Problem Details
The Siemens SIMATIC TP1200 Comfort Panel fails to complete project transfer from TIA Portal V13 SP1 over Ethernet/PN-IE. The engineering station (PG/PC) reports "Loading configuration - This will take some time" indefinitely, while the panel hangs in the transfer state showing "Connecting to host..." with no progress indicator, no error popup, and no completion acknowledgement. Runtime update begins and may halt at the 51% mark, the project is never written, and cancelling the load from the engineering software results in TIA Portal becoming unresponsive (not responding in Windows Task Manager).
Affected configuration in the original incident:
| Item | Value |
|---|---|
| Panel model | SIMATIC HMI TP1200 Comfort (6AV2 124-1MC01-0AX0 family) |
| Panel image version (new device) | V13.0.0.5 |
| Project HMI version | V13.0.0.0 (compiled) |
| Available TIA V13 SP1 HMI version | V13.0.1.0 |
| Engineering software | TIA Portal V13 SP1 (without later HSP/Updates applied) |
| Transfer medium attempted | Ethernet (TCP/IP) and PROFINET (PN/IE) |
| Resulting error code (when forced) | 0x8020AB0018F0FFF4 |
Root Cause Analysis
The TP1200 transfer pipeline in TIA Portal V13 SP1 consists of three sequential operations performed by the loader:
- OS image compatibility check between the compiled project target version and the panel's current image.
- Runtime (WinCC RT) update to the matching image version.
- Project/configuration download via the active transfer channel.
When TIA Portal V13 SP1 is installed without its cumulative HSP (Hardware Support Package) updates, the internal transfer engine carries a known defect in the configuration-download phase: the runtime updates cleanly, but the subsequent project block-stream stalls because the loader's transfer-stack buffer size, retry policy, and TLS/PN-IO handshake are out-of-sync with the panel's V13.0.0.5 firmware. The PC side then waits indefinitely for an acknowledgement that the panel never issues, producing the "Loading configuration this may take some time" indefinite state and - when a watchdog aborts - the 64-bit cancel code 0x8020AB0018F0FFF4.
| Code | Meaning | Likely cause |
|---|---|---|
| 0x8020AB0018F0FFF4 | Loader-side abort during project block transfer | Buffer/handshake mismatch between PC and panel firmware |
| (no error, indefinite hang) | Configuration load deadlock | Missing TIA V13 SP1 Update (HSP) on the engineering station |
| "Please boot the HMI" | OS update requires panel reboot that PG cannot detect | Factory Reset selected in ProSave while panel is in normal mode |
Secondary failure modes observed in the same environment:
- Factory Reset via ProSave + OS Update causes the panel to enter recovery state; the engineering station cannot detect the boot request because the network bring-up timing changed.
-
PN/IE device scan fails with the panel invisible, despite correct IP addressing (HMI
192.168.0.20/24, PG192.168.0.15/24) - root cause is the same defective transfer stack, not addressing. - Backing up / restoring with ProSave works because ProSave uses its own direct channel and is not affected by the TIA Portal transfer-engine defect.
Affected Versions and Products
| Component | Affected / Tested Versions |
|---|---|
| TIA Portal | V13 SP1 without Update 9 (or later cumulative updates) |
| TIA Portal Update | HSP/Update 9 (and later) for V13 SP1 - resolves the issue |
| TP1200 Comfort image | V13.0.0.0 / V13.0.0.5 / V13.0.1.0 (all three affected when PG side is unpatched) |
| ProSave version | V13 SP1 (bundled) - works for backup/restore and standalone OS update |
| Supported OS | Windows 7 SP1 (32/64-bit), Windows Server 2008 R2 SP1 |
Pre-Flight Verification
Before changing any panel or project settings, capture the baseline state. This data is required if a Siemens support ticket is opened.
- Open Control Panel → Transfer Settings on the TP1200 and note the active transfer channel (PN/IE or Ethernet) and the configured IP address.
- From the PG, open a command prompt and run
ping 192.168.0.20 -tto verify L3 reachability. The panel must reply consistently. - Run
arp -aand confirm the panel's MAC address matches the label on the rear of the device (in the original incident:28:63:36:21:8A:9B). - Open TIA Portal → Help → Installed Software and record the exact build number, including any Update (HSP) numbers. Compare against the TIA Portal V13 SP1 update matrix.
- Open ProSave and create a full backup of the panel before any recovery attempt. This file is essential if a rollback is needed.
Solution: Apply the Missing TIA V13 SP1 Update
The confirmed resolution for the indefinite configuration-load hang and the 0x8020AB0018F0FFF4 error is to bring the engineering software to the latest available TIA Portal V13 SP1 cumulative update. In the field incident, installing Update 9 for TIA Portal V13 SP1 allowed the project to transfer on the first attempt.
Step-by-Step Procedure
- Close TIA Portal completely. Confirm in Task Manager that
S7TGTOPX.exeand any TIA background services are stopped. - Download the latest TIA Portal V13 SP1 Update from the Siemens Industry Online Support portal. The download requires a Siemens Support account; search for TIA Portal V13 SP1 Update 9 (or the latest available for V13 SP1).
- Extract the package to a local folder. Right-click the autorun / setup and choose Run as administrator.
- Accept the license terms and select the Update option. Do not perform a clean reinstall unless explicitly required.
- Reboot the engineering station when prompted. The installer requires a restart to replace locked system files used by the transfer engine.
- Re-open TIA Portal V13 SP1. From the project tree, right-click the HMI device and select Compile → Software (rebuild all) to ensure the compiled image is consistent with the updated toolchain.
Solution: Correct Transfer Channel and IP Configuration
The transfer-channel and address settings shown in the original incident are correct for TP1200 Comfort panels, but they must be applied on both sides identically.
| Location | Setting | Value |
|---|---|---|
| TP1200 Control Panel → Transfer | Channel | PN/IE (recommended) or Ethernet (TCP/IP) |
| TP1200 Control Panel → PN/IE → Properties | IP address | 192.168.0.20 |
| TP1200 Control Panel → PN/IE → Properties | Subnet mask | 255.255.255.0 |
| TIA Portal → Online → Accessible nodes | PG/PC interface | Intel 82579LM Gigabit → TCPIP.1 |
| TIA Portal → Set PG/PC interface | Access point | S7ONLINE (default) over TCPIP.1 |
| Windows network adapter IPv4 | IP address |
192.168.0.15 / 255.255.255.0
|
| Windows network adapter IPv4 | Disable | IPv6, proxy, firewall exceptions for S7TGTOPX.exe
|
Solution: OS Update / Factory Reset via ProSave
Use ProSave when the panel needs an OS image change or a factory reset and TIA Portal cannot establish a usable transfer. ProSave uses a dedicated transfer path and is not affected by the TIA transfer-engine defect.
- Launch ProSave on the engineering station. Select the correct Ethernet or PN/IE interface and enter the panel IP
192.168.0.20. - Open the OS Update tab. Browse to the HMI image file matching the project version (for V13 SP1 projects:
SIMATIC_TP1200_Comfort_V13.0.1.0.imgor the closest available). - For an in-place image update, leave Factory Reset unchecked. Click Execute Update and wait for ProSave to report success.
- For a true factory reset, check Perform Factory Reset. ProSave will prompt "Please boot the HMI". Reboot the panel manually from the rear power switch (do not use the soft reboot) within the time window. ProSave will then push the image and reset internal storage.
- After the OS update or factory reset completes, leave the panel in transfer mode and return to TIA Portal to load the project.
Loading the Project After the Update
- Confirm the panel is in transfer mode (Start button dimmed, Transfer softkey off).
- In TIA Portal, right-click the TP1200 device in the project tree and choose Download to device → Software (only).
- In the load preview, accept Overwrite if object exists online.
- If the runtime version differs, accept Install HMI Runtime.
- Click Load. With the patched TIA Portal V13 SP1, the configuration download completes in a single pass and the panel automatically restarts Runtime.
Verification
After the project is loaded, run the following checks to confirm the fix is stable:
- Runtime started: The panel's Start button becomes active and the configured start screen displays within 30 seconds of transfer completion.
-
No transfer error: TIA Portal's load dialog shows a green Successful status; the Output window shows no
0x8020AB...codes. -
Communication test: Open Online → Accessible nodes in TIA Portal and confirm the TP1200 appears with its configured IP
192.168.0.20and MAC28:63:36:21:8A:9B. - PLC handshake: If the TP1200 is connected to an S7-1500/1200 PLC, open an HMI tag in the watch table and confirm value updates in both directions.
- Rebuild from clean: Power-cycle the panel, verify the project auto-starts, and confirm no "There is no project" message appears.
Troubleshooting Matrix
| Symptom | Likely Cause | Action |
|---|---|---|
| PG shows "Loading configuration" indefinitely | Missing TIA V13 SP1 Update | Install Update 9 (or latest) for TIA V13 SP1 and retry |
| Runtime abort at 51% with error 0x8020AB0018F0FFF4 | Loader / panel image mismatch on PG side | Apply TIA update; if persistent, perform OS update via ProSave |
| Panel reports "Please boot the HMI" indefinitely | ProSave factory-reset wait window expired | Cancel, power-cycle the panel, re-launch ProSave |
| Panel not visible in PG/PC accessible nodes | Wrong PG/PC interface selected | Set PG/PC interface to Intel 82579LM → TCPIP.1 (S7ONLINE access point) |
| TIA Portal becomes Not Responding on cancel | Loader thread deadlock | Wait 60-120 s for cleanup; do not force-kill S7TGTOPX |
| Transfer OK but project not visible after reboot | Image update succeeded but project not loaded | Re-transfer via TIA Portal; do not skip Runtime step |
| ProSave backup/restore works, TIA transfer does not | Defect in TIA transfer engine only | Apply TIA V13 SP1 Update |
Best Practices and Preventive Recommendations
- Patch discipline: Apply every cumulative TIA Portal update (HSP) to the engineering station as soon as it is released. Most transfer-engine defects are resolved by these updates.
- Version alignment: Compile the project to the same HMI image version installed on the panel. If a panel ships with a newer image than the project target, perform the OS update through ProSave first, then load the project.
- Backup before any recovery: Always run a ProSave full backup of the panel before an OS update or factory reset.
- Stable transfer channel: Prefer a direct point-to-point Ethernet cable between PG and TP1200 during commissioning; switches and VLANs add variables that are difficult to isolate later.
- Disable Runtime before transfer: The panel's Start button must be dimmed; an active Runtime will silently reject the new project download.
- Capture MAC and image version in the project documentation; this is the first data Siemens support will request.
What does TIA Portal error 8020AB0018F0FFF4 mean on a TP1200?
It is a 64-bit loader abort emitted when the PC-side transfer engine cannot complete the project block transfer to the panel. On TP1200 Comfort panels running TIA Portal V13 SP1, it is caused by a defect in the unpatched transfer engine and is resolved by installing TIA V13 SP1 Update 9 or later.
Why does my TP1200 hang at "Connecting to host" while TIA Portal says "Loading configuration this may take some time"?
The runtime has updated, but the configuration download cannot complete due to a handshake or buffer mismatch in the unpatched TIA V13 SP1 transfer engine. Installing the latest TIA V13 SP1 Update (Update 9 or later) fixes the deadlock and the project loads on the first attempt.
Can I update the TP1200 OS image from V13.0.0.5 to V13.0.1.0 over Ethernet?
Yes. Use ProSave (bundled with TIA V13 SP1) on the PG, point it to the TP1200's IP (e.g. 192.168.0.20), open the OS Update tab, and select the matching .img file. If you also want a factory reset, check the box and reboot the panel manually when ProSave prompts.
ProSave backup and restore works, but TIA Portal transfer fails. Why?
ProSave uses a dedicated direct transfer path that is independent of the TIA Portal transfer engine. The defect that causes the indefinite configuration load is in the TIA transfer engine only and is fixed by installing the missing TIA V13 SP1 Update.
After loading, my TP1200 boots and says "There is no project, please transfer the project". What now?
The OS image is present but the project was not written before the panel rebooted. Re-enter transfer mode (Start button must be dimmed), then re-run Download to device → Software (only) from TIA Portal. Confirm the load completes successfully and that you did not cancel the operation during the configuration phase.