SINAMICS S120 Startdrive: Resolving ALM Enable and EP Faults

David Krause13 min read
SiemensTIA PortalTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Overview

This guide walks through commissioning a SINAMICS S120 multi-axis drive line-up using SINAMICS Startdrive integrated into the TIA Portal. The reference line-up in this article is a typical Booksize configuration with an Active Interface Module (AIM), Active Line Module (ALM), Control Unit CU320-2 PN, a Double Motor Module, and two 1FK7 synchronous servomotors, controlled by a SIMATIC S7-1500 (CPU 1515-2 PN).

The most common first-day block when the line-up is first powered in the Startdrive commissioning tool is a chain of faults that trace back to two physical items: the 24 V supply at the EP terminal on the ALM, and the wiring of terminal X21 between the AIM and the ALM. The drive also has to be told that the ALM is part of the topology — this is done by activating the ALM in the project and assigning Siemens telegram 370 (or 371) to the infeed. This article documents the wiring, the telegram configuration, the Startdrive control-panel enable sequence, and the diagnostic workflow that turns a "Switching on inhibited" drive into a rotating motor.

Tool: SINAMICS Startdrive is the commissioning tool for SINAMICS drives inside the TIA Portal. The Startdrive product page and the "What's new" page in the TIA Portal documentation (SINAMICS Startdrive in TIA Portal v20) describe the integration scope. The commissioning manual Commissioning with Startdrive (06/2019) is the primary field reference.

Hardware Line-Up

The hardware used in this reference build is summarized in the table below. The S7-1500 is the PROFINET controller, the CU320-2 PN is the PROFINET device, and the ALM is the infeed. The Double Motor Module drives the two 1FK7042 axes.

Item Article No. Function
SIMATIC S7-1500 CPU CPU 1515-2 PN PROFINET IO controller, motion task
Active Interface Module 6SL3100-0BE21-6AB0 Line filter, pre-charging, X21 enable chain
Control Unit CU320-2 PN (6SL3040-1MA01-0AA0) Drive-side PROFINET device
Active Line Module 6SL3130-7TE21-6AA4 16 kW regulated infeed with Energy Recovery
Double Motor Module 6SL3120-2TE13-0AD0 2 × 3 A axis module (Booksize)
Servomotors 1FK7042-2AF71-1RA0-Z Two synchronous servomotors with absolute encoder
The Double Motor Module 6SL3120-2TE13-0AD0 has two integrated axis sections. Each section can be assigned to a separate drive object (DO) in the CU320-2 PN. The 1FK7042-2AF71-1RA0-Z is a 48 mm shaft-height servo with resolver or multi-turn absolute encoder — the option code after -Z is critical for the encoder telegram (e.g. telegram 3, 4, 5, 6 or 81–86).

System Topology and DRIVE-CLiQ Wiring

The CU320-2 PN is the DRIVE-CLiQ master for the line-up. The DRIVE-CLiQ ports are labeled X100 through X105 on the CU320-2 PN. The standard order for Booksize line-ups is:

  1. CU320-2 PN port X100 → ALM port X200 (DRIVE-CLiQ port 0 on the ALM, the right-hand RJ45 socket)
  2. ALM port X201 → AIM port X200
  3. ALM port X202 → first axis of the Double Motor Module (X200 on the first section)
  4. First section X201 → second section X200 (daisy-chain on the same Motor Module)
  5. Each motor encoder is wired to its own Motor Module section via the encoder cable on X202

DRIVE-CLiQ cables must be Siemens-approved 6SL3060-4Ax or motor-side 6FX8002 cables. Mixing wrong cables is a frequent source of F0135 (encoder/DRIVE-CLiQ topology fault).

S7-1500CPU 1515-2 PN CU320-2 PN6SL3040-1MA01-0AA0 AIM6SL3100-0BE21-6AB0 ALM6SL3130-7TE21-6AA4 DMM6SL3120-2TE13-0AD0 M11FK7042 M21FK7042 PROFINET X100 / X200 X201 / X200 X202 X21.1 / X21.2 enable chain AIM ↔ ALM

Prerequisites

  • TIA Portal V17 or newer with SINAMICS Startdrive option installed (Basic is sufficient for S120 Booksize with a GSD-based CU320-2 PN; Advanced is required for the S120 safety-integrated commissioning flows).
  • SINAMICS firmware on the CU320-2 PN compatible with the Startdrive version in use. The CU320-2 PN article number 6SL3040-1MA01-0AA0 ships with V5.x; check the CF card label and the Startdrive release notes before commissioning.
  • PROFINET names assigned to the controller and the device (e.g. plc1515pn and cu320pn).
  • 24 V control voltage present on the line-up (X124 on the CU320-2 PN, X21 on the ALM, X21 on the AIM).
  • All DRIVE-CLiQ cables connected in the order shown in the topology diagram.

Step 1 — Create the Drive Topology in TIA Portal

  1. Add a new S120 device in the TIA Portal project tree: Devices & networks → Add new device → Drives → SINAMICS S120.
  2. Select the Control Unit CU320-2 PN (6SL3040-1MA01-0AA0). Startdrive then opens the device configuration editor.
  3. Insert the AIM 6SL3100-0BE21-6AB0 at the Line infeed slot.
  4. Insert the ALM 6SL3130-7TE21-6AA4 at the infeed slot. The 6SL3130-7TE21-6AA4 is the 16 kW Booksize Active Line Module — pair it with the 16 kW AIM 6SL3100-0BE21-6AB0. The article-number pair is mandatory; the ALM will not pre-charge correctly with a mismatched AIM.
  5. Insert the Double Motor Module 6SL3120-2TE13-0AD0 at the next free slot. It exposes two drive objects by default.
  6. Insert both 1FK7042-2AF71-1RA0-Z motors. The encoder interface on a 1FK7042 in this article number is the multi-turn absolute encoder (DRIVE-CLiQ-ready) — pick the matching encoder telegram (typically telegram 6 or telegram 86 with the 1FK7 "-Z" options).

Step 2 — Wire the EP Terminal on the ALM (X21)

The "EP" terminal is the Enable Pulses input on the line modules. On the Booksize ALM 6SL3130-7TE21-6AA4, EP is part of the X21 customer terminal block. The EP input must see a 24 V signal relative to the X21 M terminal. Without 24 V at EP the infeed stays in the "Switching on inhibited" state and the control panel will refuse to start the drive.

ALM X21 Pin Signal Connection
X21.1 DI 0 (Enable AIM, link to AIM X21.1) Link to AIM X21.1
X21.2 DI 1 (Enable ALM, EP from controller / wired from AIM) Link to AIM X21.2 or 24 V from PLC
X21.3 DI 2 Application-specific
X21.4 DI 3 Application-specific
X21.5 DI 4 Application-specific
X21.6 DI 5 / EP+ 24 V (the ALM EP enable line)
X21.7 DI 6 Application-specific
X21.8 DI 7 Application-specific
X21.9 M (reference for DI 0–7) 24 V ground
Wiring rule: the 24 V enable to EP is a hard-wired chain. Even when commissioning the drive directly from Startdrive without the PLC application running, the EP pin must still be wired to +24 V. The Startdrive control panel does not generate EP; it only generates the ON/OFF1 command inside the drive. Connect ALM X21.6 (or the dedicated EP+ terminal on the X21 plug) to +24 V and ALM X21.9 (M) to the 24 V ground of the cabinet.

Step 3 — Wire the AIM to ALM X21 Enable Chain

The AIM must signal the ALM that pre-charging has finished and the line filter is healthy. The signals flow from the AIM customer terminal X21 to the ALM customer terminal X21. The minimum required wiring is:

  • AIM X21.1 (RDY1) → ALM X21.1
  • AIM X21.2 (RDY2) → ALM X21.2
  • AIM X21.3 (M) → 24 V ground (common with the ALM M terminal)

If this link is missing, the ALM reports F07840 (line contactor / AIM enable missing) and the Startdrive control panel shows the same "Switching on inhibited" state with no apparent path to clear it.

AIM X21 X21.1 RDY1 X21.2 RDY2 X21.3 M ALM X21 X21.1 DI 0 X21.2 DI 1 X21.3 DI 2 RDY1 enable Common M

Step 4 — Configure the Telegrams

The ALM is a PROFINET device in its own right. The standard infeed telegram for an Active Line Module is SIEMENS telegram 370 (PZD-16/16). Some applications use telegram 371 (PZD-6/6) for reduced data. The Motor Modules and 1FK7042 axes use standard telegrams 1, 2, 3, 4, 5, 6, 81, 82, 83, 84, 85, or 86 depending on the encoder option.

Set the telegrams in Startdrive as follows:

  1. Select the ALM in the device view.
  2. Open Properties → Telegram configuration.
  3. Insert SIEMENS telegram 370 (PZD-16/16). Telegram 370 is the ALM default; do not delete it unless you have a specific reason.
  4. On the PLC side, map the alarm bit ZSW1 bit 0 (ready to switch on), bit 1 (ready), bit 2 (operation enabled), and bit 3 (fault) into your control word to monitor state.
  5. On each axis, set the encoder telegram to 6 (for absolute encoders) and the drive telegram to 1 (standard positioning) or 2/3/4 for additional setpoints. For the 1FK7042-2AF71-1RA0-Z with the -Z option for safety, the safety telegram is integrated into the standard telegram 6.

If you omit the ALM from the PROFINET configuration, the line-up will still power up locally but no alarms, warnings, or the Line Module control word can be exchanged cyclically. The Startdrive control panel can still be used because it is a service-level tool, but the production code will need the telegram in the slot.

Step 5 — Compile and Download to the CU320-2 PN

  1. Right-click the S120 device → Compile → Hardware configuration. Resolve any topology errors before continuing.
  2. Right-click → Download to device. Confirm the PROFINET name of the CU320-2 PN matches the device label.
  3. When prompted, store the configuration to the CF card of the CU320-2 PN so it survives a power cycle. The dialog is RAM to ROM (Copy from RAM to ROM).

Step 6 — Use the Startdrive Control Panel to Move the Motor

  1. Open the S120 device in the TIA Portal project tree.
  2. Select the axis → Commissioning → Control panel.
  3. Set the control-panel enable bits in this order:
Bit Signal Source in Control Panel Comment
— EP at ALM X21 External wiring (24 V at X21.6) Hardware — must be wired first
— AIM-ALM X21 link External wiring Hardware — must be wired first
0 ON/OFF1 Check "Enable" First digital enable
1 OFF2 Leave unchecked (24 V) Coast-stop to GND
2 OFF3 Leave unchecked (24 V) Quick-stop to GND
3 Enable Pulses (drive-side) Check "Enable" Closes the drive-internal enable chain
— Setpoint Enter a low speed (e.g. 50 rpm) Used for direction test only
  1. Click Assume control priority. Startdrive takes master control of the drive. The ALM will close, the DC bus will pre-charge, the status line should turn blue or green, and the drive should reach "Operation enabled".
  2. Press Start. The motor will ramp to the setpoint.
  3. Press Stop, then Give up control priority before you hand the drive back to the PLC.

Verification

After the control-panel test passes, the following checks confirm the line-up is ready for the PLC program:

  • ALM online diagnostics: In Startdrive, navigate to Diagnostics → Status words → Line Module. The state word ZSW1 must read 0b0000 0000 0100 1111 (Operation enabled) after the enables above are applied.
  • DC bus voltage: r0070 (Control Unit) should match the line voltage × √2. For 400 V line: about 565 V DC nominal, 540–620 V acceptable.
  • Encoder feedback: r0021 of each axis must increment proportionally to the rotor angle when the motor is turned by hand. If it is stuck at zero, the encoder wiring or telegram selection is wrong.
  • Active faults buffer: r0945 / r0947 should be empty. Any active F code blocks further operation.
  • Safety slot: If the 1FK7042-2AF71-1RA0-Z carries a safety option, the safety telegram (PROFIsafe over PROFINET) must be configured and the STO must be exercised in the acceptance test.

Troubleshooting Matrix

Symptom in Startdrive Likely Fault Code Root Cause Resolution
"Switching on inhibited - connect 24 V to terminal EP" A01839 (warning) / no F code yet EP terminal not powered Apply 24 V to ALM X21 EP and confirm M is on the same 24 V ground
ALM will not close, AIM is healthy F07840 X21 wiring between AIM and ALM missing Wire AIM X21.1, X21.2, X21.3 to ALM X21.1, X21.2, X21.3
ALM closes but motors refuse to enable F08501 (PROFIdrive STOP) Missing ON/OFF1 / Enable Pulses bit from PLC Check STW1 bits 0 and 3, and the missing-enable parameter r0046
Motor moves, encoder counter r0021 = 0 F31117 / F31118 Wrong encoder telegram or DRIVE-CLiQ port Change encoder telegram to 6, check DRIVE-CLiQ cable to X202 of the Motor Module
Control panel says "Drive controlled by higher-level controller" — PROFINET control priority is held by the PLC Click "Assume control priority" in Startdrive, or remove the control bits from the PLC job
No telegram is sent on the ALM slot — ALM not configured in the PROFINET slot Insert telegram 370 in the ALM device configuration
Startdrive cannot find the CU320-2 PN online F0135 / F08501 PROFINET name mismatch Assign PROFINET name to the CU320-2 PN, then re-download

Drive Parameters Worth Recording at Commissioning

Once the line-up is moving, document the following parameters for the maintenance team:

Parameter Name Expected at First Run
r0002 Drive operating display "Operation enabled"
r0021 Speed actual value (axis) 0 with EP; ramps to setpoint
r0070 DC link voltage (CU) ~565 V DC on 400 V AC
r0190 Number of drive objects 3 (ALM + 2 axes)
r0945[0..7] Fault code buffer Empty after a clean run
p0922 PROFIdrive telegram selection (axis) 1, 2, 3, 4, 5, 6, 81, 82, 83, 84, 85, or 86
p2030 Field bus interface protocol PROFINET (7 for PROFINET on S120)

Edge Cases and Field-Notes

  • EP from a safety relay: if the cabinet has a safety relay, the 24 V to ALM X21.6 must come from the safety relay, not directly from the 24 V rail. A STO trip on the safety relay will drop EP, which the Startdrive control panel reports as the same "Switching on inhibited" state — but the cause is the safety chain, not the drive.
  • Double Motor Module section order: on the 6SL3120-2TE13-0AD0, the first DRIVE-CLiQ port (X200) is the section physically closer to the X200 of the ALM side. If the motor does not move but the second one does, the axes have been mapped in the wrong order. Swap the axis objects in the project, or remap the DRIVE-CLiQ cables, depending on your preferred discipline.
  • Power-module firmware: the ALM 6SL3130-7TE21-6AA4 was released with both V4 and V5 firmware. The CU320-2 PN 6SL3040-1MA01-0AA0 ships with V5.x; pairing a V4 ALM with a V5 CU can cause F0135 topology faults. The compatibility matrix is in the S120 Commissioning Manual, not Startdrive.
  • Control priority release: if you close Startdrive without clicking "Give up control priority", the drive stays in the control-priority-held state until the next stop/restore. The PLC will see "Drive controlled by higher-level controller" as long as the flag is held.
  • First motion without PLC: when the user is doing a first test without a SIMATIC program running, the control panel is the only legal way to command the drive. Do not try to drive it through PROFINET by toggling bits in TIA Portal watch tables — the control-panel handshake is required for the first power-up to take ownership.

FAQ

Why does the S120 say "Switching on inhibited - connect 24V to terminal EP" even when 24 V is wired to X21?

The EP input is the dedicated "Enable Pulses" line on the ALM, not the general 24 V supply. On the 6SL3130-7TE21-6AA4 it is X21.6, with M on X21.9. If 24 V is present on X21.1 / X21.2 (the AIM enable lines) but not on the EP pin, the warning persists. Verify the EP signal on the Startdrive diagnostics screen (Line Module, DI 0–7) and check that M is common with the 24 V return.

What is the minimum wiring between the Active Interface Module 6SL3100-0BE21-6AB0 and the ALM 6SL3130-7TE21-6AA4?

Three wires are the minimum: AIM X21.1 (RDY1) to ALM X21.1, AIM X21.2 (RDY2) to ALM X21.2, and AIM X21.3 (M) to ALM X21.3. Missing any of these three prevents the ALM from closing and produces F07840 in the diagnostics buffer.

Which PROFINET telegram should I assign to the ALM?

Use SIEMENS telegram 370 (PZD-16/16) for the Active Line Module. It carries the line-module control word, status word, and the active and reactive current setpoints / actuals. Telegram 371 is the lower-cost alternative (PZD-6/6) for installations that do not need the full diagnostics payload.

Do I have to be online with the PLC to move the motor from the Startdrive control panel?

No. The Startdrive control panel can command the drive directly over PROFINET as long as the S120 has a valid configuration loaded and EP / AIM enable are present. The PLC does not have to be in RUN, but it must not be holding control priority. Click "Assume control priority" in the control panel, and click "Give up control priority" before you return the drive to the PLC.

Why does the motor hold torque when I press Stop on the control panel, and how do I cut the DC bus?

The control-panel Stop performs OFF1 (controlled ramp-down while the drive stays enabled). To remove the DC bus, drop EP at the ALM X21 terminal, or use the Startdrive command "Disable line module". After OFF1, the drive reports "Operation enabled" until EP is removed — that is normal S120 behavior.

Back to blog