WinCC 7.x Server/Client Setup, User Administration, and Migration Guide
Siemens WinCC 7.x supports two distinct distributed HMI/SCADA architectures: the Multi-Client (a client that operates a downloaded server package and runs its own local project) and the Uni-Client (a thin client that connects to the server project without holding any local project). Selecting, identifying, and commissioning the correct topology is the foundation for any upgrade from WinCC 7.0 to WinCC 7.4 Update 1 or later, and it dictates whether the migration must touch one project or two. This reference walks through architecture selection, user-administration prerequisites (the equal-account rule), SIMATIC Shell Interconnect wiring, server-package generation, and field-verified remediation of the most common credential failures.
1. WinCC 7.x Distributed Architecture Overview
WinCC V7 is structured around a Server holding the master project (graphics, tags, archives, alarms, scripts, user administration) and one or more Clients that visualize runtime data. The WinCC Explorer on the server is the engineering entry point; clients either point at the server through a configured network share or download a copy of the server's runtime data and operate it locally.
The official configuration reference is the Siemens manual 109771695 - Client/Server Systems - Configuration WinCC V7.5. Although titled for V7.5, the architecture, dialogs, and naming conventions are unchanged from V7.0 through V7.4 SPx. The same document family covers WinCC V7.4 in entry 109772015 and the upgrade-path documentation in entry 89378679 - WinCC V7.4 Installation/Release Notes.
2. Multi-Client vs. Uni-Client: Identifying Your Topology
The single most important decision point before any upgrade or reconfiguration is identifying which client topology is currently deployed. Use the matrix below.
| Attribute | Multi-Client (Type 1) | Uni-Client (Type 2) |
|---|---|---|
| Local WinCC project on client PC | Yes (.mcp file present in client project folder) | No (client PC has no project; only WinCC RT shell) |
| Client added as "Client Computer" inside Server project | No | Yes (Computer node in WinCC Explorer) |
| Project data delivery | Server package exported from server, imported into local client project | Live, on-demand read of server share at startup |
| Migration scope | Server project AND client project (both must be migrated) | Server project only |
| Recommended use | Branch offices, redundant visualization, isolated clients with local archives | Operator rooms, control desks, short failover windows |
| Login configuration | User Administrator user with "Remote Configuration" right assigned | User Administrator user with "Remote Configuration" right assigned |
2.1 How to Identify Which Type You Have
- On the client PC, open the WinCC project folder (typically
C:\Program Files (x86)\Siemens\Automation\WinCC\WinCCProjectsor the custom project path). - If a project
*.mcpfile exists and the WinCC Explorer opens it directly on the client, you have a Multi-Client (Type 1). - If no
.mcpfile exists on the client and WinCC RT launches into a server-selection dialog, you have a Uni-Client (Type 2). - Confirm by opening WinCC Explorer on the server: under Computer, if the client PC hostname is listed as a child node with "Standard Server" or "Preferred Server" reference, you are running Type 2.
3. WinCC 7.0 to 7.4 Update 1 Migration Path
The upgrade from V7.0 to V7.4 SP1 is an in-place major upgrade and must be performed on the server first. Each project must be opened and saved with the new version so that tag, archive, and script definitions are normalized to the V7.4 schema.
3.1 Supported Upgrade Matrix
| Source | Target | Direct? | Required Step |
|---|---|---|---|
| WinCC V7.0 | WinCC V7.4 SP1 | Yes | Project migration on server (and on Multi-Client PC) |
| WinCC V7.0 + SPx | WinCC V7.4 SP1 | Yes | Same as above |
| WinCC V7.2 | WinCC V7.4 SP1 | Yes | Project migration only |
| WinCC V7.3 | WinCC V7.4 SP1 | Yes | Project migration only |
| WinCC V7.0 | WinCC V7.5 | Yes (recommended) | Project migration only; uses newer SQL Server |
Reference the release notes WinCC V7.4 - Service Pack & Release Notes for the exact SQL Server / Windows compatibility matrix (V7.4 SP1 supports Windows Server 2012 R2 / 2016 / 2019 and SQL Server 2014 / 2016 / 2017 depending on the patch level).
3.2 Pre-Migration Checklist
- Document the OS version (32 vs 64-bit), the installed WinCC version, and the SP/Update level of both PCs.
- Back up the full project folder, archive database folder, and the WinCC registry branch
HKLM\SOFTWARE\Wow6432Node\Siemens\Automation\WinCC. - Export the User Administrator table via WinCC Explorer -> User Administrator -> File -> Export.
- Verify that both PCs have a common local user with identical name and identical password (see Section 4).
- Ensure the server share hosting the project (default
\\<SERVER>\WinCC_Projects\<ProjectName>) is reachable from the client and that both the share ACL and NTFS ACL grant Read/Write to the shared user.
4. The Equal-Account Rule (User Administration Prerequisite)
WinCC remote activation relies on the SIMATIC Shell mechanism, which in turn relies on the WinCC service running under a domain or local account that can authenticate against the project share. If the accounts differ between server and client, the SIMATIC Shell will prompt for credentials on every operation and will fail Interconnect with a generic WinCC RT error dialog.
4.1 Account Architecture
| PC | Role | Operating System Account | WinCC User Administrator Account | Password |
|---|---|---|---|---|
| PC1 (Server) | WinCC Server | USER1 (local administrator) | Runtime user (e.g. WinCCAdmin) |
Identical on both PCs |
| PC2 (Client) | WinCC Client | USER1 (local administrator) - must match server | Runtime user (same name as server) | Identical on both PCs |
USER1 with no password, or a defined operator password). Mismatched account names or passwords are the cause of the SIMATIC Shell Interconnect failure with a credentials prompt.4.2 Configuring the Runtime User
- Open WinCC Explorer on the server.
- Open User Administrator.
- Create or modify the runtime user. Set the Operating system logon to Yes and configure the same Windows account name and password as the local account on the client PC.
- Assign the right Configure remote (number 1002 in WinCC right bitset) to this user. This right permits the Uni-Client to attach to and run the server project.
- Repeat the same User Administrator configuration on the client if it is a Multi-Client (Type 1); user tables may differ but the OS logon account must match.
5. SIMATIC Shell Interconnect - The Server-Client Link
SIMATIC Shell is the Windows Explorer integration that lets a client PC browse WinCC servers on the network and trigger remote activation/deactivation. It is installed automatically with the WinCC client option and registers a COM object that WinCC Explorer uses for the project picker.
5.1 Configuring Interconnect on the Client
- On the client PC, open Windows Explorer and navigate to
SIMATIC Shellin the folder tree (it appears as a virtual folder under "Network" or as a top-level namespace item). - Double-click
SIMATIC Shell. The right pane lists reachable WinCC servers. - Right-click the target server computer and select Interconnect.
- When prompted, enter the WinCC User Administrator runtime user credentials (NOT the local Windows account unless the user was created with OS logon mode).
- If the credentials are accepted, the server project appears under the server's SIMATIC Shell entry and can be activated from the client.
5.2 Verifying the Interconnect Result
- A successful Interconnect registers the server computer in the client's registry under
HKCU\Software\Siemens\Automation\WinCC\Interconnect(or under HKLM on x64 deployments). - After Interconnect, restarting the WinCC RT on the client should display the server project's start screen automatically (Uni-Client) or load the previously imported package (Multi-Client).
- If the client fails to start the server project after Interconnect, inspect the Windows Event Log (Application channel) for source "CCClient" messages - they contain the underlying error code.
6. Server Package Generation (Multi-Client Only)
A Multi-Client requires a "server package" - a snapshot of the server's compiled graphics, tag database, archive layout, and alarm configuration - to be loaded into the local client project. The package is generated on the server and copied to the client.
6.1 Generation Procedure
- On the server, open WinCC Explorer and load the server project.
- Right-click Server Data -> Create Package (or via menu Tools -> Server Data -> Create Server Package).
- Select the target client computer name from the dropdown.
- Choose the package scope: Complete (full project) or Delta (changes only).
- Click Create. The package is written to
<ProjectPath>\<ServerName>_<ClientName>.pck. - Copy the
.pckfile to the client PC and import it into the local client project via Server Data -> Load Package.
7. Migration Workflow Step-by-Step
- Backup the existing V7.0 project on the server.
- Uninstall WinCC V7.0 on the server. Reboot.
- Install WinCC V7.4 SP1 (or later) including the Server option.
- Open the project in V7.4 SP1. The Project Migrator dialog appears. Follow prompts to migrate tag database, archive database, and scripts.
- Validate the migrated project by activating Runtime locally on the server.
- Generate a fresh server package if any client is a Multi-Client.
- On each Multi-Client PC, uninstall WinCC V7.0 and install V7.4 SP1 client option. Migrate the local client project using the new package.
- On each Uni-Client PC, uninstall WinCC V7.0 client option and install V7.4 SP1 client option. The client project on disk is no longer required; the client will read the migrated server project directly.
- Re-establish SIMATIC Shell Interconnect from each client. Use the WinCC User Administrator runtime user credentials (not the OS account unless OS logon is enabled).
- Activate Runtime on the server, then verify that each client can launch and view live data.
8. Verification Checklist
| Check | Expected Result | Diagnostic if Failed |
|---|---|---|
| Server RT activates locally | Start screen appears within 10-20 s | Inspect WinCC diagnostic files in <ProjectPath>\Diagnostics
|
| Client can browse server in SIMATIC Shell | Server computer appears in right pane | UDP broadcast 50523/50524 blocked by firewall |
| Interconnect prompts for credentials | WinCC RT user (not Windows account) | Mismatched accounts - re-check Section 4 |
| Interconnect completes | Server project visible in shell tree | Event Log -> Application -> source CCClient |
| Multi-Client package import | Imported without version mismatch | Regenerate package from migrated server |
| Tag values visible on client | Process values update every 1 s (configurable) | Check connection list in WinCC Explorer on server |
| Alarm acknowledgments propagate | ACK on client clears alarm on server | Verify "Configure remote" right is granted |
| Archive read on client | Trend graph displays historical values | Archive backup folder share permissions |
9. Troubleshooting Matrix
| Symptom | Likely Root Cause | Resolution |
|---|---|---|
| SIMATIC Shell Interconnect fails with credentials prompt | Local Windows account name or password differs between server and client | Create identical local admin account (e.g. USER1) with same password on both PCs; logout/login |
| Interconnect accepts Windows credentials but fails with WinCC user | WinCC User Administrator runtime user lacks "Configure remote" right | Open User Administrator on server, grant right 1002 to runtime user |
| Server project visible but RT will not start | Project path on server share changed after migration | Update path in SIMATIC Shell entry or recreate Interconnect |
| Client cannot see server in SIMATIC Shell | UDP broadcast blocked by Windows Firewall or VLAN ACL | Allow ports 50523/50524 (and 50525 for redundancy); add inbound rules on server |
| Multi-Client package import fails with version error | Package was generated on V7.0 server but target client is V7.4 | Regenerate package after server migration to V7.4 SP1 |
| Tag values update slowly or not at all on client | Network latency > 200 ms or package out of date | Check ping latency; regenerate and reload package |
| Archives show "no data" on Multi-Client | Archive backup path not shared or NTFS denied | Share archive path; grant runtime user Modify permission |
| Runtime error "Project not found" after migration | Project migrated but path mapping lost | Open project on server, re-save; check WinCCProject.ini paths |
10. Security and Hardening Notes
Leaving local administrator accounts with no password on production WinCC systems is unacceptable in modern OT environments. Siemens recommends the following hardening baseline for any V7.x server/client installation:
- Use domain accounts instead of local accounts so password policy (length, rotation, lockout) is enforced centrally via Active Directory.
- Disable interactive login for the WinCC service account on operator HMI panels.
- Restrict the WinCC project share to the specific service account; remove "Everyone" ACL.
- Enable Windows Firewall on both PCs; explicitly open only the WinCC ports (50523, 50524, 50525, 137/138/139 or 445 for SMB, 1433 for SQL Server if used).
- Encrypt the WinCC SQL archive database with a passphrase stored on a removable media or TPM, following Siemens recommendation in WinCC V7.4 Security Guidelines.
- Apply Microsoft security patches monthly; WinCC V7.4 SP1 is validated against Windows Server 2016 / 2019 cumulative updates through the dates noted in the Siemens compatibility tool.
11. Reference Links and Official Documentation
The following Siemens Knowledge Base and documentation entries are the authoritative sources for the procedures described above:
- Client/Server Systems - Configuration WinCC V7.5 (entry 109771695)
- WinCC V7.4 - Service Pack & Release Notes (entry 109772015)
- WinCC V7.4 Installation/Release Notes (entry 89378679)
- WinCC V7.4 SP1 - Working with WinCC Explorer
- SIMATIC HMI WinCC V7 - Migration
How do I know if I have a Multi-Client or Uni-Client in WinCC 7.x?
Open the WinCC project folder on the client PC. If a *.mcp project file exists and WinCC Explorer opens it locally, you have a Multi-Client (Type 1). If no project file exists on the client and WinCC RT launches into a server-selection dialog, you have a Uni-Client (Type 2). Confirm on the server under WinCC Explorer -> Computer: a listed client node means Type 2.
Why does SIMATIC Shell Interconnect fail with a credentials prompt?
Almost always the local Windows account name or password differs between the server PC and the client PC. WinCC requires a matching user with identical credentials on both machines (commonly USER1). After the local Windows credentials are aligned, use the WinCC User Administrator runtime user credentials in the Interconnect dialog itself.
What user right is required for a Uni-Client to run the server project?
The WinCC User Administrator right "Configure remote" (right number 1002 in the WinCC rights bitset) must be granted to the runtime user. Without it the client can connect for deactivation but cannot start the project.
Do I need to migrate the client project as well as the server?
Only for Multi-Client (Type 1) deployments. Uni-Clients (Type 2) have no local project - only the server project needs to be migrated to WinCC 7.4 SP1. After server migration, re-establish the SIMATIC Shell Interconnect from each Uni-Client.
What is a server package and when is it required?
A server package (.pck) is a snapshot of the server's graphics, tags, archives, and alarms generated via WinCC Explorer -> Server Data -> Create Package. It is required only for Multi-Client (Type 1) installations and must be regenerated after every server-side project change that affects tags or archive layout.
Which ports must be open between WinCC server and client?
Open UDP 50523 and 50524 for SIMATIC Shell discovery and project activation, plus TCP 445 (SMB) for project and archive share access. SQL Server traffic on TCP 1433 is required if the archive database is queried directly from a Multi-Client. Block all other inbound ports.