A PLC110[M02] socket client can establish TCP communication and still fail to exchange useful data if it does not construct the required Modbus request. The available evidence also identifies two implementation risks: repeatedly creating sockets causes the 32-bit hClientSocket value to increase, and uncontrolled read/write calls may delay or interfere with each other.
Separate TCP Transport from Modbus Messaging
SysLibSocket provides the transport connection; it does not create the application-layer Modbus request. After opening the TCP connection, construct the request expected by the server, transmit it, receive the response, and validate that response before starting another transaction.
| Item | Evidence | Engineering decision |
|---|---|---|
| PLC family | PLC110[M02], PLC160 M02, and PLC1xx are referenced | Use an example intended for the actual runtime; portability between targets is not established. |
| Socket library | SysLibSocket |
Add Modbus message construction above the socket layer. |
| Reported server settings | MK302 at 10.0.6.20, TCP port 502, Modbus address 1
|
Apply these values only to that reported installation; verify the configured device identity before connecting. |
| Simulator/runtime | PLCWinNT V2.4.7.42 is mentioned |
Socket compatibility is unresolved by the evidence. |
Control the Socket Handle Lifecycle
The reported hClientSocket value increased when the program repeatedly created connections. A later revision stopped continuously cycling through handles. The evidence states that a closed-handle counter can wrap through its numeric range, but it gives neither the simultaneous-socket limit nor manufacturer-confirmed rollover behavior. Do not use the numeric handle value as a connection-health indicator.
Keep one handle associated with each active connection, reuse it while the connection remains valid, and close it once when leaving the connected state. Recreate the socket only after the prior handle has been closed or declared unusable. Verify resource control by confirming that a stable connection no longer produces a new handle every PLC cycle.
Serialize Reads, Writes, and Multiple Devices
Use a transaction sequence so a write and read do not operate on the same socket concurrently. The evidence reports perceived read/write slowing but provides no measurements, timeout values, or confirmed root cause; measure transaction completion before attributing the delay to socket scheduling.
- Open or retain the socket assigned to the target device.
- Construct the required Modbus request and send it only when no earlier transaction is pending.
- Wait for and validate the corresponding response before enabling the next read or write.
- For multiple modules, maintain separate connection state and handle storage for each target so one device cannot overwrite another device's transaction state.
- On a communication failure, close that device's socket before creating its replacement.
For the reported MK302 case, an intermittently flashing Eth1 indicator accompanied by an alarm LED flashing in the opposite phase proves only that Ethernet activity occurred; the evidence does not define those LED states or establish successful Modbus communication. Verify success from a valid application-layer response rather than LED activity alone.
FAQ
Why does hClientSocket keep increasing on PLC110[M02]?
The program is likely creating replacement sockets repeatedly. Retain the active handle, close it once when the connection fails or exits, and verify that normal PLC scans do not allocate new handles.
It can provide the TCP transport described in the evidence, but the PLC program must also construct and process the required Modbus messages. A successful TCP connection alone does not confirm application-layer communication.
What connection settings were reported for the MK302?
The reported installation used IP address 10.0.6.20, TCP port 502, and Modbus address 1. Confirm that the connected device is the same model and configuration before applying those values.