Resolving SINAMICS S120 F01360 Topology Error on CU320-2 DP

David Krause12 min read
SiemensTroubleshootingVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

1. Problem Statement: F01360 on SINAMICS S120 CU320-2 DP

The fault F01360 is reported by a SINAMICS S120 control unit CU320-2 DP (MLFB 6SL3040-1MA00-0AA0) when the controller is powered up with a DRIVE-CLiQ topology that does not match the expected (commissioned) topology. The fault appears immediately after the control unit boots, even with a clean CompactFlash card and no project loaded, and it persists through normal power cycles.

In a typical field occurrence, the following devices are connected to the CU320-2 DP via DRIVE-CLiQ:

  • Control Unit: 6SL3040-1MA00-0AA0 (CU320-2 DP)
  • Active Line Module (Smart Line / Active Line): 6SL3310-1TE35-0AA3 (or the related -0AA0 variant)
  • Sensor Module or Terminal Module: 6SL3055-0AA00-2TA0
  • Optional Communication Board / CF card: 6SL3054-0ED00-1BA0 upgraded to firmware 4.5 / 4.7

When all three DRIVE-CLiQ devices are present, the control unit reports F01360 and the drive will not enter Run state. Disconnecting the Line Module removes the fault, which confirms the Line Module is the trigger component.

Important: F01360 in this scenario is not a firmware bug, a missing license, or a defective CompactFlash card. It is a hardware-level topology mismatch between the Line Module part-number suffix and the CU320-2 DP firmware acceptance table.

2. F01360 Fault Definition and Value (r949)

F01360 belongs to the SINAMICS S120 fault class "Topology / component assignment errors". The fault is raised by the control unit during topology comparison and indicates that the actual DRIVE-CLiQ topology seen on the ports differs from the target topology stored on the CompactFlash card or in the project.

The supplementary fault value is stored in parameter r949 (fault value). Decoding r949 for F01360 follows the standard SINAMICS fault-value convention: it contains an index that points to the affected DRIVE-CLiQ node, the port number, and a reason code identifying the type of topology violation. Always read r949 before clearing the fault so the offending component is positively identified.

Typical r949 sub-reasons in this fault class include:

  • 1 – Component at this DRIVE-CLiQ node not equal to target
  • 2 – Topology comparison: component type differs
  • 3 – Topology comparison: component MLFB / hardware revision not accepted by current firmware
  • 4 – Topology comparison: component connected but not configured (or vice versa)
The exact sub-reason dictionary is firmware-dependent. With V4.5 / V4.7 the index encoding may be combined with the DRIVE-CLiQ port number; cross-check against the SINAMICS S120 List Manual (LH1) parameter description for r949 in your firmware version.

3. Affected Hardware and Part-Number Suffix

The root cause of the F01360 in this case study is the MLFB suffix of the Active Line Module. The 6SL3310-1TE35-0AAx family exists in at least two hardware revisions, identifiable by the final suffix:

MLFB Hardware Notes
6SL3040-1MA00-0AA0 CU320-2 DP Control unit (basic variant)
6SL3040-0MA00-0AA0 CU320-2 DP Control unit (alternate variant)
6SL3310-1TE35-0AA0 Active Line Module, suffix 0AA0 Earlier hardware revision
6SL3310-1TE35-0AA3 Active Line Module, suffix 0AA3 Later hardware revision, fully released for V4.5 / V4.7
6SL3055-0AA00-2TA0 SMC30 / Sensor Module Cabinet-Mounted Encoder evaluation module
6SL3054-0ED00-1BA0 COMM BOARD / CF card adapter Optional, firmware 4.5 / 4.7 tested

The final 4-character suffix encodes the hardware revision, feature level, and release matrix of the module. A CU320-2 DP running firmware V4.5 / V4.7 has an internal allow-list of which Line Module suffixes it will accept in a given DRIVE-CLiQ port. If the connected Line Module's suffix is not on the allow-list, the topology comparison fails and F01360 is reported.

4. Compatibility Matrix Observed in the Field

The following combinations have been observed on a working test bench with firmware V4.5 / V4.7:

Control Unit Line Module Result
6SL3040-1MA00-0AA0 6SL3310-1TE35-0AA3 OK – no F01360
6SL3040-1MA00-0AA0 6SL3310-1TE35-0AA0 NOT OK – F01360 raised
6SL3040-0MA00-0AA0 6SL3310-1TE35-0AA3 OK – no F01360

From this matrix the line of demarcation is the Line Module suffix combined with the CU320-2 DP variant 1MA. The -0AA0 suffix on the Line Module is not accepted by the 1MA CU320-2 DP at firmware V4.5 / V4.7, while the -0AA3 suffix is accepted. The control unit variant 0MA accepts the -0AA3 Line Module as well.

5. Root Cause Analysis

F01360 in this configuration is a DRIVE-CLiQ topology component-mismatch fault, not a configuration or licensing fault. The firmware of the CU320-2 DP performs a hardware-compatibility check during power-up, comparing the MLFB and hardware revision of every connected DRIVE-CLiQ device against the version of the control unit. The check has three outcomes:

  1. Component found in target topology and hardware accepted → no fault.
  2. Component found, MLFB matches the family, but hardware suffix is not in the firmware allow-list → F01360.
  3. Component missing or not in target topology → F01350 (component missing) or F01360 (depending on reason).

Common contributors that produce the same fault signature and should be excluded first:

  • Wrong / corrupt CompactFlash card – a clean card with no project reproduces the fault, which proves the project is not the cause. A correct, freshly formatted CF card is therefore not the fix.
  • Missing license – license errors raise F13000-class faults, not F01360.
  • Firmware mismatch on the COMM BOARD / SMC30 – would raise F01350 / F01357 on the specific node, not a general topology error.
  • DRIVE-CLiQ cable defect – a defective cable prevents the control unit from reading the component and the node shows as missing, not mismatched.

Once those are eliminated, the only remaining cause is hardware-revision compatibility between the CU320-2 DP and the Line Module.

6. Pre-Work: What to Capture Before Power-Down

Before swapping modules or re-commissioning, capture the following so the repair is fully documented:

  1. Read the active fault buffer with r949 and write down the fault value.
  2. Read the alarm buffer (r2122) for any associated warnings such as A01360, A01350, A01357.
  3. Read the actual topology from the CU320-2 DP: r0098[0] (Control Unit order number / MLFB), and the device-identification parameters for every connected DRIVE-CLiQ node (r9781, r9782, r9785 for the Line Module).
  4. Photograph the affected Line Module nameplate; record the full MLFB including suffix and the serial number.
  5. Verify the firmware version on the control unit: r0018 (firmware version) and r9925 (firmware build).

7. Step-by-Step Resolution Procedure

Use the following sequence to clear F01360. Each step is verified before proceeding.

7.1 Confirm Topology in STARTER / SINAMICS Startdrive

  1. Connect a PG / PC to the CU320-2 DP service interface (X127) or to PROFIBUS / PROFINET.
  2. Open STARTER (legacy, recommended for V4.x) or SINAMICS Startdrive in TIA Portal.
  3. Go online with the drive unit. Accept any topology mismatch prompts.
  4. Open Drive Unit > Topology. The right-hand pane shows the actual topology detected by the control unit, the left-hand pane shows the target topology from the project / CF card.
  5. Note the MLFB of the Line Module on the actual side. If the suffix on the actual Line Module is -0AA0 and the firmware on the CU is V4.5 / V4.7, the topology will be highlighted red on the actual side and F01360 is the expected reaction.

7.2 Check the Allow-List and Replace the Line Module

  1. Compare the actual Line Module MLFB suffix against the compatibility matrix in section 4.
  2. If the actual suffix is -0AA0 on a CU320-2 DP 1MA at firmware V4.5 / V4.7, the supported suffix is -0AA3.
  3. Replace 6SL3310-1TE35-0AA0 with 6SL3310-1TE35-0AA3. Confirm the full MLFB on the nameplate before mounting.
  4. Reconnect the DRIVE-CLiQ cables exactly as before, paying attention to the port order: CU320-2 DP port X200 typically goes to the Line Module.

7.3 First Power-Up with New Line Module

  1. Power up the control unit. The actual topology in STARTER should now show 6SL3310-1TE35-0AA3 at the Line Module slot.
  2. Read r949 – the F01360 should be replaced by a message indicating a new component has been detected, typically A01360 "Topology comparison: component inserted" or a similar alert.
  3. Acknowledge the fault, then perform a full topology commissioning (see section 8).

7.4 Fallback: Revert to a Compatible CU320-2 DP

If replacing the Line Module is not possible, the alternative path is to swap the control unit so the combination falls inside the allow-list. The matrix in section 4 shows that the 0MA variant of the CU320-2 DP accepts the -0AA3 Line Module. If the Line Module must remain at -0AA0, identify a CU320-2 DP firmware / variant that has it on its allow-list, or downgrade the control-unit firmware to a revision that includes -0AA0.

Downgrading firmware is a last resort and may disable features. Always back up the current project and the CF card before any firmware change.

8. Commissioning After Module Replacement

  1. With the new Line Module in place, perform Commissioning > Automatic configuration from STARTER / Startdrive. This step reads the actual topology and writes it as the new target topology.
  2. Verify the new target topology matches the actual topology: p9906 = 0 (target = actual) after the automatic configuration runs.
  3. If the project on the CF card contains a manual topology that no longer matches, reissue a factory reset of the control unit: p0976 = 1 followed by power cycle. This clears all parameters, the topology, and the fault buffer. Reload the project from PG/PC afterwards.
  4. Run the drive system identification: p1910 = 1 (motor identification) and p1960 = 1 (speed-controller optimization) on the active motor module.
  5. Save the project to the CF card: p0977 = 1 (save all parameters to non-volatile memory).

9. Verification Checklist

Use the following table to confirm F01360 is fully resolved and the drive is ready to run:

# Check Expected Result
1 Read fault buffer (r0945, r0947, r0949) No F01360 present
2 Read r949 on a fresh fault Returns to 0 or to a non-topology reason
3 Topology view in STARTER / Startdrive Left (target) = right (actual), no red highlight
4 Read r9771[0..n] (DRIVE-CLiQ component status) All connected components OK
5 Line Module identification (r9781, r9782) MLFB = 6SL3310-1TE35-0AA3
6 Control Unit firmware (r0018) V4.5 / V4.7 as expected
7 Run the Line Module in Ready state (no enable) Status r0002 = 0/2 (commissioning / ready)
8 Issue ON command and check r0046 (line contactor) Line contactor closes, DC link charges, no fault
9 Save parameters (p0977 = 1) and power-cycle After restart, F01360 does not reappear

10. Related Faults to Distinguish from F01360

Fault Meaning How to Tell from F01360
F01350 Topology: component missing Raised when a device is expected but not detected; DRIVE-CLiQ cable or power issue
F01357 DRIVE-CLiQ node fault Specific node has a hardware / firmware error; r949 points to the failing node
F01360 Topology: component mismatch (this case) Component is detected, but its hardware revision is not in the firmware allow-list
F08501 PROFIBUS / PROFINET communication failure Only affects the bus to the PLC, not DRIVE-CLiQ
F30001 Power unit overcurrent Load-side, not topology-related

11. Key Parameters and Their Roles

Parameter Name Role in F01360 Diagnosis
r0945 Fault code Always 1360 for this fault
r0947 Fault time received Stamps the fault to the time base
r0949 / r949 Fault value Decodes the affected component / port / reason
r9771[0..n] DRIVE-CLiQ component status Bit-coded health of every node
r9781[0..n] DRIVE-CLiQ component order number Full MLFB of each node, including suffix
r9782[0..n] DRIVE-CLiQ component serial number Unique identifier per device
p9906 Topology comparison result 0 = equal, non-zero = difference
p9907 Topology: accept actual 1 = write actual topology to target
p9908 Topology: number of nodes Count of detected DRIVE-CLiQ nodes
p0976 Factory reset 1 = reset all parameters, requires power cycle
p0977 Save all parameters 1 = copy RAM to CF card

12. Field-Proven Notes and Caveats

  • Clean card does not mean correct card. A factory-empty CF card will not bring an incompatible Line Module into the firmware allow-list. The hardware check is performed by the control unit firmware regardless of the project on the card.
  • License and F01360 are unrelated. If your drive requires a license, missing licenses produce F13000-class faults, not F01360. Do not purchase a license to clear F01360.
  • COMM BOARD firmware version. The optional 6SL3054-0ED00-1BA0 at firmware 4.5 / 4.7 is independent of the Line Module suffix. The compatibility problem lies only between the control unit and the Line Module.
  • Why disconnecting the Line Module clears the fault. With the Line Module removed, the topology comparison has nothing to compare against for that node, so F01360 is not raised. This is a useful diagnostic trick: remove one DRIVE-CLiQ device at a time to isolate the offender.
  • Spare-part procurement. When ordering a replacement Line Module, always quote the full 18-character MLFB including the suffix (6SL3310-1TE35-0AA3), not a shortened form, to avoid receiving a different hardware revision.

13. Quick Diagnostic Flowchart

[Power up CU320-2 DP]
         |
         v
[F01360 present?]--No-->[Drive is fine, exit]
         |
        Yes
         v
[Read r949 - component / port index]
         |
         v
[Read r9781 at the index in r949]
         |
         v
[Component is a Line Module?]--No-->[Go to specific node repair]
         |
        Yes
         v
[MLFB suffix = -0AA0 and CU firmware = V4.5/V4.7?]
         |                       |
        Yes                      No
         |                       |
         v                       v
[Replace with -0AA3]    [Check other causes:
         |                cable, SMC30, COMM BOARD]
         v
[Power up, read r949]
         |
         v
[Run automatic topology config]
         |
         v
[Save and verify - F01360 gone]

14. FAQ

What does fault F01360 mean on a SINAMICS S120 CU320-2 DP?

F01360 is a topology fault indicating the actual DRIVE-CLiQ topology does not match the target topology. In the case of CU320-2 DP (6SL3040-1MA00-0AA0) at firmware V4.5 / V4.7, it is most often raised when a connected Line Module (e.g. 6SL3310-1TE35-0AA0) has a hardware suffix that the control-unit firmware does not accept.

How do I read the supplementary fault value r949 for F01360?

Read r949 with STARTER, Startdrive, or the BOP20 operator panel after the fault occurs. The value encodes the affected DRIVE-CLiQ node and the reason (component mismatch, missing, or wrong MLFB). Cross-reference r949 with r9781 (component MLFB) and r9782 (serial number) at the indicated index to identify the offending device.

Does F01360 mean I need a new CompactFlash card or a new license?

No. F01360 is a hardware topology fault. A clean CF card with no project still reproduces the fault, and license-related issues raise F13000-class faults, not F01360. The correct fix is to align the hardware revisions of the control unit and the Line Module, typically by replacing the Line Module with the suffix the firmware accepts (for example, 6SL3310-1TE35-0AA3 instead of -0AA0).

Is 6SL3310-1TE35-0AA0 compatible with 6SL3040-1MA00-0AA0 at firmware V4.7?

Based on the documented field matrix, the combination 6SL3040-1MA00-0AA0 with 6SL3310-1TE35-0AA0 is not compatible at firmware V4.5 / V4.7 and raises F01360. The accepted Line Module suffix for this control unit is -0AA3 (6SL3310-1TE35-0AA3). The CU320-2 DP variant 6SL3040-0MA00-0AA0 also accepts the -0AA3 Line Module.

How do I prevent F01360 from reappearing after a fix?

After replacing the Line Module, run automatic topology configuration (p9907 = 1), execute p0977 = 1 to save parameters to the CF card, and power-cycle the control unit. Verify the topology view in STARTER / Startdrive shows target = actual with no red highlight, and read r949 to confirm no F01360 is present. Keep the MLFB suffix and firmware version recorded in the project documentation to avoid re-introducing an incompatible module during future maintenance.

Back to blog