SINAMICS S120 CU320-2 PN Firmware 4.4 Compatibility

David Krause14 min read
SiemensTroubleshootingVFD / Drives
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Problem Overview

After upgrading the SINAMICS S120 control unit CU320-2 PN (6SL3040-1MA01-0AA0) to firmware V4.4, the control unit refuses to load an offline project that was originally commissioned on a CU320-2 running firmware V2.4. The downstream hardware in the affected cabinets includes the Double Motor Module 6SL3120-2TE13-0AA0 and the Smart Line Module 6SL3130-6AE21-0AA0. STARTER / Startdrive aborts the download during topology validation with a Drive-CLiQ (DQ) component mismatch, and the control unit surfaces F0135x faults on power-up.

The technical root cause is that the 6SL3040-1MA01-0AA0 variant is supported only from firmware V4.4.x onward. The boot loader on this article number checks the firmware signature against an expected range; a V2.x card image is rejected at boot, before parameter download begins. Even when the card image is accepted, the V4.4 topology objects expect component identifiers and parameter layouts that did not exist on V2.4-era DQ components.

The CU320-2 PN order number 6SL3040-1MA01-0AA0 is supported as from firmware V4.4.x. Downgrading to V2.4 on this hardware is not a supported configuration.

Affected Hardware Components and Article Numbers

Use the table below to identify the components involved in the fault and their role in the SINAMICS S120 topology. Always cross-reference the MLFB on the rating plate before ordering firmware cards or replacement parts.

Component MLFB (Order Number) Role in Topology Firmware Constraint
CU320-2 PN (control unit) 6SL3040-1MA01-0AA0 Central drive controller with integrated PROFINET FW V4.4.x or higher only
Double Motor Module 6SL3120-2TE13-0AA0 Two-axis Motor Module on DQ Requires matching FW generation
Smart Line Module 6SL3130-6AE21-0AA0 Regenerative line infeed Requires matching FW generation
Legacy CU320 6SL3040-0MA00-0AA1 First-generation control unit Last released FW V2.6.2
CBE20 (communications board) 6SL3055-0AA00-2EB0 PROFINET option for legacy CU320 Inserts into option slot
SMC / TM modules Various (6SL3055-0AAxx) Sensor Module Cabinet / Terminal Module FW must match CU generation
SMC and TM modules in the same cabinet must be on the same firmware generation as the control unit. Mixed V2.x / V4.x components on a single DQ ring are not supported.

Root Cause: Firmware Architecture Shift

SINAMICS S120 firmware V4.x restructured the parameter set, the Drive-CLiQ topology descriptors, and the Safety Integrated channel map relative to the V2.x baseline. The parameter p0009 (Device commissioning parameter filter) carries a different scope, the topology objects compiled at offline time include new component identifiers, and the Safety Integrated telegram layout was extended. The CU320-2 PN 6SL3040-1MA01-0AA0 was introduced with the V4.x generation; its file system and CF card layout are physically incompatible with V2.4 images.

Boot signature check

At power-up, the control unit reads the firmware signature from the inserted CF card and validates it against the range expected by the hardware variant. The 6SL3040-1MA01-0AA0 expects a V4.4.x or higher image. A V2.x card produces a non-matching signature and the boot process halts without loading parameters. There is no field procedure to override this check; the only remedies are (a) use a V4.4.x image, or (b) replace the control unit hardware with a variant that supports V2.x.

Topology migration is not equivalent to firmware downgrade

Even when the V2.4 image loaded successfully, the V4.4 Drive-CLiQ topology objects expect component identifiers and parameter layouts that did not exist on V2.4-era components. The fault appears during the first commissioning download, not during parameter editing. STARTER / Startdrive reports component firmware mismatches at the DQ ports, and the affected drives remain in commissioning lock.

Firmware Compatibility Matrix

Use this matrix to determine whether a hardware swap or a firmware swap is the cheapest path forward. For each component, note the lowest supported firmware version, the recommended firmware version, and the compatibility with a V2.4 topology compiled offline.

Hardware Lowest Supported FW Recommended FW Compatibility with V2.4 Topology
CU320-2 PN (6SL3040-1MA01-0AA0) V4.4.x V4.4 or latest No - rejects V2.4 image at boot
Legacy CU320 (6SL3040-0MA00-0AA1) V2.4 V2.6.2 Yes - native support
Double Motor Module (6SL3120-2TE13-0AA0) Per module CF card Match CU generation Yes on V2.6.2; conditional on V4.4
Smart Line Module (6SL3130-6AE21-0AA0) Per module CF card Match CU generation Yes on V2.6.2; conditional on V4.4
CBE20 (6SL3055-0AA00-2EB0) Per board CF Match CU generation Required for PROFINET on legacy CU320
Verify the firmware version embedded on each component's CF card before changing topology. A V4.4 image cannot be downgraded to V2.x via CF card on the CU320-2 PN.

Solution Paths

Three engineering paths resolve the compatibility fault. Select the path that matches your cabinet count, budget, and forward-looking I/O architecture.

Path A: Migrate Drive-CLiQ topology to V4.4 components

This path keeps the CU320-2 PN hardware and the V4.4 firmware generation. Replace the affected Motor Modules and Line Module with V4.4-compatible equivalents, and update all SMC and TM modules on the same DQ ring to match. This is the correct path when V4.4 components were the long-term target anyway.

  1. Inventory all DQ-attached components and record each MLFB from the rating plate.
  2. Cross-reference each MLFB against the SINAMICS S120 V4.4 compatibility list in the firmware release notes.
  3. Order replacement modules with the appropriate CF card image for V4.4.
  4. Update the offline STARTER / Startdrive project to reference the new MLFBs.
  5. Run the topology comparison and load the project to the control unit.
  6. Verify drive object assignment: 1 Line Module plus up to 6 Servo drives (or the equivalent Vector configuration).
  7. Execute the Safety Integrated acceptance test if Basic Safety is configured.

Path B: Revert to legacy CU320 with FW V2.6.2

This is the most cost-effective alternative when only the CU320-2 PN was ordered in error and the existing V2.4 components are to be retained. The legacy CU320 (6SL3040-0MA00-0AA1) supports EPOS, retains the same maximum drive count as the CU320-2, and accepts the original V2.4 topology objects. PROFINET is added via the CBE20 communication board.

Legacy CU320 Configuration Limits

  • Servo control: 1 Line Module + 6 Drives maximum.
  • Vector control: Reduced drive count; consult the SINAMICS S120 function manual for the exact limit on the chosen drive type.
  • EPOS (Basic Positioner): Supported.
  • PROFINET: Available with CBE20 inserted into the option slot.
  • PROFIBUS: Integrated on the legacy CU320.

Commissioning steps (legacy path)

  1. Order CU320 (6SL3040-0MA00-0AA1) and CBE20 (6SL3055-0AA00-2EB0).
  2. Insert a CF card with SINAMICS S120 FW V2.6.2 image.
  3. Connect the CBE20 to the option slot and wire PROFINET to the PLC.
  4. Load the existing V2.4 offline project; verify Drive objects 1-6 map correctly.
  5. Configure the PLC (e.g., SIMATIC S7-300 / CPU 315-2 PN/DP) PROFINET interface to the new control unit.
  6. Assign the PROFINET device name and IP via the Topology Editor or the PRONETA tool.
  7. Run the drive acceptance test and verify Safety Integrated if enabled.

Path C: SIMATIC Drive Controller with SINAMICS Integrated

For greenfield installations, the SIMATIC Drive Controller embeds SINAMICS Integrated that exposes the same Safety Integrated Basic Functions as the standalone CU320-2. This consolidates PLC and drive control into a single device and removes the separate control unit from the PROFINET line.

SINAMICS Integrated on the SIMATIC Drive Controller provides equivalent Safety Integrated Basic Functions to a standalone CU320-2. Verify the exact Safety version supported against the SIMATIC Drive Controller firmware release notes for your TIA Portal version.

Drive-CLiQ Topology and Component Rules

Drive-CLiQ is the internal bus between the control unit, line modules, motor modules, and sensor modules in a SINAMICS S120 cabinet. Rules enforced by the topology check include:

  • Single firmware generation: All DQ-attached components must run firmware from the same generation. Mixing V2.x and V4.x components on a single DQ ring is not supported.
  • No loops: The DQ topology is a tree; closed rings produce topology faults at commissioning.
  • Port mapping: The control unit DQ ports (X100-X105) are populated in a defined order; the port nearest the Line Module is typically the first Motor Module port.
  • Cable length: Standard DQ cables support up to 70 m. Longer runs require fiber-optic DQ cabling with DQI converters.
  • Maximum stations: The CU320-2 / CU320 supports up to 16 DQ stations per ring, limited by the firmware generation and drive type.

When migrating from V2.4 to V4.4, treat every DQ station as a candidate for firmware update. The CU firmware alone does not bring the cabinet onto V4.4 - every Motor Module, Line Module, SMC, and TM must be brought to the same generation.

Drive Object Configuration and PROFINET Integration

Drive object (DO) layout

The SINAMICS S120 control unit organises drive objects in a fixed numeric map. The standard layout is:

  • DO 1: Control Unit (CU320 / CU320-2)
  • DO 2: Line Module (Smart Line Module / Active Line Module / Basic Line Module)
  • DO 3, 4, 5, 6, 7, 8: Drives (up to 6 on Servo configuration)
  • DO 9+: Optional terminal modules, SMC, or additional DO slots defined by the project

PROFINET integration on CU320-2 PN

The CU320-2 PN has PROFINET integrated on the control unit itself. Two PROFINET ports (X150 P1, X150 P2) are available. The control unit acts as a PROFINET IO Device with a configurable device name and IP. Telegrams from the IO Controller map to the drive objects via the slot configuration in the GSDML file.

PROFINET integration on legacy CU320 with CBE20

The legacy CU320 does not include PROFINET. Insert the CBE20 board into the option slot to add PROFINET connectivity. The CBE20 provides two PROFINET ports and uses its own firmware image that must match the control unit firmware generation.

Parameter Address / Tag Function Typical Range
r0018 / r0976 Control Unit parameter Firmware version read-out V2.6.2 - V5.x depending on CU
p0009 Control Unit parameter Device commissioning filter 0 (Run) - 30 (Reset)
p0100 Drive object Drive type (Servo / Vector / V/f) 0, 1, 2, 3, 4, 5, 6
p0922 Drive object PROFIdrive telegram selection 1 - 7, 9, 110, 111
p2030 Control Unit PROFINET / PROFIBUS fieldbus interface 0 (no), 1 (PN), 2 (PB)

EPOS and PROFIdrive Telegram Mapping

EPOS (Basic Positioner) is supported on the legacy CU320 running V2.6.2 and on the CU320-2 PN running V4.4.x. Telegram 111 is the standard EPOS telegram; it carries position setpoint, position actual value, status word, and control word across the PROFINET boundary. When migrating from PROFIBUS to PROFINET, the cyclic data mapping must be reconfigured; the slot assignment is recreated from the GSDML file rather than copied directly from the PROFIBUS configuration.

PROFIdrive Telegram Function Servo / Vector Notes
Standard 1 Speed setpoint, 16-bit V/f Basic V/f mode
Standard 2 Speed setpoint, 32-bit Servo / Vector Standard Servo
Standard 3 Speed + 2 position encoders Servo Position feedback
Standard 5 Servo with DSC Servo Dynamic Servo Control
Standard 7 Positioning with 32-bit Servo Positioning mode
SIEMENS 110 Servo with extended channel Servo Vendor-specific extension
SIEMENS 111 Servo with EPOS Servo Required for Basic Positioner
SIEMENS 220 Servo with DSC + EPOS Servo High-performance EPOS
SIEMENS 999 Free configuration Servo / Vector User-defined mapping

Firmware Update Procedure (V2.x to V4.4.x)

Per the official Siemens update instructions, the supported update path on the CU320-2 PN is V4.3.x to V4.4 (and higher). Direct upgrade from V2.x to V4.4 in a single step is not supported because the boot loader signature check on the 6SL3040-1MA01-0AA0 expects a V4.x intermediate image. Use STARTER / Startdrive with a PC connected to the CU320-2 PN service interface (X127) or via the plant network.

Update sequence

  1. Back up the parameter set using STARTER / Startdrive (Project > Save to memory card).
  2. Verify the current firmware version on the control unit via parameter r0018 or r0976.
  3. Insert a CF card containing the V4.4.x firmware image; the control unit auto-detects on power-up.
  4. Wait for the LED sequence: RDY green steady, COM green steady. Do not interrupt power.
  5. Reload the project and verify the topology comparison report.
  6. Update downstream component CF cards to match the control unit generation.
  7. Run the Safety Integrated acceptance test if Basic Safety is configured.
A firmware update on the CU310-2 / CU320-2 must use a card image compatible with the target hardware. Confirm the article number on the card label matches the control unit rating plate before powering up.

LED Diagnostics and Fault Code Reference

Control unit LED indicators

LED State Meaning
RDY (Ready) Green steady Control unit operational
RDY Green flashing 0.5 Hz Commissioning or factory reset in progress
RDY Red steady Firmware error or hardware fault
RDY Red flashing 2 Hz General fault, see buffer
COM (Communication) Green steady PROFINET / PROFIBUS cyclic communication active
COM Off No cyclic communication
SAFE Yellow steady Safety Integrated active

Common fault codes

Fault Code Cause Remedy
F0135x Drive-CLiQ topology component mismatch Update component firmware to match CU generation
F0164x CF card signature invalid Insert CF card with matching firmware image
A0190x PROFINET connection lost Check PROFINET cable and device name
F0850x Safety Integrated fault Re-run Safety acceptance test
F3000x Power unit fault Check Motor Module / Line Module diagnostics
The fault code ranges above are typical for SINAMICS S120. Always read the detailed fault value and remedy via STARTER / Startdrive, because the specific sub-code determines the exact corrective action.

Verification and Commissioning Checklist

  1. Article number check: Confirm the CU320-2 PN label reads 6SL3040-1MA01-0AA0 before any firmware operations.
  2. Firmware version: Parameter r0018 (or r0976) returns the installed FW; cross-check against the SINAMICS S120 compatibility list.
  3. Topology diagnostics: The Drive-CLiQ diagnostics page in STARTER shows green port status for every DQ port.
  4. Drive object count: DO 1 = Control Unit, DO 2 = Line Module, DO 3+ = drives. Maximum 6 drives on Servo configuration.
  5. Safety Integrated: If Basic Safety is configured, verify Safety functions pass the acceptance test.
  6. PROFINET connectivity: Ping the control unit from the PLC engineering station; verify the device name and IP are set.
  7. EPOS homing: Perform reference run for each EPOS-configured axis.
  8. Brake check: Run the brake control test if the drive is configured with a holding brake.
  9. Encoder check: Verify the encoder actual value matches the mechanical position after homing.

Field Troubleshooting Matrix

Symptom Likely Cause Action
CF card with V2.4 image not recognised on CU320-2 PN 6SL3040-1MA01-0AA0 requires V4.4.x Use a V4.4.x CF card or revert to legacy CU320
F0135x fault on first commissioning download Topology contains V2.4 component firmware references Update component CF cards to V4.4 or migrate to legacy CU320
Drive object count limited to 2 (Servo mode) Vector mode selected instead of Servo Switch drive type via p0100 in project configuration
PROFINET not visible on legacy CU320 CBE20 not inserted or firmware mismatch Insert CBE20 and verify option slot firmware matches CU generation
EPOS reference run fails Encoder not configured or telegram missing Configure encoder; assign SIEMENS Telegram 111 to the drive
SMC / TM module not detected Mixed V2.x / V4.x firmware on the DQ ring Update all components to a single firmware generation
Safety acceptance test fails Safety version mismatch between CU and Motor Module Align Safety Integrated firmware versions across the DQ ring
PLC loses cyclic connection during drive motion PROFINET watchdog too short for the cycle Increase PROFINET watchdog time; verify cycle time matches drive cycle
F3000x on Motor Module Power unit overcurrent or ground fault Check motor wiring; verify parameter p0290 (current limit)

Field-Engineered Recommendations

When the cabinet contains more than five affected components (Motor Modules, Line Modules, SMCs, TMs), the cost analysis typically favours Path B (legacy CU320 with V2.6.2) because new modules plus a V4.4 commissioning cycle exceed the price of one CU320 plus CBE20. Reserve Path A for greenfield installations where V4.4 components can be ordered from the start.

Always confirm the control unit MLFB before ordering firmware cards. The boot loader signature check is enforced at the hardware level and cannot be bypassed via parameter changes. The official Siemens firmware update instructions for the CU310-2 / CU320-2 document the supported image-to-hardware matrix.

For new installations where Safety Integrated is required and a compact footprint is preferred, evaluate the SIMATIC Drive Controller with SINAMICS Integrated as a single-device alternative that exposes the same Safety Integrated Basic Functions as the standalone CU320-2.

Can I downgrade the CU320-2 PN 6SL3040-1MA01-0AA0 to firmware V2.4?

No. The 6SL3040-1MA01-0AA0 hardware variant is supported only from firmware V4.4.x onward. The boot loader rejects V2.x card images at power-up.

What is the maximum drive count on a legacy CU320 with FW V2.6.2?

For Servo control the legacy CU320 supports 1 Line Module plus up to 6 Drives. Vector control carries a lower maximum; consult the SINAMICS S120 function manual for the exact value on the chosen drive type.

Can I add PROFINET to the legacy CU320?

Yes. Insert the CBE20 communications board (6SL3055-0AA00-2EB0) into the option slot; the legacy CU320 then communicates over PROFINET instead of PROFIBUS.

Does EPOS work on the legacy CU320?

Yes. EPOS is supported on the legacy CU320 running firmware V2.6.2; assign PROFIdrive SIEMENS Telegram 111 to the drive.

Is SINAMICS Integrated equivalent to a standalone CU320-2?

SINAMICS Integrated on the SIMATIC Drive Controller exposes the same Safety Integrated Basic Functions as a standalone CU320-2. For higher Safety Integrated levels or specific extended functions, verify against the SIMATIC Drive Controller firmware release notes for your TIA Portal version.