Overview
The SIMATIC S7-1200 CPU stores its operating firmware in onboard flash memory. Unlike a program, the firmware is the internal execution engine that defines the instruction set, web server features, motion capabilities, and CPU-internal diagnostics. A change in firmware version is therefore not a user operation but a controlled maintenance task that must match the engineering tool selected in the project.
When a CPU is delivered from the factory it typically carries a baseline firmware version (commonly V1.0 on the early 121x and 122x/123x/124x/150x hardware variants) or a higher factory version such as V2.0 or V4.x. Loading a project that was created with a TIA Portal selecting a different firmware version causes the engineering tool to flag an inconsistency. Resolving that mismatch requires either selecting the correct CPU/firmware in the project or updating the physical CPU firmware so it matches the project target.
Siemens provides two official paths for changing S7-1200 firmware: an online update from the connected PG/PC using the Online & Diagnostic tools in TIA Portal, and an offline update using a SIMATIC Memory Card (SD card) prepared with the firmware update package. Both methods are documented in the official Updating firmware section of the S7-1200 manual collection.
TIA Portal and Firmware Compatibility Matrix
The interaction between the TIA Portal version, the firmware version selected in the device configuration, and the actual firmware on the physical CPU follows a fixed compatibility rule: the project configuration and the target CPU must be aligned, and the TIA Portal must be new enough to know the firmware descriptor in question.
| TIA Portal Version | Selected FW in Project | FW on Physical CPU | Result / Behavior |
|---|---|---|---|
| V10.5 SP1 | V1.0 | V1.0 | Project loads, CPU executes as V1.0 |
| V10.5 SP1 | V1.0 | V2.0 | Project loads, CPU runs in V1.0-compatible mode (V2.0 features unavailable) |
| V11 | V1.0 | V1.0 | Project loads, CPU executes as V1.0 |
| V11 | V1.0 | V2.0 | Project loads, CPU runs in V1.0-compatible mode |
| V11 | V2.0 | V2.0 | Full V2.0 feature set, web server enabled, optimized block access available |
| V13 / V14 / V15 / V16 / V17 | V4.x | V4.x | Full feature set, User Management & Access Control (UMAC) on V4.7 |
This matrix is the root cause of the most common S7-1200 firmware complaint: a V2.0 CPU is shipped from Siemens, the educational software bundle (STEP 7 V10.5 SP1) only contains a V1.0 device descriptor, the user loads the project, and the engineering tool rewrites or coerces the CPU into a V1.0-compatible state. The PLC is not damaged, but the V2.0 capabilities (such as the integrated web server and the optimized block access) become inaccessible until firmware V2.0 is restored.
Firmware Version Feature Differences
Each major firmware release on the S7-1200 introduces or unlocks features that are otherwise latent in the hardware. The following table summarizes the version-to-version deltas most relevant to commissioning and support decisions.
| FW Version | Key Features / Capabilities |
|---|---|
| V1.0 | Baseline S7-1200 feature set; no integrated web server beyond diagnostic pages; basic PID; no UMAC. |
| V2.0 | Integrated web server with user-defined pages; optimized block access (S7-1500-style); expanded PROFINET diagnostics; improved motion blocks. |
| V4.0 – V4.4 | OPC UA server; Secure Communication (TLS); expanded trace; user-defined web pages via User-Web-Editor. |
| V4.5 | Performance optimizations; extended PID self-tuner; OPC UA companion spec support. |
| V4.6 | Additional code/data work memory through code customization; improved download performance; see Firmware V4.6 release note (ID 109814248). |
| V4.7 | User Management & Access Control (UMAC); TLS hardening; additional security event logging; see Firmware V4.7 release note (ID 109976907). |
When a CPU is downgraded to V1.0 (intentionally or by a mismatched project download), the V2.0 feature block is masked, not deleted. Restoring V2.0 or higher firmware re-enables those features without any hardware change.
Prerequisites for Firmware Update
- Identify the exact CPU order number (MLFB). The firmware package is bound to the article number, e.g. 6ES7214-1BE30-0XB0 for CPU 1214C AC/DC/Rly. Mixing order numbers results in a failed update and a CPU in STOP.
- Match TIA Portal version to target firmware. Use the Siemens Support Online HSP (Hardware Support Package) mechanism to teach older TIA Portal versions the newer firmware descriptor. New firmware is supported in the matching TIA Portal release or later, never in an earlier release.
- Provide stable 24 V supply to the CPU. Loss of supply during a flash write can brick the CPU. Use a UPS or buffer the supply for the duration of the update (typically 1 to 3 minutes for S7-1200).
- Stop the CPU before initiating the firmware update. A running CPU will be placed into STOP by the update routine, but a clean stop prevents scan-time faults from corrupting the log.
- For SD card method: Use a Siemens-branded SIMATIC Memory Card (SMC) of at least 4 MB; the 24 MB card referenced in legacy kits is functionally identical to modern 4 MB / 12 MB / 24 MB / 256 MB / 2 GB cards for the S7-1200 update use case.
- Have a serial or project backup of the current user program. Firmware updates preserve the user program on the CPU but a project backup on the engineering PG is mandatory engineering practice.
Online Firmware Update via TIA Portal
The online path is the preferred method for a single CPU that is reachable on the PROFINET/PROFIBUS network and physically accessible to confirm a successful restart. The procedure is documented in the Updating firmware page of the TIA Portal cloud manual.
- In the project tree, select the S7-1200 CPU and open Online & Diagnostics from the context menu.
- Expand the Functions folder and select Firmware Update.
- In the right pane, TIA Portal displays the currently connected CPU's article number, the firmware version installed, and the firmware files available on the local PG.
- Click Browse and navigate to the firmware update package (typically a
.updfile extracted from the HSP download). The path looks similar toC:\Program Files\Siemens\Automation\HWUpdate\6ES7214-1BE30-0XB0\FW_UPDATE\V04.07.00. - Select the target firmware version and click Execute Update. The CPU enters STOP, the MRES LED pattern indicates a flash operation, and the CPU automatically restarts when the update completes.
- After the restart, re-compare the online and offline configuration. The online diagnostic should now report the new firmware version under Diagnostics > Device Information.
.upd files from the official Siemens Industry Online Support portal.Firmware Update via SIMATIC Memory Card (Offline)
The SD card method is the field-engineer fallback when the CPU is not online-reachable, when the TIA Portal on site is older than the target firmware, or when an entire fleet of CPUs (for example, an educational kit of 6 CPUs) must be brought to a common baseline.
- Insert the SMC into a card reader on the engineering PC.
- Create the folder structure required by the S7-1200 update: place the firmware
.updfile and theS7_JOB.S7Strigger file at the root of the card. The trigger file content is plain text and is generated by selecting PLC > Memory Card File Browser > Firmware Update in TIA Portal, or manually written as:// S7_JOB.S7S Firmware_Update - Safely eject the SMC and power down the target CPU.
- Insert the SMC into the CPU's card slot.
- Power on the CPU. The RUN/STOP, MAINT, and ERROR LEDs cycle to indicate a firmware read; the CPU copies the firmware from the card into internal flash, then performs an automatic restart.
- After the restart, remove the SMC. The card is no longer required for normal operation.
.upd file does not match the CPU order number. Re-extract the correct HSP and repeat the procedure.Firmware Downgrade Considerations
Downgrading firmware on the S7-1200 is technically supported by Siemens only when moving to a version that the TIA Portal descriptor knows. Practical cases that drive a downgrade request include:
- Reclaiming V1.0 behavior on a V2.0 CPU to match an existing V10.5 project archive that cannot be re-engineered.
- Reversing a misapplied firmware push from a mismatched project download.
- Replicating a test environment that runs at a known firmware level for reproduction of a support case.
The mechanics of a downgrade are identical to an upgrade (online or SD card), only the source and target versions change. Note that features introduced after the target version (for example, OPC UA on V4.x) are no longer available after the downgrade, but the user program in the CPU is preserved.
Educational Kit Specifics
Siemens has historically sold educational kits containing 6 × CPU 1214C AC/DC/Rly (order number 6ES7214-1BE30-0XB0) bundled with STEP 7 V10.5 SP1 on six DVDs. The factory firmware on these CPUs at the time of the kit was V2.0, but V10.5 SP1 only supports V1.0 device descriptors. The result is that an end-user running the bundled software against the V2.0 CPU will see the project compile and download as a V1.0 configuration, masking the V2.0 web server and optimized block access features.
For institutions in this situation, the supported recovery path is:
- Upgrade the engineering tool to TIA Portal V13 or later (free for educational licensees through the Siemens Automation & Drives educational program).
- Install the matching HSP for the desired firmware level (V2.0, V4.0, V4.4, V4.6, or V4.7).
- Perform an online firmware update or an SD card update to bring the CPU firmware to match the project.
Contacting the local Siemens field office for a firmware-update visit is the recommended path when six or more CPUs are involved; Siemens field representatives can perform the updates in a single session using a card writer and pre-loaded firmware.
Verification and Diagnostics
After any firmware change, verify the new state using the following checks:
- Online > Online & Diagnostics > Diagnostics > Device Information: confirm the firmware version reported by the CPU matches the project target.
- Project > Compile > Software (rebuild all): a clean compile after the firmware change verifies that no block attributes rely on features that have moved or been renamed between versions.
-
Web server test: navigate to
http://<cpu-ip>/from a browser. A V2.0+ CPU will expose the user-defined web pages; a V1.0 CPU only shows the diagnostic default page. - Diagnostic buffer read: in Online & Diagnostics, open Diagnostics Buffer. A clean firmware update leaves an event of category "Firmware update successful" with the old and new version strings. Any error events here point to a partial flash and require a repeat of the procedure.
- PROFINET device name and IP: firmware updates do not change the IP address or PROFINET device name on the CPU, but a power-cycle is recommended to confirm network reattachment.
Troubleshooting Matrix
| Symptom | Likely Cause | Corrective Action |
|---|---|---|
| MAINT LED flashing after SD card update | Article number mismatch between .upd file and CPU |
Re-extract the correct HSP for the CPU MLFB and repeat the SD card procedure |
| ERROR LED solid, CPU in STOP after online update | Power loss during flash | Re-attempt the update; if the CPU fails to recover, contact Siemens support with the diagnostic buffer export |
| Project compiles but web server is not visible | CPU firmware is V1.0 (web server V2.0 features not available) | Update CPU firmware to V2.0 or higher, then recompile with the matching device descriptor |
| TIA Portal V10.5 cannot select V2.0 in device configuration | TIA Portal version too old to know the V2.0 descriptor | Upgrade TIA Portal to V11 or later; or install the V2.0 HSP that matches the TIA Portal version |
| Firmware update option is greyed out in TIA Portal | HSP not installed; no firmware files in the PG cache | Open Options > Support Packages and install the S7-1200 HSP for the target TIA Portal version |
| CPU reports "Firmware update failed - signature invalid" | Unsigned or modified firmware file | Re-download the firmware from Siemens Industry Online Support and verify the SHA hash |
| Downloaded program is missing UMAC users | CPU was downgraded from V4.7 to a lower version after the user list was created | Re-upgrade to V4.7 and restore the user list from the TIA Portal project |
Field-Commissioning Checklist
- Confirm the CPU MLFB and the firmware version printed on the front of the CPU against the project target.
- Verify the TIA Portal version installed on the PG supports the target firmware descriptor; otherwise install the matching HSP.
- Capture a project backup (
.ap14,.ap15,.ap16, or.ap17depending on TIA Portal version) before any firmware operation. - Document the old and new firmware versions in the commissioning log; this is mandatory for support case escalation.
- For fleet updates, label each SMC with the target CPU MLFB and firmware version to avoid cross-application errors.
- After the update, perform a STOP-to-RUN transition under no load and observe the diagnostic buffer for one scan cycle before reconnecting field wiring to actuators.
Frequently Asked Questions
Can a TIA Portal V10.5 project be used to write firmware to a V2.0 S7-1200 CPU?
No. TIA Portal V10.5 only knows the V1.0 device descriptor. Loading a V10.5 project into a V2.0 CPU coerces the CPU to behave as a V1.0 device, masking V2.0 features. Use TIA Portal V11 or later with the V2.0 HSP installed to access the V2.0 feature set.
Is the SD card strictly required to update S7-1200 firmware?
No. The online method via Online & Diagnostics > Firmware Update in TIA Portal is the preferred path and does not require a SIMATIC Memory Card. The SD card is used for offline updates when the CPU is not network-reachable or when an entire fleet must be brought to a common baseline.
Does a firmware update erase the user program in the CPU?
No. Siemens preserves the user program, IP address, and PROFINET device name across firmware updates. A project backup on the engineering PG is still mandatory engineering practice and is required for any support case escalation.
What is the latest firmware available for the S7-1200?
As of the current Siemens release notes, firmware V4.7 is the latest published release for the S7-1200 family. V4.7 introduces User Management & Access Control (UMAC) and is documented in support entry 109976907. Firmware V4.6 (entry 109814248) is the preceding major release.
How long does an S7-1200 firmware update take?
Typical S7-1200 firmware updates complete in 1 to 3 minutes for the online method and 2 to 5 minutes for the SD card method, followed by an automatic CPU restart. The duration scales with the firmware file size and the write performance of the SMC.