SIMOTION C240 MMC License Assignment Error: Hardware Fix

David Krause11 min read
Motion ControlSiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Summary

A SIMOTION C240 controller (MLFB 6AU1240-1AA00-0AA0, hardware release D per the type plate marking A5E00346777 VERSION D) returns the message "license cannot be assigned and or has been assigned already" when the engineer attempts either of the following actions in SIMOTION SCOUT:

  1. Pressing the Accept button after SCOUT has discovered the C240 on Ethernet (the Accept control remains grayed out / inactive).
  2. Registering the runtime license key from the CoA (Certificate of License) paper against the controller's MMC serial number on the Siemens web license portal.

Concurrent symptoms include a steady-blinking SF (System Fault) LED on the C240 after the MMC has been inserted and the controller booted. The BF (Bus Fault) LED behavior, RUN/STOP states, and the 7-segment display code provide additional diagnostic data that must be captured before the controller is reset.

Critical: This failure mode is not caused by a corrupted MMC, a wrong CoA number, or a Scout installation error. The root cause is a hardware release constraint on the C240 that is silently violated when a V5.x firmware MMC is inserted. Do not attempt to re-flash the MMC with V5.x firmware - it will not clear the SF LED.

Affected Hardware Identification

Before applying any firmware work, capture and verify the type plate data on every C240 in scope. The hardware release letter is the single most important value for compatibility.

Component MLFB / Order Number Data Shown on Source
SIMOTION C240 controller 6AU1240-1AA00-0AA0 A5E00346777 VERSION D
MMC card (firmware/license carrier) 6AU1720-1KA00-0AA0 V5.4 SP3, 64 MB, Bootloader V1.2.0.0, single license
SIMOTION SCOUT (engineering) V5.4 SP3 Matches the MMC firmware generation

The hardware release letter (A, B, C, ... G, H, ...) is printed after "VERSION" on the type plate. It is not the same as the firmware version, the Scout version, or the MMC card's software version. Mixing these three version axes is the most common cause of "the controller should work but it doesn't" incidents on the SIMOTION C platform.

Root Cause: Hardware/Firmware Version Mismatch

SIMOTION controllers enforce a one-way compatibility rule between the controller hardware release and the SIMOTION runtime firmware loaded onto the MMC. From SIMOTION runtime V4.5 onward, the C240 platform requires a controller with hardware release G or higher. Controllers with hardware releases A through F cannot boot a V4.5 or V5.x runtime; the bootloader rejects the firmware image, the SF LED starts to blink, and the license key on the MMC is reported as "already assigned" because the runtime that owns the license never came up to validate it.

The reported controller has hardware release D. The MMC ships with V5.4 SP3 firmware. The combination is therefore incompatible at the bootloader level, and no amount of project re-creation, license re-registration, or Scout reinstallation will resolve it. The fix is to match the runtime firmware to the hardware release, not to upgrade the hardware.

SIMOTION C240 Hardware/Firmware Compatibility Matrix

The matrix below summarizes the compatibility boundaries relevant to C240 hardware releases A through H. The authoritative list is the SIMOTION Compatibility List at the Siemens support page cited below.

C240 Hardware Release Maximum Supported SIMOTION Runtime Minimum SCOUT Version Notes
A V4.1 / V4.2 SCOUT V4.2 Legacy projects only
B V4.2 SCOUT V4.2 -
C V4.3 SCOUT V4.3 -
D V4.4 (HF11 recommended) SCOUT V4.4 or SCOUT V5.4 (cross-mode) Configuration in scope of this article
E V4.4 SCOUT V4.4 -
F V4.4 (last hot-fix chain) SCOUT V4.4 -
G V4.5 / V5.x SCOUT V5.x First release supporting V4.5+ runtime
H and later V5.x (latest SP) SCOUT V5.x (latest SP) Current production

Source: SIMOTION Compatibility List (Entry ID 18857317), page 9 of 45 (controller/hardware compatibility table) and page 39 of 45 (MMC compatibility table).

Required Firmware Selection

For a C240 with hardware release D, the supported SIMOTION runtime is the V4.4 line. The recommended hot-fix level is V4.4 HF11, which carries all released defect corrections for the V4.4 line and is the version Siemens continued to validate against late-life C240 hardware. The runtime files are distributed as a single .zip archive containing the MMC image (SIMOTION_C240.bin or equivalent) plus the SCOUT add-on.

Download the V4.4 HF11 image from the official Siemens support entry:

SCOUT cross-mode operation: SCOUT V5.4 can open, edit, compile, and download projects targeting a V4.4 runtime. SCOUT prompts the user when a V4.4 runtime is detected on the target and offers the appropriate project format. This means the existing V5.4 SP3 SCOUT installation does not need to be uninstalled; only the MMC firmware must be downgraded to V4.4 HF11.

MMC Card Verification Before Re-flashing

Before writing a new firmware image to the MMC, confirm the card itself is healthy. The MMC carries the runtime, the technology packages, the user program, and the runtime license. A failing MMC will produce symptoms that look like a firmware mismatch.

Check How Expected Result
MMC readable in card reader Insert MMC in a PC card reader; check that the FAT partition appears. Partition SIMOTION visible, ~60 MB free of ~64 MB
Bootloader revision Read SYSTEM.LOG on the MMC or use Scout's "Accessible nodes" diagnostics after a partial boot. Bootloader V1.2.0.0 (matches source) - bootloader is independent of runtime major version
License key file Open KEYS.TXT on the MMC and confirm the license key from the CoA paper is present. One license line per C240; license key matches the CoA paper exactly
Card write-protect Inspect the MMC housing for a mechanical write-protect slider. Slider must be in the unlocked position before flashing

Step-by-Step Recovery Procedure

The procedure restores the C240 to a bootable state with the firmware the hardware can actually run. Total time on a single controller is typically 20 to 35 minutes, dominated by the MMC write operation and the firmware download.

Step 1 - Capture project archive (if controller still partially responsive)

  1. Power the C240 and insert the MMC with V5.4 SP3 firmware.
  2. Connect the engineering PC to the C240's RJ45 (X127) port.
  3. In SCOUT, open Project > Accessible nodes. The C240 should appear with its IP address and the system fault banner.
  4. If the controller is still online enough to read the project, perform Project > Save project archive before any further action.

Step 2 - Power down and remove the MMC

  1. Switch off the 24 V supply to the C240. Wait at least 10 s for the internal capacitors to discharge.
  2. Press the MMC ejector to release the card. Do not use tools.

Step 3 - Write V4.4 HF11 to the MMC

  1. Insert the MMC in the PC's SD/MMC card reader.
  2. Back up any user files (USER/, project archives, recipes) to a separate folder on the PC. The next step will erase the card.
  3. Unzip the V4.4 HF11 firmware archive downloaded from Entry ID 31263919.
  4. Run the included write tool (SIMOTION_MMC_Writer.exe or the Scout-integrated Write MMC image action). Select the correct drive letter for the MMC and the V4.4 HF11 image.
  5. Wait for the write to complete and verify the tool's success message. Do not interrupt the write.

Step 4 - Restore the license key

  1. Open the MMC partition in Windows Explorer. The new image contains a KEYS.TXT with placeholder lines.
  2. Edit KEYS.TXT (use Notepad in administrator mode if Windows protects the file) and replace the placeholder with the license key from the CoA paper. Save.
  3. Eject the MMC safely through the operating system.

Step 5 - Re-insert and power up

  1. Insert the MMC into the C240 with the controller powered off.
  2. Apply 24 V. Observe the LED sequence.
  3. The expected sequence: SF LED on briefly, then a 5 to 15 s period where the bootloader decompresses the runtime, then a slow regular blink from the SF LED for ~30 s during the initial project load, then SF off, RUN green.

Step 6 - Recreate the SCOUT project

  1. In SCOUT V5.4, create a new project. Select controller type SIMOTION C240.
  2. Set the Ethernet address of the new project to match the C240's X127 address range. The C240 default is 169.254.11.22; the engineering PC must be on the same subnet (commonly 169.254.x.y / 16 or a static IP such as 192.168.0.1 / 24 with the C240 set to 192.168.0.2).
  3. Use Project > Download to target with the option Download project to target with reset (PO without reset is acceptable once the project matches the target configuration).
  4. Wait for the download to complete. SCOUT will report Target state: RUN.

Ethernet Addressing Constraints

SCOUT will refuse the "Accept" action when the controller's configured IP and the engineering PC's IP are not on the same subnet or when a firewall blocks UDP broadcast on the SIMOTION discovery ports. The two most common discovery failure modes and their fixes:

Symptom in SCOUT Likely Cause Remedy
C240 visible in Accessible nodes, Accept button grayed Project IP address range does not match controller IP Recreate project with correct controller type, set Ethernet interface to the same subnet, set the controller's IP via the rotary switches or via the SCOUT assignment
C240 not visible at all PC on different subnet, firewall blocking UDP, or wrong RJ45 port Use X127 (top port) for engineering; disable Windows firewall or add Scout exception; set a static IP on the PC
C240 visible, Accept fails with "already assigned" Firmware/runtime mismatch (this article) Apply the V4.4 HF11 fix per Step 3

Verification

After completing Step 6, confirm the controller is fully operational:

  1. LED state: SF off, BF off, RUN solid green. The 7-segment display shows 8 (boot OK) momentarily then - or a node number.
  2. Scout diagnostics: Target system > Diagnostics > Version overview shows runtime V4.4.0.x (HF11 build number).
  3. License status: Target system > Licenses shows the CoA license key as valid and assigned to the C240 with the correct MMC serial number.
  4. Project round-trip: Project > Save project archive and Project > Read from target both complete without errors.
  5. Runtime test: Set a test output, toggle from SCOUT, observe the C240's digital output hardware indicator LED.

Troubleshooting Matrix

Observed Symptom Probable Cause Corrective Action
SF LED steady blink after MMC insertion; "already assigned" error C240 hardware release below required for MMC firmware Downgrade MMC firmware to the highest runtime supported by the hardware release
SF LED rapid blink at power-up; no Ethernet response Corrupted MMC or write interrupted Re-write MMC with known-good image; verify card integrity in PC reader
License rejects the CoA key, error "license not valid for this serial number" License key assigned against a different MMC serial number Re-register license against the correct MMC serial number on the Siemens web license portal
SCOUT sees C240 but Accept is grayed Project IP address range differs from controller IP Set the controller's IP via rotary switches or set the project IP to the same subnet; recreate the project if necessary
SF LED on, license accepted, but RUN does not start Technology package (TP) version on MMC incompatible with project TP version Reinstall the matching TP version using SCOUT V4.4
BF LED on solid PROFIBUS or PROFINET cable/connector fault, or wrong slave address Check cabling, termination, slave addresses; consult Scout's Accessible nodes over PROFIBUS
C240 with hardware release G or later still shows "already assigned" License genuinely already assigned to a different controller or MMC; user trying to reuse a license Verify the license is unassigned on the web portal; reuse of a CoA license on multiple controllers is not supported

Field-Proven Cautions

  • Never power-cycle the C240 during the initial 30-second MMC boot sequence. Removing power mid-decompress can corrupt the MMC and produce a secondary failure mode that masks the original "already assigned" message.
  • Do not attempt to flash firmware V4.5 or V5.x onto a hardware-release D C240, even "just to test." The bootloader will reject the image, but the failed flash can leave the MMC in a state that requires re-imaging on a PC.
  • Always back up the user project, recipes, and the USER/ directory from the MMC before re-imaging. Re-imaging overwrites everything except the bootloader partition.
  • License keys are MMC-bound, not controller-bound. Moving an MMC to a different C240 transfers the license to that controller's serial number; the web portal must be updated to match.
  • SCOUT cross-mode: SCOUT V5.4 can manage V4.4 targets, but the reverse is not true - SCOUT V4.4 cannot load a V5.x project. Plan engineering PC installations accordingly.
  • Hardware release G is the boundary for V4.5+ runtime support. If the application requires V5.x features (for example, new technology packages), the C240 hardware must be replaced - the controller cannot be firmware-upgraded past its hardware release boundary.

Related Documentation

Why does my C240 hardware release D reject a V5.4 MMC with "license already assigned"?

The message is misleading. The C240 hardware release is below the minimum required for the SIMOTION V4.5/V5.x runtime, so the bootloader never finishes initializing and cannot read the MMC's license file. Downgrade the MMC firmware to V4.4 HF11 to match the hardware release.

Which SIMOTION runtime is the highest version a C240 hardware release D can run?

V4.4, with V4.4 HF11 as the recommended hot-fix level. V4.5 and later require hardware release G or higher.

Do I need to uninstall SCOUT V5.4 to work with a V4.4 runtime?

No. SCOUT V5.4 supports V4.4 runtimes in cross-mode and will prompt to convert the project when the target runtime is detected. Only the MMC firmware needs to change.

What is the MLFB for the C240 and the recommended MMC?

The C240 controller is 6AU1240-1AA00-0AA0. For a hardware release D controller, use MMC 6AU1720-1KA00-0AA0 loaded with V4.4 HF11 firmware and a single runtime license.

Can I upgrade a C240 hardware release D to support V5.x firmware?

No. The hardware release is fixed by the type plate and cannot be changed by firmware. To use SIMOTION V5.x features, replace the C240 with a hardware release G or later unit.