Resolving SIMOTION Scout V5.3 Internal Error During Project

David Krause11 min read
Motion ControlSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Resolving SIMOTION Scout V5.3 Internal Error During Project Creation

The "An Internal Error Occurred while creating a new project. 19" message in SIMOTION SCOUT V5.3 is a recurring engineering-side defect that prevents both the creation of new projects and the opening of legacy SCOUT projects (V4.x, V5.1, V5.2 SP1). The fault originates inside the project database layer that SCOUT uses to persist device topology, technology objects, and program containers, and is not a motion-control runtime error. This reference covers root cause, supported configurations, the mandatory Microsoft Access Database Engine fix, and the verification steps required to clear the dialog from the workbench.

Scope: SIMOTION SCOUT V5.3 and V5.3 SP1 engineering environment on Windows 7 64-bit, Windows 10 64-bit, and Windows Server 2008 R2. The procedures apply to standalone SCOUT installations and to SCOUT integrated with STEP 7 V5.5 + SPx.

1. Problem Description

When an engineer launches SCOUT V5.3 and attempts either of the following actions, the application raises an unhandled exception and aborts:

  • File > New Project — creates a blank SCOUT project on the local session.
  • File > Open — opens an existing SCOUT project (any prior version).
  • File > Open with SIMOTION device set — opens a project containing a SIMOTION controller such as D425, D435, D445, D455, or P320.

The full error chain presented by the IDE is:

An Internal Error Occurred while creating a new project. 19
Siemens SIMOTION Diagnostic
The Application has a problem and needs to close.

The numerical suffix (19) corresponds to a JET / ACE database provider failure code rather than a SIMOTION runtime fault code. It is emitted by the Microsoft OLE DB provider when SCOUT's project back-end cannot bind to the expected ACE engine. After the dialog is dismissed, the IDE terminates and any unsaved work in the open session is lost.

2. Affected Versions and Environments

Component Versions Known to Exhibit the Error Verified Resolved In
SIMOTION SCOUT V5.1, V5.2 SP1, V5.3, V5.3 SP1 V5.3 SP1 Hotfix + ACE 2010 Redistributable
SIMOTION SCOUT TIA V5.4 (in TIA V16+) Not affected when SCOUT V5.4 is bundled
STEP 7 V5.5 + SP1 .. SP4 Independent of STEP 7 patch level
Microsoft Office 2007, 2010, 2013, 365 (x86 or x64) Trigger when Office bitness does not match ACE engine
Operating System Windows 7 SP1 x64, Windows Server 2008 R2, Windows 10 x64 Windows 10 1909+ with ACE 2010 x64
Microsoft Access Database Engine 2007 Redistributable, 2010 Redistributable, ACE 16 2010 Redistributable x86 + x64 both installed
Observation: The error is consistently reported on Windows 7 64-bit engineering stations with SIMOTION SCOUT V5.3 SP1. It is not platform-dependent — Windows 10 x64 installations with mismatched ACE engine also reproduce the fault.

3. Root Cause Analysis

3.1 SCOUT Project Database Back-End

SIMOTION SCOUT persists the project structure (devices, technology objects, programs, libraries, connections) in a Jet / ACE database (file extension .sdf or proprietary SCOUT project files). When the user creates or opens a project, SCOUT loads the Microsoft OLE DB provider for ACE:

Provider=Microsoft.ACE.OLEDB.12.0;Data Source=<project.sdf>;

If the provider is missing, mis-registered, or registered only in a bitness the SCOUT process cannot load, the provider binding fails and SCOUT surfaces the generic internal error 19 instead of a meaningful provider message.

3.2 Bitness Mismatch Trigger

The most frequent cause is a bitness mismatch between:

  1. The installed Microsoft Office suite (32-bit Office installs the 32-bit ACE engine).
  2. The SCOUT executable (always 32-bit in V5.3 SP1, even on 64-bit Windows).

If 64-bit Office (or the 64-bit ACE 2010 redistributable) is installed and a 32-bit SCOUT process attempts to bind to the OLE DB provider, the COM activation fails with E_CLASSNOTREG / 0x80040154. SCOUT catches this and re-raises the diagnostic as internal error 19.

3.3 Legacy Project Schema Corruption

Projects originally created in SCOUT V4.x or V5.1 may carry forward schema elements (CAM technology object extensions, path interpolation blocks, safety integrated configuration data) that are partially migrated when opened in V5.3. If the migration handler cannot write to the local session because the ACE provider is unavailable, the partial migration writes corrupt records that propagate into subsequent File > New Project attempts until the local working directory is cleaned.

3.4 Missing Administrator Privileges

SCOUT V5.3 writes user-specific project templates to %APPDATA%\Siemens\Automation\SCOUT\<version> and registers COM components on first launch. Without Run as administrator, the COM registration is incomplete on locked-down engineering stations, leading to intermittent project creation failures.

4. Resolution Path Summary

Priority Action Expected Outcome Effort
1 Install Microsoft Access Database Engine 2010 Redistributable (matching SCOUT bitness, x86) Eliminates OLE DB provider binding failure 5 min
2 Run SCOUT with administrator privileges Completes COM registration 1 min
3 Clear SCOUT local working directory Removes partial-migration artifacts 5 min
4 Re-register ACE OLE DB provider via regsvr32 Forces COM re-activation 2 min
5 Repair/reinstall SCOUT V5.3 SP1 with Microsoft hotfix package Re-applies SCOUT binaries and SCOUT-specific ACE shims 30 min

5. Step-by-Step Resolution Procedure

5.1 Prerequisites

  • Local administrator account on the engineering station.
  • Microsoft Access Database Engine 2010 Redistributable download (both AccessDatabaseEngine.exe for x86 and AccessDatabaseEngine_X64.exe if 64-bit Office is present).
  • SIMOTION SCOUT V5.3 SP1 installation media (DVD, hard-drive image, or SCADA/PLM download portal access).
  • Internet access for Microsoft redistributable downloads and Siemens support entry 109476578.

5.2 Install the Access Database Engine 2010 Redistributable

  1. Close all Office applications (Outlook, Excel, Word, Access, OneNote).
  2. Close any running instance of SCOUT, STEP 7, and SIMATIC Manager.
  3. Determine the bitness of the local Office installation: File > Account > About Word — record whether it shows (32-bit) or (64-bit).
  4. Download Microsoft Access Database Engine 2010 Redistributable from Microsoft Download Center (ID 13255).
    • If Office is 32-bit, install AccessDatabaseEngine.exe (x86).
    • If Office is 64-bit, install AccessDatabaseEngine_X64.exe (x64), then also install the x86 redistributable in a side-by-side configuration using the /quiet switch:
AccessDatabaseEngine.exe /quiet
Why both engines? SCOUT V5.3 is a 32-bit process. Even on a 64-bit Windows host with 64-bit Office, SCOUT cannot load the 64-bit ACE OLE DB provider; the 32-bit engine must be present so that the SCOUT process can bind to Microsoft.ACE.OLEDB.12.0.
  1. Verify installation. Open Control Panel > Programs and Features and confirm Microsoft Access Database Engine 2010 (English) appears for the installed bitness.

5.3 Re-register the ACE OLE DB Provider

  1. Open an elevated Command Prompt (Run as administrator).
  2. For 32-bit provider on a 64-bit OS, execute:
cd "C:\Program Files (x86)\Common Files\Microsoft Shared\OFFICE14\"
regsvr32 /u oledb32.dll
regsvr32 oledb32.dll
regsvr32 /u msjetoledb40.dll
regsvr32 msjetoledb40.dll
  1. Confirm both registrations return DllRegisterServer in <file> succeeded.
  2. Launch dcomcnfg and verify that the Microsoft OLE DB Provider for ACE 12.0 is listed under Component Services > Computers > My Computer > DCOM Config.

5.4 Clear the SCOUT Local Working Directory

  1. Close SCOUT.
  2. Navigate to %LOCALAPPDATA%\Siemens\Automation\SCOUT\<version>\workspace and %APPDATA%\Siemens\Automation\SCOUT\<version>.
  3. Move the contents (not the folders) to a backup directory. This removes partial-migration artifacts from old V5.1 / V5.2 projects.
  4. Empty the Windows TEMP directory: %TEMP%\Siemens\*.

5.5 Launch SCOUT as Administrator

  1. Right-click SIMOTION SCOUT in the Start menu.
  2. Select Run as administrator.
  3. Confirm the UAC prompt.
  4. SCOUT completes the COM activation and writes the project template seeds to the user profile.
Persistent elevation: To avoid repeating this step, edit the SCOUT shortcut > Properties > Compatibility > Run this program as an administrator. On controlled engineering stations, deploy this setting via Group Policy Preferences > Shortcuts.

5.6 Apply the SCOUT V5.3 Hotfix

If the Access Database Engine installation does not resolve the fault, install the SCOUT V5.3 SP1 HF update referenced in Siemens support entry 109476578. The hotfix replaces the SCOUT-internal project back-end bindings and re-registers the SIMOTION-specific OLE DB extensions.

6. Verification

After applying the resolution steps, validate the fix with the following checks:

  1. Create Project Test: Launch SCOUT, choose File > New Project, name the project VERIFY_SCOUT_V53, and confirm the device insert wizard opens without raising internal error 19.
  2. Open Project Test: Open a previously corrupted V5.1 or V5.2 project. SCOUT should display the migration dialog and complete the schema upgrade without terminating.
  3. Offline/Online Test: Insert a SIMOTION D435 device, download the empty project to the controller in STOP / startup mode, and confirm the device goes online (PROFINET or PROFIBUS depending on topology).
  4. Technology Object Test: Insert a SINAMICS_Integrated axis with a TO_SpeedAxis object and a TO_Cam object. Compile and confirm the technology package generates without errors.
  5. Diagnostic Log: Inspect SCOUT > Project > Diagnostics > Event Log and verify no OLE DB provider or ACE errors are recorded.
Verification Step Pass Criterion Failure Action
File > New Project Project wizard opens Repeat §5.3 regsvr32
Open legacy V5.2 project Migration completes Re-import project, check .sdf integrity
Insert SIMOTION D4xx device Device appears in project tree Repair SCOUT install
Compile technology objects Build succeeds with 0 errors, 0 warnings Re-install technology packages
Online connect to controller Online tab populates Check PROFINET/PROFIBUS topology

7. Preventive Measures and Configuration Hardening

7.1 Standardise ACE Engine Deployment

Deploy both the x86 and x64 Access Database Engine 2010 Redistributable via Group Policy Software Installation or a managed software deployment tool such as Siemens SIMATIC Automation Tool or Microsoft Endpoint Configuration Manager. This guarantees that SCOUT can bind to the provider regardless of the local Office bitness.

7.2 Use SCOUT TIA Bundle for New Projects

For new installations, prefer SIMOTION SCOUT V5.4 integrated in TIA Portal V16 or later. The TIA Portal back-end does not depend on the legacy ACE OLE DB provider and avoids the bitness issue altogether. Reference the TIA Portal Possible error messages during check-in documentation for related team-engineering diagnostics.

7.3 Project Hygiene

  • Always perform Project > Save As with explicit version increment; avoid opening the same project in SCOUT V5.3 and SCOUT TIA simultaneously.
  • Run Project > Check Consistency before closing SCOUT to detect schema drift early.
  • Maintain the engineering station using the Siemens SIMATIC Automation Tool image to keep ACE, SCOUT, and technology package versions synchronised.

7.4 Bitness Audit Script

Run the following PowerShell snippet on each engineering station to verify ACE engine presence and bitness alignment:

$office = (Get-WmiObject -Class Win32_Product | Where-Object { $_.Name -like "*Office*" } | Select-Object -First 1).Name
$ace32  = Test-Path "HKLM:\SOFTWARE\WOW6432Node\Microsoft\Office\14.0\Access Connectivity Engine"
$ace64  = Test-Path "HKLM:\SOFTWARE\Microsoft\Office\14.0\Access Connectivity Engine"
Write-Host "Office : $office"
Write-Host "ACE x86 present : $ace32"
Write-Host "ACE x64 present : $ace64"
if (-not $ace32) { Write-Warning "Install AccessDatabaseEngine.exe (x86) for SCOUT V5.3." }

8. Troubleshooting Matrix

Symptom Likely Cause Resolution
Internal error 19 on New Project ACE provider missing or wrong bitness Install ACE 2010 x86 (§5.2)
Internal error 19 on Open Project Legacy schema corruption Clean workspace (§5.4) then re-open
Internal error 19 after Office update Office upgrade replaced ACE registration Re-run ACE 2010 install in /quiet mode
Application closes immediately on launch COM registration incomplete Run SCOUT as administrator (§5.5)
Same error persists after ACE install Antivirus blocking COM activation Add %ProgramFiles%\Siemens\Automation to AV exclusions
Error only on multi-user server projects TIA Portal check-in conflict Review TIA check-in error reference
Error when opening V4.5 project V4.x schema migration unsupported in V5.3 Open in V5.2 first, save, then open in V5.3
Error after Windows update .NET or VC++ redistributable updated Repair SCOUT install via Control Panel

9. Related Siemens Support Entries

10. Field-Proven Caveats

  1. Do not install ACE 16 alongside ACE 2010 without testing. ACE 16 changes the default OLE DB provider priority and may re-trigger the same error in SCOUT V5.3 SP1.
  2. Avoid side-by-side Office 32-bit and 64-bit installations. This is not officially supported by Microsoft and produces intermittent ACE provider failures that look identical to internal error 19.
  3. SCOUT V5.3 SP1 Hotfix 1+ is cumulative. Always install the latest HF package — partial hotfix applications can leave the SCOUT-ACE shim in an inconsistent state.
  4. Engineering station images must include ACE 2010. When capturing Windows images with Microsoft Deployment Toolkit or similar tools, add the ACE redistributable as a post-deployment task to avoid re-imaging hundreds of stations.

What does internal error 19 mean in SIMOTION SCOUT V5.3?

Internal error 19 is a SCOUT-side database provider failure. The IDE cannot bind to the Microsoft ACE OLE DB provider required to read and write the SCOUT project file. It is not a SIMOTION runtime fault code and is unrelated to the motion control application.

Which Microsoft Access Database Engine version do I install for SCOUT V5.3?

Install the Microsoft Access Database Engine 2010 Redistributable (download ID 13255). Always install the x86 build because SCOUT V5.3 SP1 is a 32-bit process; if 64-bit Office is present on the engineering station, install the x64 build first, then the x86 build using /quiet.

Do I need to upgrade to SCOUT V5.4 in TIA Portal to avoid this error?

No. Installing the Access Database Engine 2010 x86 redistributable and running SCOUT with administrator privileges is sufficient for V5.3 SP1. However, for new projects, SCOUT V5.4 in TIA Portal V16+ removes the ACE dependency entirely and is the recommended forward path.

Why does the error appear after installing or updating Microsoft Office?

Office installers re-register the ACE OLE DB provider in their own bitness. If Office bitness does not match SCOUT's 32-bit requirement, SCOUT cannot load the provider and raises internal error 19. Re-run the ACE 2010 redistributable that matches SCOUT bitness to restore the binding.

Can I open a SCOUT V4.5 project directly in V5.3?

No. SCOUT V5.3 cannot migrate V4.x schema directly. Open the project in SCOUT V5.2 first, perform a Project > Save As, then open it in V5.3. If the V5.2 install is unavailable, request a project conversion from your Siemens representative or use the SCOUT project migration tool supplied with V5.3 SP1 Hotfix 1.