Siemens Drive P1121 Reset After Stop: RAM-to-ROM Save

David Krause13 min read
SiemensTroubleshootingVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Siemens Drive P1121 Reset After Stop: RAM-to-ROM Save Procedure

1. Problem Overview

Field engineers commissioning legacy Siemens MICROMASTER 4xx and entry-level SINAMICS drives (V20, G110, G120 with CU230/CU240 control units) routinely encounter a frustrating behavior: ramp-down time parameter P1121 is changed via the Basic Operator Panel (BOP), verified, used during a run cycle, and then found reverted to factory default after the stop command. No power cycle occurred between the change and the apparent reset. The technician reports the change, runs the machine, stops it, reads back P1121, and finds the default value of 10.00 s (or whatever factory default applies for the firmware) sitting where 30.00 s was entered minutes earlier.

This symptom is not a hardware defect, EEPROM write failure, or firmware bug. In virtually every documented case the root cause is one of two conditions:

  1. Supervisory controller overwriting the parameter. A PLC, HMI, or SCADA tag is writing P1120/P1121 back to the project default on every scan, every stop event, or every parameter-download cycle. The BOP edit is silently overwritten by the controller.
  2. RAM-only change never committed to non-volatile memory. The BOP edit was written to volatile RAM. Without executing P0971 = 1 (RAM-to-ROM transfer), the value is lost on the next power-up or on certain parameter-reset triggers tied to command-source changes.
Critical field observation: Both root causes produce identical symptoms. Always rule out the PLC-overwrite path first because no amount of EEPROM saving will keep a value that the controller actively overwrites each cycle.

2. Affected Drive Families and Firmware

The P1120/P1121/P0971 numbering is part of the legacy MICROMASTER parameter schema that Siemens preserved across the entry-level SINAMICS product lines. Parameter availability, however, varies by firmware version and control-unit type.

Drive Family Control Unit / Model Firmware Branch P1121 Exposed BOP Support
MICROMASTER 420 MM420 All legacy FW Yes Yes (BOP, AOP)
MICROMASTER 430 MM430 All legacy FW Yes Yes
MICROMASTER 440 MM440 All legacy FW Yes Yes
SINAMICS V20 6SL3210-5BE... FW 3.0x and later Yes Yes (BOP, IOP)
SINAMICS G110 CU230P-2 (basic) FW 4.4 and later Yes (compatibility mode) Yes (BOP-2)
SINAMICS G120 CU230P-2 / CU240B-2 / CU240E-2 FW 4.4 / 4.7 SPx Yes when BOP/IOP or MM4 emulation active Yes (BOP-2, IOP)
SINAMICS G120D CU240D-2 DP/PN FW 4.7 SPx Yes in compatibility mode Yes (BOP-2, IOP)
SINAMICS G120C Compact USS/Modbus variants FW 4.7 SPx Selective Yes (IOP-2)

Refer to the official SINAMICS V20 operating instructions and the MICROMASTER 440 parameter list for parameter map specifics per firmware branch.

3. Root Cause Analysis: Two-Tier Parameter Storage

Siemens entry-level drives expose a two-tier parameter storage model that is identical in principle across MM420/430/440, SINAMICS V20, and the SINAMICS G-series compatibility-mode parameter set:

  • Volatile RAM (working memory): All parameter writes from the BOP, AOP, IOP, USS, Modbus, PROFIBUS-DP, or PROFINET land here first. RAM is fast but is cleared on power-down and on certain reset events tied to factory-reset or command-source changeovers.
  • Non-volatile EEPROM (back-up memory): Parameters that should persist across power-cycles must be explicitly transferred from RAM to ROM using P0971 = 1. The transfer is a block write of all marked parameters and typically takes 3 to 30 seconds depending on the drive family and EEPROM wear.

The default for P0971 is 0 (idle, no save in progress). When the operator uses the BOP to change P1121, the BOP software automatically initiates a per-parameter write to RAM. Historically, many MM4 BOP interfaces write small parameter changes immediately to EEPROM. With certain SINAMICS V20 firmware revisions and certain IOP/BOP-2 combinations, the behavior switched to RAM-only write unless P0971 = 1 is issued afterward. This change in default behavior is the source of much field confusion.

3.1 Reset Triggers Beyond Power-Cycle

Several events other than power-cycle will silently drop a RAM-only value:

  • Factory reset (P0010 = 30, P0970 = 1)
  • Parameter-set switchover between parameter sets 0 and 1 (P0820/P0821)
  • Restore-factory-defaults command from PLC over fieldbus
  • Drive firmware update via STARTER or SINAMICS Startdrive
  • Plug-and-play / I-component replacement on SINAMICS G120

Engineers observing P1121 "self-resetting" should record whether any of these triggers preceded the observation.

4. Key Parameter Reference

The following table lists the parameters that govern ramp timing and parameter persistence on the affected drive families. Verify the index and range against the parameter list specific to your firmware branch using Siemens Industry Online Support.

Parameter Name Range (typical) Default Function
P1120 Ramp-up time 0.00 to 650.00 s 10.00 s Time to accelerate from 0 Hz to P1082 (max frequency)
P1121 Ramp-down time 0.00 to 650.00 s 10.00 s Time to decelerate from P1082 to 0 Hz
P1130 Ramp-up initial rounding 0.00 to 40.00 s 0.00 s Smoothing time at start of ramp-up
P1131 Ramp-up final rounding 0.00 to 40.00 s 0.00 s Smoothing time at end of ramp-up
P1132 Ramp-down initial rounding 0.00 to 40.00 s 0.00 s Smoothing time at start of ramp-down
P1133 Ramp-down final rounding 0.00 to 40.00 s 0.00 s Smoothing time at end of ramp-down
P1134 Rounding type 0 / 1 0 0 = continuous smoothing, 1 = discontinuous smoothing
P1135 OFF3 ramp-down time 0.00 to 650.00 s 5.00 s Emergency-stop / fast-stop deceleration time
P1082 Maximum frequency 0.00 to 650.00 Hz 50.00 Hz Upper frequency reference limit
P0971 Save parameter set (RAM to ROM) 0 / 1 0 0 = idle, 1 = start save and reset to 0
P0010 Commissioning parameter filter 0 to 30 0 0 = ready, 1 = quick commissioning, 30 = factory settings
P0970 Factory reset 0 / 1 0 1 = reset all parameters to factory defaults
P0700 Command source selection 0 to 6 2 Determines ON/OFF/REV source (BOP, terminal, USS, Modbus, PROFIBUS, PROFINET)
P1000 Setpoint source selection 0 to 7 2 Determines frequency setpoint source

5. Solution A: RAM-to-ROM Transfer via P0971

When the root cause is genuine RAM-only loss, the fix is a one-shot write of the parameter set to EEPROM using P0971. The procedure works on every drive family listed in Section 2.

5.1 Procedure on the BOP / BOP-2

  1. Confirm the drive is in ready state (no active run command, no fault active). The BOP displays the drive state in the top-right indicator (MM4) or via status LED (BOP-2/IOP).
  2. Navigate to P1121 and verify the desired value. Do not run the motor between edit and save.
  3. Navigate to P0971.
  4. Press OK / Fn / P to enter edit mode.
  5. Set the value to 1 and press OK / Fn / P to commit.
  6. Wait until P0971 returns to 0 on its own (3 to 30 s). The BOP typically displays "busy", "save", or a flashing decimal during the transfer.
  7. Power-cycle the drive. Verify P1121 retains the edited value.
Important: Do not remove control voltage or mains during the transfer. Interrupting a save cycle can corrupt the EEPROM block on legacy MM4 hardware. The drive must sit undisturbed until P0971 reads 0 again.

5.2 Procedure via USS / Modbus RTU

For PLCs controlling the drive over RS485 (USS protocol or Modbus RTU), the same P0971 write can be issued as a parameter write over the bus. The PKW (USS) or register 4031xx (Modbus) address for P0971 must be calculated against the parameter number using the formula:

Modbus register address = 40000 + (parameter_number × 2) + 1

For P0971: register = 40000 + (971 × 2) + 1 = 41943 (read), 41942 (write low word).

Function code 06 (preset single register) or 16 (preset multiple registers) writes the value. Issue write of 1 to register 41942. Poll parameter r3996 (or status word bit) to confirm the save completes. See the SINAMICS V20 Modbus RTU parameter mapping reference for the precise address map on V20 firmware.

5.3 Procedure via PROFIBUS-DP / PROFINET

On PROFINET (SINAMICS G120 with CU240 PN) and PROFIBUS-DP (MM440 with PROFIBUS option), the parameter channel is mapped via PKE/IND/PWE words in the cyclic I/O or via acyclic record (PROFIBUS DPV1 / PROFINET record write). Use STARTER or the PLC's parameter-access FB to write 1 to P0971. Acyclic writes via record 0xB02E (PN) or DPV1 index 0x2F are accepted.

6. Solution B: Identify and Stop the PLC Override

If the PLC is the controlling entity, it is common practice for the HMI or PLC program to write default ramp times from the project database on every start-up, every recipe change, or every stop event. This is normal behavior in well-architected control code, but it makes ad-hoc BOP edits useless.

6.1 Diagnostic Procedure

  1. Place the drive in hand / jog mode via P0700 = 1 (BOP) and P1000 = 1 (motor potentiometer / BOP). This isolates the drive from the PLC.
  2. Edit P1121 to a non-default value, e.g., 45.00 s.
  3. Save via P0971 = 1.
  4. Power-cycle the drive.
  5. Verify P1121 = 45.00 s after the power-up.
  6. If the value survives, the PLC is the source of the overwrites.

6.2 Where to Look in the PLC Project

Search for the following patterns in the PLC code, regardless of manufacturer (Siemens S7-1200, S7-1500, Allen-Bradley CompactLogix, Schneider M340, Beckhoff TwinCAT):

  • Function blocks named Drive_Param_Write, VFD_Sync, Parameter_Load, Recipe_Apply
  • Logic blocks that execute on First_Scan, Cold_Restart, Drive_Ready_Rising_Edge
  • Data blocks or tag databases with strings like ramp_time, decel_time, RAMP_DN, P1121
  • Recipe-management blocks that push a complete parameter set on recipe selection

Disable or comment out the offending write block, recompile, and download. Verify that P1121 retains its edited value across a stop event.

7. Verification Checklist

After applying either Solution A or Solution B, run the following verification sequence before returning the machine to production:

  1. Confirm drive state = Ready (no active run command).
  2. Read P1121 and confirm intended value.
  3. Issue a controlled run command from the controlling source (BOP, terminal, or PLC).
  4. Run the motor for at least 30 s at a frequency > 10 Hz to verify ramping.
  5. Issue stop. Measure ramp-down time with a stopwatch or from r0899 (ramp-function-generator output frequency) trace.
  6. Stop and read P1121. Confirm intended value still present.
  7. Power-cycle the drive. Read P1121 again.
  8. If all three read-backs agree, close the work order.

8. Field-Proven Caveats

  • Edit-only-when-stopped: Some BOP-2 firmware revisions reject writes to P1121 while the drive is in Run state. Always edit with the drive stopped. The MM4 manual explicitly documents this requirement.
  • Quick-commissioning mode (P0010 ≠ 0): Writes issued while P0010 = 1 (quick commissioning) may not persist the same way as writes in P0010 = 0. Always set P0010 = 0 before issuing the P0971 save.
  • Recipe download via STARTER / Startdrive: When the project is downloaded to the drive via STARTER or SINAMICS Startdrive, the tool issues its own RAM-to-ROM transfer at the end of the download sequence. You should still verify with P0971 = 1 if the value reverts.
  • Multi-parameter-set drives: MM440 supports parameter set switchover via P0820/P0821. Each set has its own P1121 value. If switchover is active, you are only editing one set.
  • Fieldbus fault behavior: On PROFIBUS/PROFINET, a faulted fieldbus or watchdog timeout can revert P0700/P1000 to their fault-handling values, which in some configurations silently restores factory ramp defaults.
  • EEPROM wear: Each P0971 = 1 transfer is a full parameter-block write to EEPROM. EEPROM cells on MM4 hardware are rated for ~100,000 write cycles. In test-and-tune environments where engineers issue P0971 = 1 many times per shift, this can become a wear issue. Cache changes in RAM and only issue P0971 = 1 when the parameter set is final.

9. Related Parameter Set to Audit

If P1121 was reverting because of PLC override or generic parameter reset, the same issue applies to every parameter the PLC or operator edits. Audit the following list as a starting point:

Parameter Function Risk if reverted
P1120 Ramp-up time Aggressive acceleration → motor current spikes
P1121 Ramp-down time DC-link over-voltage, drive fault F0002
P1135 OFF3 fast-stop time Safety-relevant; must follow risk assessment
P1080 Minimum frequency Reverse-direction fault if undersized
P1082 Maximum frequency Process overspeed if reverted
P2000 Reference frequency Scaling mismatch with analog setpoint
P2200 PID controller enable Process loop becomes open-loop
P1215 Braking chopper enable Loss of dynamic braking

10. Troubleshooting Matrix

Symptom Likely Cause First Check Fix
P1121 reverts within minutes, drive never power-cycled PLC active write Disable fieldbus, repeat edit Remove PLC write block
P1121 reverts on power-cycle only RAM-only edit, no P0971 Read P0971 = 0 after edit Issue P0971 = 1
P1121 reverts on stop, drive remains powered PLC writes on stop event or drive-ready edge Trace PLC code for edge-triggered write Move write to first-scan only
All parameters revert Factory reset via P0970 = 1 or PLC command Check P0970 history in fault log Re-commission, then P0971 = 1
P1121 reverts after recipe download Recipe contains P1121 Open recipe file Edit recipe value, re-download
P1121 reverts after STARTER download Project default not changed Read project offline P1121 Edit in project, re-download
P1121 reverts after PROFINET name/IP change Drive restore defaults on replace Check r3996 history Re-commission from project

11. Manual and Documentation References

For deeper parameter context, fault-code listings, and wiring examples, consult the official Siemens documentation:

Fault-code references for ramp-related faults encountered after a P1121 override attempt:

Fault Code Meaning Typical Cause After P1121 Edit Action
F0001 Overcurrent Ramp-up too aggressive, motor stalls Lengthen P1120, check load
F0002 DC-link overvoltage Ramp-down too aggressive for inertia Lengthen P1121, enable brake chopper (P1215)
F0003 Drive overload (I²t) Sustained high current during long ramp Shorten ramp or reduce load
F0004 Motor overtemperature (I²t) Self-cooled motor at low frequency, slow ramp Reduce ramp, increase P1110/P1111 motor protection
F0005 Inverter I²t Sustained overload Reduce load profile
F0021 Ground fault Wiring fault during commissioning Inspect motor and cable
F0022 Power unit fault Hardware fault after transient Power-cycle, check F0022 detail in r0949

12. Frequently Asked Questions

Why does P1121 keep reverting to 10 s even though I never turn off the drive?

Either the PLC is writing P1121 from its project database on every scan, every stop event, or every parameter download, or your BOP wrote the change to volatile RAM only and an internal reset event cleared it. Switch P0700 = 1 and P1000 = 1 (BOP-only control) and re-test to isolate the cause.

What does P0971 = 1 actually do?

P0971 = 1 triggers a one-shot transfer of the working parameter set from volatile RAM to non-volatile EEPROM. The drive writes the entire parameter block, then automatically resets P0971 to 0 when the transfer completes (typically 3 to 30 s). Do not remove control power during the transfer or the EEPROM block may corrupt.

Does setting P1121 from the BOP automatically save to EEPROM?

On legacy MM4 with classic BOP the answer has historically been yes. On SINAMICS V20 and G120 with BOP-2/IOP the behavior depends on firmware version; many recent firmware revisions only commit to RAM and require an explicit P0971 = 1 save. Always issue P0971 = 1 after editing and verify with a power-cycle.

How do I find which PLC block is overwriting my drive parameters?

Search the PLC project for any function block or routine that writes to the drive parameter channel, especially those triggered on First_Scan, Cold_Restart, Drive_Ready_Rising_Edge, or Recipe_Select. Look for tag names containing ramp, decel, P1121, or Drive_Param. Temporarily disable the write and verify that the BOP edit survives a stop event.

Can I edit P1121 while the drive is running?

Most legacy BOP and BOP-2 interfaces reject writes to P1121 while the drive is in Run state and return the value to its prior setting. Always bring the drive to a complete stop, edit, save via P0971 = 1, then run. Editing during run is a common reason the BOP appears to "accept" the change but it never sticks.

Back to blog