALM service running | Status: Started, Startup: Automatic | services.msc » ALM |
| S7DOS service running | Status: Started, Startup: Automatic | services.msc » S7DOS |
| BCE / SOFTNET / HARDNET key present | No red exclamation in ALM, version matches runtime | ALM » select drive |
| OS-RT license present | Tagged "In use" on the system drive | ALM » select drive |
| Named connection count ≤ license limit | Connections: 1…8 (BCE/LEAN), 1…64 (SOFTNET) | WinCC Explorer » Tag Management |
| Network adapter classified as General IE | Configuration Console » General IE | SIMATIC NET Configuration Console |
| No popup at OS startup | Clean WinCC taskbar, no SIMATIC NET dialog | Visual + Event Log » Application |
11. Troubleshooting Matrix
| Symptom | Likely Root Cause | Remediation |
|---|---|---|
| Popup says "SIMATIC NET license missing" | BCE / SOFTNET / HARDNET key not in ALM | Install the correct key family per the network adapter type |
| Popup says "v14 required, v13 found" | SIMATIC NET runtime newer than key | Rehost key to v14 or downgrade SIMATIC NET to v13 |
| Popup appears only with second AS connection | Connection limit of BCE (8) exceeded | Upgrade to SOFTNET-S7 or HARDNET-S7 |
| Popup on first boot of OS Single Station | OS-RT license not transferred to the local drive | Open ALM, transfer the OS-RT Single Station key to the system drive |
| Popup after a service pack update | License key SP-level lower than runtime | Request a rehosted key from Siemens with the correct SP stamp |
| Popup recurs every 2 hours | ALM service enters recovery when S7DOS retries | Stop S7DOS, stop ALM, restart ALM, then start S7DOS |
| Popup in redundant OS server pair | REDCONNECT license missing or only one CP 16xx installed | Install two CP 1623/1628 cards and the REDCONNECT license |
12. Special Case: Redundant OS Servers (H-System)
If the plant later migrates to a redundant AS 410 H architecture, the OS server must also be configured for connection redundancy. The single OS station using BCE is no longer sufficient. Re-license as follows:
- Install a CP 1623 or CP 1628 PCIe card in each OS server (two NICs in total per server for the S7 channel).
- Bind the cards in SIMATIC NET Configuration Console as IE HARDNET.
- Allocate the SIMATIC NET IE HARDNET S7 REDCONNECT license (MLFB
6GK1 716-1EX11-0AA0for H variant). - Configure two named connections per AS in WinCC Explorer — one for each physical path.
The HARDNET S7 license (non-redundant) is intended for H-system topologies but with single-path configuration; the REDCONNECT variant enables WinCC to switch the connection transparently when one AS rack fails. The license model is version-specific to the CP card family and the SIMATIC NET version, so always re-verify with the Siemens Industry Online Support manual corresponding to the deployed SIMATIC NET version.
13. Notes on PCS 7 V8.2 and Cemat V8.2 Library
The Cemat V8.2 mining/cement library is a superset of PCS 7 V8.2 and inherits its licensing rules. The Cemat OS server still requires a separate WinCC RT Server license in addition to the OS RT license of PCS 7. If both OS servers (PCS 7 main + Cemat) coexist on the same machine, count both sets of named connections against the SIMATIC NET bundle limit. A Cemat OS with eight PCS 7 connections plus four Cemat-specific connections will exceed the BCE 8-connection bundle.
For multi-server Cemat installations, plan for SIMATIC NET IE SOFTNET-S7 (64 connections) or HARDNET-S7 (CP-based) to avoid the popup at first OS activation.
14. Long-Term Hardening
- Document the license stack in the plant's System Manual and link the ALM export PDF to the document control system.
- Add an OS server health check that verifies the ALM, S7DOS, and WinCC services are running before the OS enters production. Siemens PCS 7 Maintenance Station can monitor these services and raise a "License not available" alarm.
- Subscribe to Siemens Industry Online Support notifications for the SIMATIC NET version in use, so version-mismatch popups are addressed before a planned OS upgrade.
- Re-verify the connection count after every AS or OS project migration. Every added S7 connection consumes one slot in the license bundle.
15. Frequently Asked Questions
Which SIMATIC NET license is correct for a single OS server with a standard Ethernet NIC?
Use the SIMATIC NET IE S7 BCE (Basic Communication Engine) license, MLFB 6GK1 716-1CB00-0AA0. It supports up to 8 S7 named connections and is the minimum-cost choice for an OS Single Station or single-OS-server PCS 7 V8.2 plant that uses the Windows onboard NIC as a "General IE" interface.
Why does the popup say "v14 required" when the ALM shows a v13 license?
The ALM binds a license key to the SIMATIC NET runtime major version. A v13 key cannot be assigned to a v14 runtime. Either request a rehosted v14 key from Siemens via the License Key Generator portal, or downgrade the SIMATIC NET installation to v13 SPx to match the available key. PCS 7 V8.2 supports both SIMATIC NET v13 and v14.
How many named connections does the BCE license allow?
The BCE bundle allows up to 8 S7 named connections. When the WinCC project exceeds 8, upgrade to SIMATIC NET IE SOFTNET-S7 (64 connections) for standard NICs, or to HARDNET-S7 (64 / 128 connections) when a Siemens CP 16xx PCIe card is installed.
Do I need the HARDNET S7 license for a non-redundant single-server PCS 7 V8.2 system?
No. HARDNET S7 is required only when the OS server uses a Siemens CP 1613, CP 1623, or CP 1628 PCIe Communication Processor. For standard onboard Ethernet or any third-party NIC exposed as "General IE", the BCE or SOFTNET license is sufficient. HARDNET S7 REDCONNECT is needed only for redundant AS 410 H configurations.
What should I check first when the Simatic Net License popup appears at OS startup?
Open the Automation License Manager and verify (1) a SIMATIC NET license key is transferred to the system drive, (2) the key's version stamp matches the installed SIMATIC NET runtime, (3) the OS-RT or WinCC RT Single Station license is present, and (4) the ALM, S7DOS, and WinCC License Windows services are all in the "Started" state. This sequence resolves more than 90% of field popups on PCS 7 V8.2.
Does the Cemat V8.2 library change the SIMATIC NET licensing rules?
No. Cemat V8.2 inherits PCS 7 V8.2 licensing. However, it adds additional named connections for Cemat-specific tags. If a Cemat OS already uses 4–5 Cemat connections, only 3–4 PCS 7 connections remain inside the BCE 8-connection limit. Plan for SOFTNET-S7 or HARDNET-S7 to avoid the popup at OS activation.
Can the ALM be running but the S7DOS service stopped, and still cause the popup?
Yes. The S7DOS service is the S7 communication dispatcher. If it is stopped or in a recovery state, the S7 channel in WinCC will fail to bind a license even if ALM is healthy, and the popup is raised by the WinCC channel handler. Restart ALM first, then S7DOS, then WinCC Runtime in that order to clear the state.