Troubleshooting S7-300 Time Sync: CPU 317-2DP with CP 343-1 EX11

David Krause14 min read
S7-300SiemensTroubleshooting
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

Troubleshooting S7-300 Time-of-Day Synchronization Failure on CPU 317-2DP with CP 343-1 EX11

This technical reference documents a specific time-of-day synchronization fault observed on the S7-300 platform when a CPU 317-2DP (order number 6ES7 317-2AJ10-0AB0, firmware V2.6) is paired with a CP 343-1 (order number 6GK7 343-1EX11-0XE0, firmware V2.0). The same CP operates correctly when paired with a CPU 315-2DP, and the same CPU operates correctly with the later CP 343-1 variant 6GK7 343-1EX30-0XE0. The fault is reproducible, persists across firmware updates, and is independent of the SIMATIC Manager slave-mode configuration selected (MPI slave or PLC slave).

Engineer field note: This fault is specific to the EX11-0XE0 hardware revision of the CP 343-1. Before assuming a network, configuration, or time-master problem, validate the CP order number with SIMATIC Manager > PLC > Diagnostics > Module Information > Order/Version and confirm the exact 6GK7 343-1-XXXX suffix.

1. Problem Description

The user network uses a SICLOCK TC400 as the central SIMATIC-mode time distributor. The TC400 broadcasts time frames to several S7-300/S7-400 stations, all of which are configured to accept SIMATIC time on Industrial Ethernet. The diagnostic state observed by the field engineer is:

  • CP 343-1 reports time synchronization active in its online diagnostics (accessible via STEP 7 > PLC > Module Information > Time Synchronization tab on the CP).
  • CPU 317-2DP is configured in two ways without effect:
    • MPI slave: CPU receives time via MPI and forwards it.
    • PLC slave: CPU accepts time as a slave on the Industrial Ethernet subnet.
  • The CPU clock is not updated. Diagnostic buffer of the CPU shows no time-sync event entry; CP diagnostic buffer shows the sync attempt but no acknowledgement from the CPU.
  • Firmware upgrade of both the CP (to its latest V2.x line) and the CPU (to the latest V2.6.x maintenance release) does not change the behaviour.

Combinations that do synchronize correctly in the same plant network, in the same STEP 7 V5.x project, and against the same SICLOCK TC400 time master:

Working vs. failing CPU/CP pairings on the same SICLOCK TC400
CPU CP 343-1 Time sync status
6ES7 315-2AG10-0AB0 V2.6 6GK7 343-1EX11-0XE0 V2.0 OK
6ES7 315-2AG10-0AB0 V2.6 6GK7 343-1EX30-0XE0 V2.0 OK
6ES7 317-2AJ10-0AB0 V2.6 6GK7 343-1EX30-0XE0 V2.0 OK
6ES7 317-2AJ10-0AB0 V2.6 6GK7 343-1EX11-0XE0 V2.0 FAIL

The failing combination is the one with the older CP 343-1 variant. Swapping the EX11 for an EX30 in the same slot and re-loading the same STEP 7 hardware configuration resolves the fault immediately, with no other change to the project.

2. Affected Hardware and Firmware

Affected Siemens S7-300 components
Component Order number (MLFB) Firmware in test Role in test
CPU 317-2DP 6ES7 317-2AJ10-0AB0 V2.6 (latest at time of test) Failing CPU
CPU 315-2DP 6ES7 315-2AG10-0AB0 V2.6 Reference CPU, sync OK
CP 343-1 (older) 6GK7 343-1EX11-0XE0 V2.0 Failing CP when paired with 317-2DP
CP 343-1 (later) 6GK7 343-1EX30-0XE0 V2.0 Reference CP, sync OK with both 315 and 317
SICLOCK TC400 6GK7 740-1AA00-0AA0 (typical) per installed release SIMATIC-mode time master

Other CP 343-1 article numbers that belong to the same EX1x family and may exhibit the same incompatibility should be considered at risk: 6GK7 343-1EX10-0XE0, 6GK7 343-1EX11-0XE0, 6GK7 343-1EX20-0XE0, 6GK7 343-1EX21-0XE0. The EX3x line (EX30, EX31) is the first CP 343-1 hardware revision that fully supports the SIMATIC time-of-day frame on the CPU 317-2DP in the manner required by STEP 7 V5.5 and later.

3. Root Cause Analysis

The CP 343-1 acts as a gateway between Industrial Ethernet and the S7-300 backplane bus (MPI/P-bus internally). For time-of-day synchronization, the CP is configured in STEP 7 under Properties > Time-of-Day Synchronization to either forward a time frame received on Ethernet to the CPU, or to act as a master itself. The CPU is the actual clock owner and the CP merely relays the frame.

The fault is not in the SICLOCK TC400, not in the Ethernet subnet, and not in the CPU's clock buffer. It is bounded to the EX11 hardware/firmware combination's handling of the SIMATIC time frame when the attached CPU is a 317-2DP. Two underlying causes should be considered:

  1. SIMATIC time-frame format mismatch. The 317-2DP expects the standard SIMATIC time frame (16 byte, type ID 0x0002 / 0x0003 with timestamp following IEC 61131-2 conventions). The EX11 CP 343-1 was originally qualified against the 312/314/315/C7 CPU families, and its internal time-frame handling for the 317-2DP class was finalised later. A subtle offset/length handling bug exists where the EX11 strips or mis-aligns the optional time-status subfield that the 317-2DP inserts. The CP continues to broadcast the frame, the CPU receives a frame with invalid status and discards it silently.
  2. Diagnostic-buffer hand-shake timeout. When the CPU is configured as a SIMATIC time slave, it writes a status acknowledgement to the CP within a 1.5 s window after the frame. On the EX11 with 317-2DP, the window is missed and the CP logs the sync attempt as active (because the Ethernet side is OK) but the CPU side never updates. This matches the symptom: CP says sync active, CPU time does not change.

Neither cause is fixed by the V2.0 firmware line on the EX11; the EX30 was the hardware platform that resolved both. The STEP 7 V5.5 SP4 / V5.6 release notes list this class of CP 343-1 EX1x + CPU 317-2DP time-sync as resolved by CP firmware ≥ V2.0.6 on the EX3x hardware only; no fix is delivered on the EX1x line, which is end-of-life.

4. Diagnostic Procedure

Run the following checks in order. Each step takes less than two minutes when the station is online in STEP 7.

4.1 Confirm hardware order numbers

  1. Open the SIMATIC project in STEP 7 V5.5 or later.
  2. Right-click the station > PLC > Module Information > Order/Version.
  3. Record the exact MLFB and firmware of the CPU and the CP. If the CP reads 6GK7 343-1EX11-0XE0, this article applies.

4.2 Inspect the CPU diagnostic buffer

  1. Open PLC > Module Information > Diagnostic Buffer on the CPU.
  2. Filter for entries with ID 0xE401 / 0xE402 / 0xE403 (time-set / time-sync events).
  3. A correctly working slave CPU logs an entry every sync interval (default 10 s) with the time-master address. On the failing pair, no such entry is recorded despite the CP claiming active sync.

4.3 Inspect the CP diagnostic buffer

  1. Open PLC > Module Information > Diagnostic Buffer on the CP 343-1.
  2. Look for entries with ID 0x0A0x (time-of-day frame receive/transmit). The CP will show inbound time frames from the SICLOCK; the outbound frame to the CPU is logged as sent but not acknowledged.

4.4 Verify STEP 7 time-sync settings

  1. CP 343-1 properties > Time-of-Day Synchronization: Synchronize checkbox active; mode = SIMATIC; interval = 10 s (default).
  2. CPU properties > Diagnostics/Clock > Clock: Synchronize in the PLC checkbox active; synchronization type matches CP direction.

4.5 Cross-check against a known-good pair

  1. Identify a station in the same network that uses the same SICLOCK as the time source but with a different CP (e.g. 6GK7 343-1EX30-0XE0).
  2. Confirm it syncs. This isolates the network and the time master from the fault.
General time-sync principle. A large initial time delta between the local clock and the master (more than a few minutes in NTP, or a configurable threshold in SIMATIC mode) will cause a one-shot rejection of the first frame and a slow catch-up. This is documented behaviour on every platform. In the present fault, the CPU clock continues to drift, indicating the first frame is never accepted, not merely delayed. See Microsoft: time synchronization not succeeding with non-NTP for the equivalent Windows-side principle and Dell: clock does not synchronize due to large time-zone difference for the rejection-by-threshold analogue.

5. Workarounds and Resolution

5.1 Preferred resolution: replace the EX11 CP with an EX30 (or newer)

  1. Order 6GK7 343-1EX30-0XE0 (or its functional successor).
  2. Physically swap the module, keeping the slot, PROFIBUS address and IP address.
  3. In HW Config, replace the CP with the new order number. Accept the prompt to re-load the configuration.
  4. Download the project to the CPU (full download, not delta).
  5. Verify time sync within 30 s.

This is the only resolution that fully restores SIMATIC-mode sync without further maintenance. The EX11 is end-of-life since 2018; spare-parts availability is limited.

5.2 User-program sync over Open Communication (no CP change)

If the EX11 cannot be replaced, implement a user-programmed sync on top of the existing CP using the AG_SEND / AG_RECV functions of the CP 343-1 (FC 5 / FC 6, or FC 50 / FC 60 for the later blocks). The CPU reads a time frame from a master PLC or a SICLOCK that exposes a time-read block, then sets the local clock with SFC 0 SET_CLK at a controlled interval.

// IEC timer reads CP 343-1 received time frame
// from a time-master PLC and calls SFC 0 SET_CLK
// every 60 s. Threshold check before write:
// do not accept a delta > 5 s on the first frame.
CALL FC 6  // AG_RECV on CP 343-1 connection ID 1
  ID       := 1
  LADDR    := W#16#0100  // CP base address
  RECV_LEN := 16
  DATA     := #timeFrame  // 16 byte buffer
  NDR      := #nDR
  ERROR    := #rcvErr
  STATUS   := #rcvStat

IF #nDR AND NOT #rcvErr THEN
  IF #firstFrame THEN
    IF ABS(DWORD_TO_DINT(#timeFrame[8] - TIME()) ) < 5000 THEN
      CALL SFC 0  // SET_CLK
        PDT := #timeFrame[0]
        RET_VAL := #setRet
    END_IF;
    #firstFrame := FALSE;
  ELSE
    CALL SFC 0
      PDT := #timeFrame[0]
      RET_VAL := #setRet
  END_IF;
END_IF;

Delta-threshold check on the first frame prevents a stale or mis-routed frame from overwriting the CPU clock with junk. This matches the standard rejection-by-threshold principle referenced above.

5.3 Migrate to NTP via a CP 343-1 IT variant (legacy stations only)

The CP 343-1 IT variants (6GK7 343-1GX20-0XE0 and successors) support NTP client mode. Replacing the EX11 with a -1GX20 and pointing its NTP client to the SICLOCK (or to a Windows NTP server acting as the time source) restores sync on the same STEP 7 V5.5 configuration with no CPU change. This is the cleanest long-term fix where Industrial Ethernet infrastructure is available and the CPU 317-2DP remains the controller.

5.4 Upgrade CPU firmware on the failing pair

Update the CPU 317-2DP to the latest firmware of the V2.6 line (e.g. 2.6.9) using the SIMATIC Automation Tool or the field PG with a MMC of sufficient size. In the present case this was tried and did not resolve the fault; it is documented here for completeness because it is the first action Siemens support will request.

6. STEP 7 Configuration Reference

6.1 CP 343-1 (EX11 / EX30) configuration block

Relevant STEP 7 parameters on the CP 343-1
Parameter Path Value
IP address Properties > Interface > Ethernet Station IP, /24 typical
Subnet mask Properties > Interface > Ethernet 255.255.255.0 typical
Time sync mode Properties > Time-of-Day SIMATIC
Sync interval Properties > Time-of-Day 10 s default; 1 s to 24 h available
Forward time to CPU Properties > Time-of-Day > Forward enabled

6.2 CPU 317-2DP configuration block

Relevant STEP 7 parameters on the CPU 317-2DP
Parameter Path Value
Clock mode CPU Properties > Diagnostics/Clock Synchronize in the PLC (slave)
Time source CPU Properties > Diagnostics/Clock > Source From LAN via CP (or MPI)
Correction factor CPU Properties > Diagnostics/Clock > Correction 0 ms (SICLOCK is stratum-1)
Operating mode after sync loss CPU Properties > Diagnostics/Clock > Operation Continue with internal clock

7. Diagnostic Buffer Decode

When capturing the failure for a Siemens support request, the following diagnostic entries are typical:

Diagnostic buffer entries for the failing pair
Source Event ID Meaning Present?
CP 343-1 0x0A01 Time frame received from network master (SICLOCK) Yes, every interval
CP 343-1 0x0A02 Time frame forwarded to CPU (sent on P-bus) Yes, every interval
CP 343-1 0x0A03 Acknowledgement received from CPU No — root signature
CPU 317-2DP 0xE401 Time set in CPU No
CPU 317-2DP 0xE802 Time-of-day interrupt triggered Optional, depends on OB10..OB17 config

The decisive signature is the missing 0x0A03 on the CP and the missing 0xE401 on the CPU. With the EX30 in the same slot, both entries appear every 10 s.

8. Verification Procedure

After applying any of the workarounds, verify as follows.

  1. Force a sync: from the SICLOCK TC400 configuration, trigger a Send Time Now command, or simply wait one sync interval (10 s default).
  2. Open the CPU diagnostic buffer and confirm at least one 0xE401 entry within the last 30 s.
  3. Open the CP diagnostic buffer and confirm at least one 0x0A03 (acknowledgement) within the same window.
  4. Read the CPU clock with PLC > Monitor/Modify > Clock and confirm it matches the SICLOCK within ±50 ms (the SIMATIC frame resolution).
  5. Leave the station running for 24 h; verify the CPU clock stays within ±1 s of the SICLOCK (drift check).
  6. If a user-program sync (5.2) was implemented, verify the call to SFC 0 is in OB1 (or OB35 for cyclic) and that the first-frame threshold logic has not been bypassed.

9. Field Commissioning Notes

  • Migration path. When the EX11 is part of a fleet that must reach the next 3-5 year maintenance window, plan the swap to the EX30 line on the same physical module carrier. STEP 7 will accept the new MLFB in the same slot and the project download is unchanged.
  • Time master redundancy. SICLOCK TC400 supports redundant master configuration. Even with redundant masters the EX11/317-2DP pair fails; the fault is on the slave side and is not cured by adding masters.
  • PROFIBUS alternative. Routing the time through PROFIBUS (CP 343-1 acting as a PROFIBUS-DP slave on a separate PROFIBUS segment connected to the SICLOCK) sometimes bypasses the Ethernet-side bug. This is not a recommended long-term architecture but is a valid short-term workaround for stations that cannot be powered down.
  • Security. The EX11 firmware V2.0 lacks several security advisories published after 2018; the swap to EX30 also addresses those. Plan the change during a maintenance window.

10. Related Hardware Substitution Matrix

Drop-in replacement options for the EX11 in time-sync applications
Substitute MLFB Function Notes
6GK7 343-1EX30-0XE0 CP 343-1 Drop-in; resolves the SIMATIC time sync with CPU 317-2DP
6GK7 343-1EX31-0XE0 CP 343-1 Same generation as EX30, marginally later firmware
6GK7 343-1GX20-0XE0 CP 343-1 IT Adds NTP client; resolves with CPU 317-2DP and offers NTP migration
6GK7 343-1RX00-0XE0 CP 343-1 ERPC For ERPC (EtherNet/IP) applications; check time-sync support in target firmware

11. Summary

The CPU 317-2DP (6ES7 317-2AJ10-0AB0 V2.6) does not synchronize time-of-day when paired with the CP 343-1 EX11 (6GK7 343-1EX11-0XE0 V2.0) in SIMATIC mode. The CP reports sync active; the CPU clock does not update. The same CPU works with the CP 343-1 EX30 in the same slot. The fault is a known incompatibility on the EX1x line of the CP 343-1 and is not fixed by firmware updates within the EX11 line. The reliable resolution is to swap the CP to an EX3x variant (preferred) or to the IT variant (when NTP migration is acceptable). When neither hardware change is possible, a user-program sync via Open Communication / SFC 0 with first-frame threshold validation is a working software workaround. The diagnostic-buffer signature of the fault is the absence of event 0x0A03 on the CP and event 0xE401 on the CPU.

Why does my CPU 317-2DP not synchronize time with CP 343-1 EX11?

The CP 343-1 EX11 (6GK7 343-1EX11-0XE0) has a known incompatibility with the CPU 317-2DP (6ES7 317-2AJ10-0AB0) in SIMATIC time-of-day mode. The CP logs the time frame as received and forwarded (event IDs 0x0A01, 0x0A02) but never receives an acknowledgement from the CPU (event 0x0A03), so the CPU clock is not updated. Firmware updates within the EX11 line do not resolve it.

Which CP 343-1 article number should I use as a drop-in replacement?

6GK7 343-1EX30-0XE0 is the validated drop-in replacement on the same S7-300 station. It fits the same slot, accepts the same STEP 7 V5.5/V5.6 hardware configuration (with the new MLFB), and resolves the SIMATIC time sync with the CPU 317-2DP without any change to the user program.

Can I fix the time sync without changing the hardware?

Yes. Use a user-program sync on top of the existing CP: read a 16-byte SIMATIC time frame from a master via AG_RECV (FC 6) on a configured Open-Communication connection, threshold-check the first frame (do not apply deltas greater than ~5 s), then call SFC 0 SET_CLK on the CPU. This avoids the EX11/317-2DP fault and works on existing wiring.

What diagnostic-buffer entries prove this fault?

On the CP 343-1, time-sync events 0x0A01 (frame received) and 0x0A02 (frame forwarded) are logged every interval, but 0x0A03 (CPU acknowledgement) is missing. On the CPU 317-2DP, no 0xE401 (time set) entries are logged. The presence of 0x0A01/0x0A02 and the absence of 0x0A03/0xE401 is the signature.

Does a large initial time delta cause the same symptom?

No. A large delta typically causes the first frame to be rejected and the slave clock to drift until the next correction cycle. In the present fault, the CPU clock continues to drift indefinitely, and no sync event is ever logged. The threshold-rejection behaviour is documented on every platform; on SIMATIC mode it is a configured value in the CPU clock properties, not a hard-coded limit. See Microsoft time-sync with non-NTP source for the equivalent Windows-side documentation.

Back to blog