Selecting CP 5613 A3 PROFIBUS Card for CM 1243-5 S7-1200 at 430 m

David Krause14 min read
Industrial NetworkingSiemensTechnical Reference
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Selecting CP 5613 A3 / CP 5623 for CM 1243-5 PROFIBUS Communication at 430 m

1. Problem Overview

A SIMATIC S7-1200 CPU equipped with the CM 1243-5 communications module must communicate over PROFIBUS DP to a WinCC Runtime Advanced V16 station (PC-based HMI/SCADA) installed in a Dell or Lenovo industrial PC. The physical separation between the PLC cabinet and the HMI PC is 430 m, which is the central sizing constraint because PROFIBUS segment length is bounded by the selected baud rate and the cable characteristics.

The decision space covers:

  • The PROFIBUS master on the PC side (CP 5612 / CP 5613 A3 / CP 5622 / CP 5623)
  • The PROFIBUS cable type (6XV1830-0EH10 FC Standard Cable GP or equivalent)
  • The achievable baud rate at 430 m, which dictates whether a repeater, OLM, or fiber segment is mandatory
  • The HARDNET-PB DP software license required to operate the PC as a DP class 1/2 master under WinCC Runtime Advanced V16

This reference gathers the cable-length limits, the order numbers, the licensing, and the TIA Portal / SIMATIC commissioning steps required to bring the link up reliably.

2. CM 1243-5 PROFIBUS DP Master – Technical Summary

The CM 1243-5 (article number 6GK7243-5DX30-0XE0) is the PROFIBUS DP master module for the SIMATIC S7-1200 family. It plugs into the left-hand bus of the CPU and is configured from TIA Portal V13 SP1 or later. Refer to the official SIMATIC CM 1243-5 Operating Instructions for full parameter ranges.

Parameter Value
Article number 6GK7243-5DX30-0XE0
Function PROFIBUS DP-V0 / DP-V1 master
Baud rates supported 9.6 kbps to 12 Mbps (automatic detection up to 1.5 Mbps in many firmware loads)
Maximum DP slaves 32 per segment, 125 with repeaters (electrical) – master itself counts as one node
Connector 9-pin D-sub (RS-485), terminating resistor integrated (switchable)
Diagnostics Cyclic and acyclic via TIA, web server diagnostic pages on CPU (where supported)
Compatible CPUs S7-1200 from firmware V4.x onward; S7-1500 also supported when using the equivalent CM 1542-5

The CM handles cyclic data exchange with DP slaves and operates as a Class 1 master. For Class 2 diagnostics from a separate PC (for example, the WinCC station), a CP 5xxx card on the PC side is the correct hardware.

The CM 1243-5 is not a DP slave. If the PC station is to act as a Class 2 master reading diagnostics from the same CM, that PC uses its CP card in DP-Master (Class 2) mode and the S7-1200 must be reachable through the CM as a slave proxy – check the TIA project topology before commissioning.

3. PROFIBUS Cable-Length vs Baud Rate – Why 430 m Forces a Lower Baud

PROFIBUS DP segment length is bounded by the signal rise-time budget and the cable attenuation. The values most commonly used in field engineering, taken from the IEC 61158 / IEC 61784 PROFIBUS specification, are summarized below.

Baud rate Max segment length (Type A cable) Application
9.6 kbps 1 200 m Slow I/O, drives on long plant runs
19.2 kbps 1 200 m Slow I/O, drives
45.45 kbps 1 200 m Slow I/O
93.75 kbps 1 200 m Slow drives
187.5 kbps 600 m (some sources 1 000 m) Plant backbone, very common for multi-VFD lines
500 kbps 400 m Default factory line speed
1.5 Mbps 200 m High-speed I/O hubs
3 Mbps 100 m Rare
6 Mbps 100 m Rare, only short drops
12 Mbps 100 m Reserved, hardly used

At 430 m, 500 kbps is not achievable on a single copper segment. The next lower standard baud, 187.5 kbps, supports up to 600 m and therefore accommodates the 430 m run without any repeater or media converter.

If the application cannot tolerate 187.5 kbps (because of, for example, a high-speed drive profile), the engineered options are:

  1. Add an RS-485 repeater (e.g., 6GK1500-3AA00) at the 400 m mark and continue with 500 kbps on the second segment.
  2. Convert to fiber with an OLM/OLP pair (e.g., 6GK1502-3AB10 OLM/G11) – single-mode fiber can carry PROFIBUS over kilometers.
  3. Add a second CP card on the PC – one CP stays at 187.5 kbps on copper for diagnostics, the other is routed via OLM if fiber is present.
For a single-drop diagnostic link of 430 m, the simplest and most reliable answer is to set the PROFIBUS network to 187.5 kbps and use the standard FC cable. Verify with the master module that the bus parameters (TSL, TSET, min TSDR, max TSDR, quiet time, slot time) are consistent with the chosen baud rate.

4. PROFIBUS PCI / PCIe Card Selection on the PC Side

The WinCC Runtime Advanced V16 station (6AV2104-0FA05-0AA0, 2048 PowerTags) requires a SIMATIC NET CP that exposes a WinCC-compatible DP channel. The four candidates identified in the original question are compared below.

Article Bus interface Function Status (2024)
CP 5612 6GK1561-2AA00 PCI DP-Master (Class 1/2), DP-Slave, S7/PG, FMS Spares only, replaced by CP 5612 A2 / CP 5613 A3 / CP 5623
CP 5613 A3 6GK1561-3AA02 PCI (32-bit, 5 V/3.3 V) DP-Master (Class 1/2), DP-Slave, S7/PG, FMS, PG function Active, recommended for legacy PCI hosts
CP 5622 6GK1562-2AA00 PCIe X1 DP-Master (Class 1/2), DP-Slave, S7/PG Active
CP 5623 6GK1562-3AA00 PCIe X1 DP-Master (Class 1/2), DP-Slave, S7/PG, FMS, PG function Active, recommended modern choice

Recommended selection:

  • If the PC has free PCI slots (older Dell/Lenovo industrial models): use the CP 5613 A3 (6GK1561-3AA02). It is the current generation PCI card and supersedes the obsolete CP 5612A2. It supports DP class 1 and class 2 masters, which is exactly what a WinCC Runtime Advanced station needs to integrate with the CM 1243-5.
  • If the PC is a modern PCIe-only platform: use the CP 5623 (6GK1562-3AA00). It is functionally equivalent to the CP 5613 A3 but on PCIe X1, and is the long-term lifecycle solution.

Both cards ship with the SIMATIC NET PC software on a USB stick or DVD. The CP 5623 is referenced in the SIMATIC NET V16 manuals and is fully compatible with WinCC Runtime Advanced V16. The CP 5613 A3 is referenced in WinCC RT Professional V16 architecture slides, which explicitly recommend pairing a CP 5613 A3 with a Hardnet PB DP V15 license for this scenario.

CP 5613 A3 is the safest pick for the 6AV2104-0FA05-0AA0 WinCC Runtime Advanced V16 station when the host is a PCI-equipped industrial PC. If the host is PCIe-only, substitute the CP 5623 – the configuration in TIA Portal is identical.

5. HARDNET-PB DP Software License

PROFIBUS on the PC side does not work with stock Windows drivers. Siemens bundles a SIMATIC NET software stack and a license that authorises the CP to act as a DP master (class 1 or class 2). For this scenario, the order number is:

License Order number Notes
HARDNET-PB DP V15 6GK1713-5DB15-0AA0 Reference example shown in WinCC RT Professional V16 architecture slides
HARDNET-PB DP V16 6GK1713-5DB16-0AA0 (verify against the SIMATIC NET V16 catalog) Match the license major version to the SIMATIC NET V16 / WinCC V16 software you install
SOFTNET-PB DP 6GK1704-5DW… DP slave only – not usable as a master for WinCC Runtime Advanced

The license is keyed to the CP card. It enables:

  • DP-Master (Class 1) for cyclic data exchange (DP-V0)
  • DP-Master (Class 2) for diagnostics (DP-V1 acyclic)
  • PG function (routing S7 frames between PROFIBUS and Ethernet via the station)
  • S7-communication over PROFIBUS, which WinCC Runtime Advanced uses to read S7 tag data from the CM 1243-5 / S7-1200 backplane
If WinCC Runtime Advanced V16 is installed on the PC, the SIMATIC NET version on the same PC must be V16. Mixing V15 SIMATIC NET with V16 WinCC Runtime Advanced may work for a few scenarios but is not supported for new installations. Match the license to the SIMATIC NET major version (V16).

6. Cable Specification – 6XV1830-0EH10

The SIMATIC NET PROFIBUS FC Standard Cable GP (article 6XV1830-0EH10) is the violet-jacketed Type A cable designed for the longest runs. Key data:

Parameter Value
Article number 6XV1830-0EH10
Conductor 2 x 0.64 mm (24 AWG), solid copper
Impedance (Z₀) 150 Ω ± 15 Ω at 3 to 20 MHz
Loop resistance ≤ 110 Ω/km
Capacitance ≤ 28 nF/km
Velocity of propagation ≈ 0.66 c
Colour Violet (RAL 4001)
Shielding Aluminium-foil + braided tinned copper, ≥ 60 % coverage
Operating temperature −40 °C to +75 °C (fixed); −10 °C to +60 °C (flexing)
Min. bend radius 75 mm (fixed), 125 mm (flexing) – approx. 7.5 × OD

At 430 m the cable attenuation budget is well inside the 187.5 kbps specification. The PROFIBUS FC cable must be terminated at both ends with the integrated 220 Ω terminating resistor (switched on) or with active PROFIBUS connector terminators (6GK1500-0FC10).

Never leave one end floating. With a single CM 1243-5 on the PLC side and a single CP card on the PC side, the two ends of the segment must each have the terminating resistor enabled. If a third station is added (e.g. a programming port), intermediate stations must have terminators OFF.

7. TIA Portal / WinCC Configuration Sequence

  1. Install SIMATIC NET V16 on the WinCC Runtime PC. This installs the CP 5613 A3 / CP 5623 driver, the HARDNET-PB DP V16 license enforcement, and the Station Configuration Editor.
  2. Insert the CP in the PC station using the Station Configuration Editor. Assign index 1 (or 2 if a second CP is present). The configured name and index must match what is later bound in WinCC.
  3. Transfer the license using Automation License Manager. Without the license key the CP runs in demo mode (only ~10 minutes of operation per boot).
  4. In the TIA Portal project, add the S7-1200 with the CM 1243-5 in Devices & Networks. Configure the CM as PROFIBUS master with baud rate 187.5 kbps, profile DP-V0 or DP-V1 as required, and address the S7-1200 CPU on PROFIBUS (default for CM is automatically chosen; pick a free master address, typically 2).
  5. Connect the WinCC Runtime Advanced station in TIA via the HMI connection type. Pick S7-1200/S7-1500 as the partner and select PROFIBUS as the access point if the HMI is to talk to the PLC over the CP card.
  6. Compile and download the PC station from TIA Portal into the WinCC PC. The downloader writes the Station Configuration Editor database.
  7. Run WinCC Runtime Advanced and verify that the configured connection shows Connected status. From the WinCC project tree, use the Connections > Status diagnostics to confirm the S7-1200 is reachable.

8. Verification and Acceptance Tests

After the wiring is complete and the project is downloaded, perform the following checks in sequence.

Test Method Acceptance criterion
Bus voltage / signal Measure DC between pin 3 (+5 V) and pin 8 (GND) of the PROFIBUS connector at each end with the CP/CM powered 4.75 – 5.25 V DC
Terminating resistors Power down the segment. Measure across pins 3 and 8 of every node: only the two end nodes should show ~220 Ω between them, intermediate nodes ~infinite Two and only two terminators active
Bus scan Run PC Internal > PROFIBUS Diagnostics in SIMATIC NET or use PROFIBUS Diagnostics tool Both stations visible at expected addresses
Cycle time Observe the DP cycle on TIA diagnostics or in SIMATIC NET trace Cycle time consistent with the configured baud rate, no retries
Cyclic I/O Force a tag in TIA on the S7-1200 side and observe it in WinCC Runtime Advanced Tag value updates every cycle, no jitter > 2 × configured watchdog
Burst of errors Run a 30-minute soak with 95 % bus load Zero error counters in Station Configuration Editor diagnostics

9. Troubleshooting Matrix

Symptom Likely cause Corrective action
Bus scan shows no stations Cable break, polarity reversed, no terminator Verify continuity end-to-end with a TDR; confirm A–A, B–B polarity; enable both end terminators
Bus scan shows master but no slave Baud-rate mismatch or duplicate PROFIBUS address Force all nodes to 187.5 kbps (set CM 1243-5 baud in TIA, CP baud in Station Config); reassign addresses 0–125 uniquely
Connection drops after < 10 min HARDNET-PB DP license missing or expired Re-transfer license with Automation License Manager
High retry counter EMC noise on cable route, shield not bonded at glands Bond shield 360° at every gland; reroute cable away from VFD power; install PROFIBUS Trunk Terminator (6GK1500-0FC10)
Cycle time too slow at 500 kbps Cable too long for 500 kbps Lower baud to 187.5 kbps or split the segment with a repeater (6GK1500-3AA00)
WinCC shows connection faulted but Station Config shows bus healthy WinCC connection is configured for Ethernet not PROFIBUS Change connection mode to PROFIBUS / S7-1200 access point = CP 5613 A3 (PROFIBUS)

10. Sizing Worksheet – 430 m PROFIBUS Link

Use this worksheet to size the components before ordering:

Cable run               : 430 m (one continuous segment)
Baud rate required      : _________ kbps
Max segment @ baud rate : _________ m (from table in §3)
Margin check            : (max – run) >= 0 ?  OK / NOT OK

If NOT OK -> add repeater at ____ m, OR lower baud, OR add OLM.

Cable                    : 6XV1830-0EH10 (Type A FC Standard GP)
  Length ordered (10 % slack) : 430 m × 1.10 = 475 m, round to 500 m drum
Connector quantity        : (number of stations) + (spare 2)
Terminating resistors    : active at the two far ends only

PC-side CP               : CP 5613 A3 (6GK1561-3AA02)  –OR–  CP 5623 (6GK1562-3AA00)
HARDNET license          : 6GK1713-5DB16-0AA0 (V16, matches SIMATIC NET V16)

WinCC station            : 6AV2104-0FA05-0AA0 (WinCC RT Advanced V16, 2048 PT)

11. Safety, Shielding, and Routing Notes

  • Route the PROFIBUS cable in a dedicated, continuously bonded metallic tray or conduit; do not share with VFD power cables. Maintain at least 200 mm separation from 400 V power, more if parallel for long distances.
  • Bond the shield at both ends with 360° EMC glands. For very long runs in harsh EMC environments, use equipotential bonding conductors (typically 16 mm²) between the two grounding points.
  • Inside cabinets, keep the PROFIBUS cable at least 100 mm from the 24 VDC power tracks and away from contactor coils. Add RC snubbers on the coil side of contactors that share the cabinet.
  • Do not exceed the 4 N per contact mating force on PROFIBUS connectors; if the run is in a vibration area, use the 6GK1500-0FC10 with a vibration-resistant locking mechanism.
  • When commissioning the WinCC station, do not run the 24 VDC into the CP/CM connector body – the connector provides the bus terminator only and the cable shields enter via the housing strain relief, not the signal pins.

12. Field-Proven Recommendations

  1. For a single 430 m copper PROFIBUS link, the simplest working design is: CP 5613 A3 or CP 5623 + HARDNET-PB DP V16 + 6XV1830-0EH10 + 187.5 kbps. This is well within the cable's capability, no repeater needed.
  2. For future-proofing, prefer the CP 5623 on PCIe – the CP 5613 A3 is still active but PCI slots are disappearing from industrial PCs.
  3. For very long future runs (> 600 m) or harsh EMC environments, switch to OLM/G11 with fiber at the 400 m mark and continue PROFIBUS on copper after the OLM, or run the entire 430 m as fiber with OLM pairs at each end.
  4. Always size the WinCC Runtime Advanced V16 power-tag count to match the actual variables; the 6AV2104-0FA05-0AA0 (2 048 PT) part is fine for most < 1 500 tag installations.
  5. Document the baud-rate and the bus parameters in the project documentation – 187.5 kbps with default bus parameters is acceptable, but record the actual TSL, TSET, min TSDR, max TSDR values from TIA in the as-built drawings.

Which CP card should I buy – CP 5613 A3 or CP 5623?

Pick the card that matches your PC's bus. Use CP 5613 A3 (6GK1561-3AA02) for PCI slots; use CP 5623 (6GK1562-3AA00) for PCIe X1 slots. Both support DP-Master Class 1/2 and pair with the HARDNET-PB DP license under WinCC Runtime Advanced V16.

Can I run 500 kbps PROFIBUS over 430 m of cable?

No. The PROFIBUS specification caps a single Type-A segment at 400 m for 500 kbps. For 430 m you must drop to 187.5 kbps (600 m max), insert a repeater at the 400 m mark to keep 500 kbps on each segment, or convert to fiber with OLM modules.

What cable should I use for the 430 m run?

SIMATIC NET PROFIBUS FC Standard Cable GP, article 6XV1830-0EH10. It is Type A, 150 Ω, with attenuation and capacitance within the IEC 61158 PROFIBUS specification for the full 430 m at 187.5 kbps.

Do I need a HARDNET-PB DP license?

Yes. For WinCC Runtime Advanced V16 on a PC acting as DP-Master, install SIMATIC NET V16 and license the CP with HARDNET-PB DP V16 (for example, 6GK1713-5DB16-0AA0). Without the license, the CP runs in demo mode for about 10 minutes per boot.

How do I configure the CM 1243-5 for 187.5 kbps?

In the TIA Portal project, open the CM 1243-5 in Devices & Networks, switch to the PROFIBUS interface properties, and set Transmission rate = 187.5 kbps. Compile and download. Set the PC CP card to the same baud in the Station Configuration Editor. Verify with the SIMATIC NET bus diagnostics that both stations appear with the expected addresses.

Back to blog