1. Application Overview
The Siemens LOGO! 8 logic relay (6ED1052-xxx08-0BA8) is a compact controller used in small pumping, HVAC, and process skids. This reference documents three integration tasks for a pump station with a 4–20 mA pressure transducer (0–10 BAR range) and an integrated operating time counter:
- Analog fault detection — fire a text message on the LOGO! display when the loop current falls below the sensor's valid range.
- Operating time (OT) reset — zero the maintenance counter from the LOGO! built-in display when the pump is replaced, while keeping a separate total-hours counter intact.
- Alarm display — present fault states to the operator with clear, unambiguous visual feedback.
For sensor break and out-of-range detection, the convention adopted across process instrumentation is NAMUR NE43, Standardization of the signal level for the failure information of digital transmitters. NE43 partitions the 4–20 mA span into valid measurement, out-of-range, and failure-information bands. The thresholds chosen in this article respect those bands so that the LOGO! fault logic is interoperable with field instruments from any manufacturer.
2. Sensor Scaling Mathematics
Mapping a 4–20 mA pressure transducer to 0–10 BAR is a linear transform. Use the formulas below as the design baseline before configuring any LOGO! block.
2.1 Linear transfer function
For a current I in mA at the LOGO! analog input, the engineering value P in BAR is:
P [BAR] = (I [mA] − 4) × (P_max − P_min) / (I_max − I_min) + P_min
With P_min = 0 BAR, P_max = 10 BAR, I_min = 4 mA, I_max = 20 mA:
P = (I − 4) × 10 / 16 = (I − 4) × 0.625
| Loop Current I (mA) | Engineering Value (BAR) | Status per NAMUR NE43 |
|---|---|---|
| ≤ 3.5 | ≤ −0.3125 | Sensor failure / open loop |
| 3.5 – 3.8 | −0.3125 to −0.125 | Failure information |
| 3.8 – 4.0 | −0.125 to 0.0 | Out-of-range (lower) |
| 4.0 – 20.0 | 0.0 to 10.0 | Valid measurement |
| 20.0 – 20.5 | 10.0 to 10.3125 | Out-of-range (upper) |
| ≥ 20.5 | ≥ 10.3125 | Failure information |
2.2 Internal LOGO! AI scaling
The LOGO! 8 analog input block reports the measured current on an internal scale of 0 to 1000 units, where 0 corresponds to the configured zero point (0 mA in 0–20 mA mode, 4 mA in 4–20 mA mode) and 1000 corresponds to the configured span (20 mA). The relationship is:
AI_units = (I − I_zero) × 1000 / (I_full − I_zero)
For 4–20 mA mode (I_zero = 4, I_full = 20):
AI_units = (I − 4) × 62.5
To produce a fault at 3 mA:
AI_units(3 mA) = (3 − 4) × 62.5 = −62.5
Round to −62 to keep the threshold just above the noise floor of the AM2 input stage. The Analog Threshold Trigger block (B002) compares the AI value against this fixed offset and sets its output high when the input is less than or equal to the threshold.
3. Configuring the Analog Input Block
Open LOGO! Soft Comfort V8.x or later and add the Analog Input (AI) block from the analog function group. The parameter dialog contains the following fields:
| Parameter | Value for 4–20 mA, 0–10 BAR | Notes |
|---|---|---|
| Sensor type | 4 – 20 mA | Selectable on AM2 (0BA8) inputs AI1–AI4 depending on base module variant. |
| Zero point (Min) | 0 | 0 units = 4 mA |
| Span (Max) | 1000 | 1000 units = 20 mA |
| Gain | 1.00 | Leave at 1.0 unless the engineering span must be displayed directly in BAR. |
To display the value directly in BAR without a downstream amplifier, change the Gain so that 1000 AI units = 10 BAR. With Gain = 0.01 the output reads in BAR. With Gain = 1.0 the output reads in AI units and an additional Analog Amplifier (B001) maps it to the engineering range. The choice depends on which downstream block uses the value first.
Reference: see the Siemens LOGO! 8 (0BA8) System Manual, edition 06/2022 for AM2 input ranges and parameter limits. Additional analog block reference data is in the LOGO! 8 application examples KB article.
4. Setting the Fault Threshold
The Analog Threshold Trigger (B002 in this design) implements the under-range detection. Place a comparator block on the AI output and configure the threshold (On) and hysteresis (Off) parameters carefully to avoid chatter when the loop current hovers near the trip point.
4.1 Threshold and hysteresis table
| Block Parameter | Value | Engineering equivalent | Purpose |
|---|---|---|---|
| On threshold (B002) | −62 | 3.008 mA / −0.62 BAR | Trip point for the "sensor failed" flag |
| Off threshold | −50 | 3.200 mA / −0.50 BAR | Hysteresis to prevent chattering |
| Gain | 1.00 | — | Preserve AI units at the comparator input |
The hysteresis band of 12 AI units (≈0.192 mA) is wide enough to absorb AM2 quantisation noise of ±2 units yet narrow enough to release the fault within one scan cycle after a healthy signal returns. Always test the hysteresis with a 4–20 mA calibrator (Beamex MC6, Druck DPI 620, or equivalent) sweeping the loop slowly across the trip point.
4.2 NAMUR NE43 conformance
NE43 specifies that valid measurements occupy 4 to 20 mA, with out-of-range information above 20 mA and below 4 mA. A LOGO! threshold of −62 units (3.008 mA) is conservative and triggers a fault inside the NE43 sensor-failure band of ≤ 3.5 mA. Adjust the threshold upward to −25 units (3.6 mA) if the application requires NE43 out-of-range detection at 3.8 mA — the user's tolerance for nuisance trips should drive the choice.
5. Operating Time Counter Reset
The Operating Hours Counter block (B016 / B019 in the LOGO! function library) accumulates runtime for maintenance scheduling. The block exposes two inputs (R and Ral) and two outputs (OT and AL) that can be wired to a Message Text (B017) and to maintenance alarms.
5.1 Block terminals
| Terminal | Symbol | Function |
|---|---|---|
| Input R | Reset | Pulse to clear the elapsed operating time to zero |
| Input EN | Enable | Hold high to allow the counter to accumulate |
| Input Ral | Reset alarm | Clear the maintenance-alarm flag without clearing the time |
| Output OT | Operating time | Elapsed time in h:mm format |
| Output AL | Alarm | Set when OT ≥ service interval |
5.2 Resetting OT from the LOGO! display
The LOGO! 8 base module with built-in display (6ED1052-1MD08-0BA1, -1BB08-0BA1, etc.) has a dedicated menu for the operating hours counter. The procedure to zero the OT field while preserving the cumulative total is:
- Use the
◀/▶cursor keys to navigate to the message text that displays OT (B017 in the project). - Press
OKto enter edit mode; the cursor jumps to the "R" connector marker on the screen. - Press the
OKbutton a second time to fire the reset pulse on the R input. OT returns to 0:00, the alarm (AL) is cleared if the service interval was reached, and the cumulative hours remain on a separate Message Text that the maintenance log reads.
The R pulse is one LOGO! scan long (typically 50 ms depending on program length). It is not latching, so there is no risk of the counter being held at zero after a power cycle.
5.3 Resetting OT via a digital input (alternative)
For a remote reset, wire a momentary pushbutton to a digital input (e.g., I5) and route I5 to the R input of B016 through an OR block. Add a second OR with a discrete flag (M8) that the operator can toggle from the LOGO! menu under "Parameter assignment" to enable or disable remote resets. This prevents accidental resets by a curious operator on a remote HMI.
6. Alarm Message Configuration
The Message Text (B017) block is the LOGO!'s primary operator interface. Place a text block per fault condition. Each block has a "Display" parameter that selects where the message appears: on the built-in LCD, on the LOGO! TDE, or both. A second parameter, "Acknowledge", controls whether the message must be acknowledged with a key press to clear.
6.1 Fault table design
| Fault condition | Trigger source | Message text content | Behaviour |
|---|---|---|---|
| Pressure sensor out of range | Output of B002 (Analog Threshold Trigger) | "PRESSURE SENSOR FAULT — CHECK 4–20 mA LOOP" | Latched until acknowledged; tag transitions to red on TDE. |
| Pump dry-running (no water at I3) | NOT I3 with 5 s on-delay (B011) | "PUMP DRY-RUN — INLET PRESSURE LOW" | Latched; stops pump via output Q1. |
| Service interval reached | AL output of B016 | "PUMP MAINTENANCE DUE — OT: 4000 h" | Non-latched reminder; clear with Ral. |
6.2 Red background / "red screen" capability
The LOGO! built-in display on 0BA8 base modules cannot render red text or a red background. The amber/white LCD does not support colour. The "red screen" effect — black text on a red field — is exclusive to the LOGO! Text Display External (TDE) module, order numbers:
- 6ED1055-4MH00-0BA0 — LOGO! TDE (6-line, red-capable on alarm)
- 6ED1055-4MH08-0BA0 — LOGO! TDE successor variant with updated firmware
When the message text is enabled (EN = 1) and the Acknowledge (Ack) parameter is set to "high active", the TDE renders the message with a red background and the bell icon. The same block appears as black text on the standard white/amber LCD of the base module, so the user always sees the fault — only the cosmetic emphasis differs.
7. Wiring and Electrical Considerations
The AM2 analog input module accepts passive 2-wire and active 3/4-wire transmitters. For a 2-wire pressure sensor, the AM2 provides 24 V loop power; for 4-wire sensors, the loop is powered by the sensor's own supply and the AM2 only measures the current. The wiring diagrams in the LOGO! 8 system manual show the terminal assignments for each case.
| Terminal on AM2 | Function | Use for 2-wire sensor | Use for 4-wire sensor |
|---|---|---|---|
| UI1+ / UI2+ | Analog input + | Sensor + output | Sensor current output + |
| UI1− / UI2− | Analog input − | Sensor − output (return) | Sensor current output − |
| Supply | 24 V loop power | Sensor supply (used) | Not connected to loop |
| M | Ground reference | Tied to PSU 0 V | Tied to PSU 0 V |
For cable runs longer than 10 m, use shielded twisted pair (e.g., Belden 8760, Lapp Ölflex 110 CY) and ground the shield at the panel end only. The AM2 input has a common-mode range tied to M; do not float the panel ground or the AI reading will be unstable. The maximum loop resistance is 600 Ω at 24 V supply (per the AM2 data sheet); verify that the sum of cable resistance plus sensor burden does not exceed this limit. Reference: LOGO! 8 System Manual, Section 4.6 (Wiring of the Analog Inputs).
8. LOGO! 8 Hardware Variant Selection
Not all 0BA8 base modules expose onboard analog inputs. Confirm the part number before assuming an AI is available without an AM2 expansion:
| Order number | Display | DI | DO | Onboard AI | Typical use |
|---|---|---|---|---|---|
| 6ED1052-1MD08-0BA1 | Yes | 8 | 4 relay | 2 (0–10 V only) | Pump control with discrete sensors |
| 6ED1052-1BB08-0BA1 | No | 8 | 4 relay | 2 (0–10 V only) | Blind panel + external HMI |
| 6ED1052-2MD08-0BA1 | Yes | 8 | 4 transistor | 2 (0–10 V only) | Fast-switching loads |
| 6ED1052-1CC08-0BA1 | No | 8 | 4 transistor | 2 (0–10 V only) | Compact cabinet installations |
The onboard AI channels of the base module are 0–10 V only. A 4–20 mA sensor must be wired through an AM2 (6ED1055-1MA00-0BA2) or AM2 RTD (6ED1055-1MA00-0BA7) module. The 4–20 mA mode is selected per-channel in the AI block configuration. The AM2 supports two independent 4–20 mA loops; the AM2 RTD supports one 4–20 mA plus two PT100/PT1000 inputs.
9. Complete Program Skeleton
The following list summarises the blocks of a working program for this application. Block numbering follows the convention used in the original project; substitute local tags as needed. The complete FBD is small enough to review in a single screenshot — roughly 12 blocks total.
| Block | Function | Inputs | Outputs |
|---|---|---|---|
| B001 | Analog Amplifier (gain 1.0, offset 0) | AI1 (4–20 mA, 0–10 BAR) | Normalised AI value |
| B002 | Analog Threshold Trigger (On = −62, Off = −50) | B001 output | Fault flag M1 |
| B011 | On-delay 5 s | NOT I3 | Dry-run flag M2 |
| B012 | OR gate | M1, M2 | Pump-stop request M3 |
| B013 | AND gate (pump run enable) | Start PB, NOT M3, NOT I4 (overload) | Q1 latch set M4 |
| B014 | RS flip-flop (pump latch) | Set: M4; Reset: M3, stop PB | Q1 pump run |
| B015 | NOT | Q1 | — |
| B016 | Operating Hours Counter (interval = 4000 h) | Q1 (enable), I5 (R), I6 (Ral) | OT → B017, AL → B018 |
| B017 | Message Text — OT display | EN = 1 | Shows OT on LCD/TDE |
| B018 | Message Text — "PRESSURE FAULT" | EN = M1 | Red on TDE |
| B019 | Message Text — "DRY RUN" | EN = M2 | Red on TDE |
| B020 | Operating Hours Counter (cumulative, no reset) | Q1 (enable) | OT → B021 |
| B021 | Message Text — total hours | EN = 1 | Always visible |
Use OR gates to combine all fault flags (M1, M2) and route the result to a single message text that prioritises by sequence order. The Message Text block priority is set under "Properties → Priority" with 1 being highest. If multiple messages are active, the highest-priority one takes the display.
10. Verification and Commissioning Procedure
Walk through the following checklist before handing the panel over to operations.
- Continuity check. With the LOGO! powered off, measure resistance between the AM2 input terminals. A healthy 2-wire sensor loop reads 50–500 Ω depending on model. An open loop reads > 1 MΩ and confirms the wiring is intact (but not the polarity).
- Live current check. Power up, break the loop at the AM2 input, insert a multimeter in mA mode. The reading should match the process pressure within the sensor's stated accuracy class. For a 5.0 BAR measurement: I = 4 + 5.0 × 1.6 = 12.0 mA.
- Threshold verification. With the calibrator injecting 3.5 mA, the LCD should display the sensor-fault message. At 4.0 mA the message should clear. The hysteresis between On and Off should make the transition clean, not flickering.
- OT counter test. Force the pump output Q1 on from LOGO! Soft Comfort online mode. The OT should increment every minute. Apply I5 (or navigate the display to R) and verify that OT zeroes but the cumulative counter B020 remains.
- Power-cycle test. Power down the LOGO! for 30 seconds. On reboot, the OT and the fault latches should retain their last state (LOGO! retains retentive flags and counter values by default).
- TDE-only test. If a TDE is installed, replicate the fault and confirm that the red background appears. Disconnect the TDE cable and confirm that the message is still shown on the base module display (in black).
- EMC spot check. Energise a 5 kW VFD on the same panel bus and watch the AI value on the LOGO! Soft Comfort online monitor. The reading should not deviate by more than ±2 AI units; anything larger suggests a grounding or shield-termination issue.
11. Troubleshooting Matrix
| Symptom | Likely cause | Diagnostic step | Remedy |
|---|---|---|---|
| Sensor fault message never triggers, even with disconnected loop | AI block configured as 0–20 mA instead of 4–20 mA | Inspect the AI block in LOGO! Soft Comfort; the zero point should be 4 mA | Change the sensor type to 4–20 mA; the AI units at 0 mA will then read −250 |
| Fault triggers immediately on power-up | AM2 input not enabled, or AI block input is an open connector | Online monitor: hover the AI block input; reading should be near the loop current, not −1000 | Route the AM2 input terminal block to the AI block |
| OT counter resets by itself | R input is wired to a level signal, not a pulse | Online monitor: trace the R input for stuck-high | Insert a pulse generator or wire R to a momentary pushbutton, not a maintained switch |
| Red screen never appears | Application uses only the base module LCD, no TDE | Verify the message text is enabled on the TDE in the message properties | Either add a 6ED1055-4MH00-0BA0 TDE, or replace the red-screen alarm with an icon-based alarm on the built-in LCD |
| OT shows 0:00 after every power cycle | Retentivity disabled for the OT counter | Right-click the block, enable retentivity for the OT and AL flags | Re-enable retentivity in the project and re-transfer the program |
| AI value jitters ±5 units at steady state | AM2 input sharing ground with a digital output, switching noise | Measure loop current with isolated DMM; compare to AI value | Move the sensor cable away from relay output wiring; add 100 µF/50 V capacitor at the AM2 input |
| Pump does not start despite valid AI value | Dry-run flag M2 latched and holding the pump latch reset | Online monitor: inspect M2 and the RS flip-flop inputs | Investigate the actual inlet condition; clear the latch via dedicated reset input or power-cycle |
| Alarm message flickers on and off near trip point | Hysteresis band too narrow for the application noise | Online trend log: observe the AI value over 60 s at steady state | Increase the gap between On and Off thresholds to 15–25 units |
12. Frequently Asked Questions
What threshold value do I set in LOGO! Soft Comfort to detect a 4–20 mA sensor fault at 3 mA?
With the AI block configured for 4–20 mA and a 0–1000 internal scale, set the Analog Threshold Trigger "On" parameter to −62 (or any value between −62 and −200). The "Off" hysteresis should be 8–15 units above "On" to prevent chattering. −62 corresponds to 3.008 mA, well below the NAMUR NE43 sensor-failure band of 3.5 mA.
Why can't the LOGO! Soft Comfort simulator enter a negative current value?
The simulator enforces the sensor's valid range. In 4–20 mA mode, the minimum is 4 mA. To verify the fault path, use a hardware 4–20 mA calibrator (Druck DPI 620, Beamex MC6) or temporarily switch the AI block to 0–20 mA mode and inject 3 mA through the sensor input terminal of the AM2 module.
How do I reset the operating time (OT) from the LOGO! display?
Navigate with the cursor keys to the message text that displays the OT value, press OK, then press OK again while the cursor is on the R connector. The OT resets to 0:00 in a single scan. The Ral input clears the alarm bit only and does not zero OT — use it for "acknowledge" rather than "reset".
Can the LOGO! built-in LCD show a red background for fault messages?
No. The base module's monochrome LCD does not support colour. The red background appears only on the LOGO! TDE (6ED1055-4MH00-0BA0 or −4MH08-0BA0). For base-module-only panels, communicate severity with text prefixes ("FAULT:", "ALARM:") or icon glyphs in the message string.
Do I need a separate counter for the total pump lifetime if I want to reset OT on pump replacement?
Yes. The standard Operating Hours Counter resets via R. Add a second Operating Hours Counter (B020) wired to the same pump run signal but with no reset input. Route its OT to a separate message text labelled "TOTAL HOURS". The two counters run in parallel; only the maintenance counter is resettable.