1. Overview
Updating a deployed Siemens WinCC v7.0 SCADA project in the field is fundamentally different from recompiling an application: the runtime database (ArchiveManager, <Project>RT.mdf, <Project>RT.ldf) is the live historian of the plant, and TagLogging segments, AlarmMessage ring buffers, and user archives must survive the upgrade. This article documents the field-proven procedure to deploy a new WinCC v7.x project revision (graphics, C-scripts, VBA macros, dynamics, alarm configuration) onto a customer computer while keeping the entire runtime history intact, and to re-attach that history to the freshly opened project after the upgrade.
The procedure applies to projects authored in WinCC v7.0 and migrated within the v7.x branch (v7.0, v7.2, v7.3, v7.4, v7.5). For major version jumps (e.g., v6.2 → v7.4) use WinCC Project Migrator; for same-version engineering revisions (v7.0 SP3 → v7.0 SP3 on two different computers) the manual merge procedure below is sufficient and avoids migrating segment databases that would otherwise be rebuilt empty.
HKLM\SOFTWARE\Siemens\WinCC) before beginning any update. A failed re-attach of the ArchiveManager folder is recoverable only if the original runtime databases are still on disk.2. Prerequisites
Verify the following before touching the customer PC:
-
WinCC version parity. The engineering PC and the runtime PC must run the same WinCC major/minor version (e.g., both v7.0 SP3). Mismatched service packs will cause Project Migrator to refuse the file, and the binary project file (
<Project>.MCP) is not forward- or backward-compatible across SPs in all cases. - Identical licensing. The customer computer must have a WinCC RC + RT license (Runtime + Configuration). An RT-only license cannot open the project in the Graphics Designer; you will need RC activated temporarily, or you must edit the project on the engineering PC and copy the closed project file over.
-
SQL Server runtime. WinCC v7.x uses Microsoft SQL Server (2005/2008/2012/2014 depending on service pack) to host the runtime database. Confirm the SQL Server service (
WinCC -> SQL Serverinservices.msc) is running before the backup. - Consistent computer name handling. When the project was first copied from engineering to customer, the internal computer name string was already overwritten. After update, the customer computer name must remain identical, otherwise internal computer-specific references (startup lists, server prefixes) need to be re-mapped.
- Tag name stability. The TagLogging tags, AlarmMessage tags, and User Archive field names must not be renamed between the old and new project version. If tag names changed, archive re-linking will produce orphaned or empty columns and the old data is effectively lost.
- Administrative Windows account. You need local administrator rights plus the SQL Server sysadmin role on the WinCC instance to detach/attach MDF/LDF files.
3. WinCC Project Folder Structure
A standard WinCC v7.x project directory contains the following load-bearing subfolders. Knowing which folder owns which data is essential for a partial update that keeps history alive.
| Path under <ProjectFolder> | Content | Update behavior |
|---|---|---|
ArchiveManager |
TagLogging and AlarmMessage ring-buffer segments (.dtl, .dta compressed/encrypted segment files), plus the Archive Configuration database |
Preserve verbatim. Never overwrite with the engineering copy; re-attach after the new project opens. |
<Project>RT.mdf |
SQL Server primary data file for runtime system data (alarms in queue, user archives, internal variables) | Preserve verbatim. Detach, copy, re-attach in the new project. |
<Project>RT.ldf |
SQL Server transaction log for the runtime database | Preserve verbatim. Required for a consistent re-attach. |
GraCS |
Process pictures (.pdl), library symbols, project graphics, language files |
Replace with the new engineering revision. |
Library |
Project-specific C-script action library headers and source files | Replace with the new engineering revision. |
PAS |
Process-Action Scripts folder for picture-specific actions | Replace with the new engineering revision. |
ScriptLib |
Global C-script function library | Replace with the new engineering revision; may require regenerating function headers. |
Pictures |
Legacy binary picture cache (older projects only) | Discard — replaced on next picture compile. |
Textbibliothek |
Multilingual text library (Textbib) | Replace with the new revision. |
UserArchives |
CSV/DBF user archive data views (in addition to RT.mdf) | Preserve if user archive field structure is unchanged. |
Redundancy |
Optional redundant server state files | Preserve only if a redundant partner exists. |
<Project>.MCP |
Master Control Project — the binary project file (the one opened in WinCC Explorer) | Replace with the new engineering revision. |
<Project>.ldf (project, not RT) |
SQL Server transaction log for the engineering database | Discard or replace; engineering DB is rebuilt from MCP. |
ComputerName / RT
|
Computer-specific runtime configuration (startup list, hotkeys, services) | Preserve the customer-side settings. |
4. Pre-Update Backup Procedure
Run the full backup sequence on the customer computer with WinCC Runtime stopped. Stop the project in WinCC Explorer (right-click the project → Stop Runtime) or stop the WinCC Runtime and WinCC -> SQL Server services.
- Stop the WinCC Runtime and the
SIMATIC WinCC -> SQL Serverservice fromservices.msc(or usenet stop "WinCC_Project"andnet stop "WinCC_SqlServer"). - Copy the entire project folder to a timestamped backup directory on a separate drive:
copy D:\WinCC\Projects\<ProjectName> E:\Backup\<ProjectName>_preUpdate_<YYYYMMDD> /E /H /K - Export the ArchiveManager configuration by running WinCC Archive Configurator and selecting Backup → Connect Backup. This forces a segment rollover and creates a consistent snapshot.
- Detach the runtime database using SQL Server Management Studio (SSMS) connected to
WINCC\WINCC(the default WinCC instance) — right-click<ProjectName>RT→ Tasks → Detach, checking Drop Connections and Update Statistics. - Copy
<Project>RT.mdfand<Project>RT.ldffrom the SQL Server default data directory (typicallyC:\Program Files\Microsoft SQL Server\MSSQLxx.<instance>\MSSQL\DATA) into the backup directory. - Back up the Windows registry hive:
reg export "HKLM\SOFTWARE\Siemens\WinCC" E:\Backup\wincc_reg_backup.reg /y - Record the current TagLogging segment sizes, segment times, and archive tags to a text file using the WinCC Archive Configurator Export function — this lets you diff against the new project.
.mdf/.ldf files while the SQL Server service is running; the files will be locked and the copy will be inconsistent. The ArchiveManager folder is safe to copy after WinCC Runtime is stopped.5. File-by-File Update Strategy
The general rule for a same-version update is: replace what the engineer changed, preserve what the runtime accumulated. The merge is asymmetric.
5.1 Components to REPLACE from the engineering revision
-
GraCS\— All new and modified.pdlpictures, including copy-pasted pictures transferred from the engineering GraCS folder. -
Library\,PAS\,ScriptLib\— All C-scripts, VBA macros, and project functions. Function header regeneration is typically required when global function signatures changed; the Graphics Designer prompts for this on first compile. -
Textbibliothek\— Updated text IDs and language variants. -
<Project>.MCP— The new master project file. - Alarm Logging configuration files (within the project database) if alarm classes, priorities, or message tags were revised — handled automatically by opening the new MCP.
5.2 Components to PRESERVE from the customer PC
-
ArchiveManager\— All TagLogging and AlarmMessage ring-buffer segments. These are the historical record. -
<Project>RT.mdfand<Project>RT.ldf— The SQL Server runtime database, containing the alarm message queue state, user archive current values, and WinCC internal data. -
UserArchives\— Active user-archive data (if not in RT.mdf). - Customer-side
ComputerName\settings — startup sequence, hotkey configuration, services list, redundancy partner if any.
6. Step-by-Step Update Procedure
The following is the field procedure used when an engineer delivers a new WinCC v7.0 project revision to a customer PC and the runtime history must be retained.
-
Stop runtime and SQL services on the customer computer, as in Section 4. Confirm both services show Stopped in
services.msc. -
Detach the runtime database in SSMS:
WINCC\WINCC→ Databases →<ProjectName>RT→ Tasks → Detach. -
Stage the engineering project. Create a new folder
D:\WinCC\Update\<ProjectName>_v2and copy the entire new engineering project (MCP, GraCS, Library, PAS, ScriptLib, Textbibliothek) into it from the engineering computer. -
Replace the project file on the customer PC. From the staged folder, copy into the existing customer project location:
Do NOT copy ArchiveManager, RT.mdf, or RT.ldf from the staged folder.xcopy /E /I /Y D:\WinCC\Update\<ProjectName>_v2\GraCS D:\WinCC\Projects\<ProjectName>\GraCS xcopy /E /I /Y D:\WinCC\Update\<ProjectName>_v2\Library D:\WinCC\Projects\<ProjectName>\Library xcopy /E /I /Y D:\WinCC\Update\<ProjectName>_v2\PAS D:\WinCC\Projects\<ProjectName>\PAS xcopy /E /I /Y D:\WinCC\Update\<ProjectName>_v2\ScriptLib D:\WinCC\Projects\<ProjectName>\ScriptLib xcopy /E /I /Y D:\WinCC\Update\<ProjectName>_v2\Textbibliothek D:\WinCC\Projects\<ProjectName>\Textbibliothek copy /Y D:\WinCC\Update\<ProjectName>_v2\<ProjectName>.MCP D:\WinCC\Projects\<ProjectName>\<ProjectName>.MCP -
Re-attach the old runtime database. In SSMS, right-click Databases → Attach and select the preserved
<Project>RT.mdf; the transaction log file (.ldf) is auto-discovered if it is in the same directory. -
Re-link the ArchiveManager folder. Open WinCC Explorer on the customer computer and open the upgraded
<Project>.MCP. The new project will detect an existing ArchiveManager and prompt to reconnect; confirm. If no prompt appears, open Tag Logging → right-click the archive tag → Properties → Archive Configuration → verify the segment storage path still points to the originalArchiveManagerfolder.If the TagLogging tag names changed, the old segments are no longer matched to the new tags. Either revert the rename or accept that the disconnected segments are unrecoverable. Always diff tag names in the Archive Configurator export between old and new revisions before merging. - Verify picture scripts compile. Open the Graphics Designer, load the start picture, and run Tools → Recompile All Pictures. Resolve any "Function not defined" errors by regenerating function headers (right-click the picture → Header → Reset).
-
Restart services:
net start "WinCC_SqlServer"followed bynet start "WinCC_Project"(or use the WinCC Service Control Applet). - Activate the project in WinCC Explorer and verify the runtime starts cleanly.
7. Re-Linking Historical Archives After the Update
After the new project is open and the ArchiveManager folder is in place, verify the historical continuity of each TagLogging tag and AlarmMessage class. The runtime is now writing new segments into the same folder; the old segments remain in place and are queried by the WinCC Trend Control and Alarm Control on demand.
To re-link explicitly (only needed if the re-attach was not automatic):
- Open WinCC Explorer → Tag Logging.
- Right-click the project node → Archive Configuration.
- For each archive tag, confirm the Storage Location field shows the path to the original
ArchiveManagerfolder, not a new empty path. - Click Connect Backup in the toolbar to merge the new tag configuration with the existing segment files. A status dialog lists the number of segments linked.
For AlarmMessage ring buffers, the same logic applies: Alarm Logging → Archive Configuration → Connect Backup. The WinCC AlarmControl view should immediately show historical messages with their original timestamps when the time range filter is widened.
8. Verification Checklist
| Check | Expected result | Verification method |
|---|---|---|
| Runtime starts | Project activates without error popup; no red X icons in WinCC Explorer | Open WinCC Explorer → project node shows green play icon |
| TagLogging continuity | Old trend values visible in WinCC Trend Control for the same tag across the upgrade timestamp | Open a trend view, set time range to span the update instant, verify continuous line |
| AlarmMessage history | Old alarms still listed in AlarmControl with original timestamps | Open AlarmControl, set time filter to pre-update, verify entries |
| Picture scripts | All .pdl pictures compile without "Function not defined" |
Graphics Designer → Tools → Recompile All; check output log for errors |
| VBA macros | VBA project loads, modules run, references intact | ALT+F11 in Graphics Designer → verify project tree and run a sample macro |
| User archives | Old user-archive rows still queryable with current values updated | Open User Archive table view, verify row count and current values |
| Database consistency | DBCC CHECKDB on the attached RT database returns clean | In SSMS: DBCC CHECKDB('<ProjectName>RT')
|
| Segment rollover | New segments created under ArchiveManager with correct size/time | Check ArchiveManager folder for new .dtl files post-activation |
9. Troubleshooting Matrix
| Symptom | Likely cause | Resolution |
|---|---|---|
| WinCC Explorer reports "Project database is not compatible" | MCP came from a different WinCC service pack | Verify versions match with WinCC Explorer → Help → About on both PCs; if different, use WinCC Project Migrator on the engineering side first |
| Tag Logging shows no historical data after update | Tag names were renamed in the new project, or ArchiveManager path was overwritten | Diff tag names between old and new archive exports; restore ArchiveManager from pre-update backup if overwritten |
| SSMS cannot attach RT.mdf: "Access is denied" | File permissions on the .mdf/.ldf, or SQL service account lacks write access | Grant NT SERVICE\MSSQLSERVER (or instance account) Full Control on the folder; re-attach |
| AlarmControl shows alarms only after the update timestamp | AlarmMessage segments not re-linked | Alarm Logging → Archive Configuration → Connect Backup |
| Picture "Function xxx not defined" on open | C-script function headers in the new MCP do not match the existing GraCS pictures | Graphics Designer → right-click picture → Header → Reset; recompile |
| VBA: "Cannot find project or library" | VBA references resolved against the engineering PC's library paths | ALT+F11 → Tools → References → re-resolve missing entries; or re-import the VBA project from the engineering .bas exports |
| SQL Server service fails to start after re-attach | Master database and RT.mdf are from mismatched SQL Server versions | Restore original RT.mdf from backup; re-attach via sp_attach_db with sp_detach_db first |
| New segments being written to a wrong path | Archive Configuration storage path was reset when the new MCP was opened | Tag Logging → Archive Configuration → correct the Storage Location back to ArchiveManager and re-link |
| Computer name string inside project still references engineering PC | Project was not "re-copied with computer name change" after update | Use WinCC Explorer → right-click the project → Change Computer Name… to re-stamp the customer PC name |
10. When to Use WinCC Project Migrator Instead
The manual merge procedure above is the right tool for same-version engineering updates. For different version updates, use WinCC Project Migrator, which automates the conversion of the project file and all referenced sub-projects. Migrator is invoked from Start → Siemens Automation → WinCC → Tools → Project Migrator and steps through:
- Selection of source project (older version) and target version.
- Backup of the source project (mandatory — Migrator refuses to proceed without one).
- Conversion of the MCP, the engineering database, and the runtime database schema.
- Generation of a migration log listing all converted objects, warnings, and errors.
For installations where continuous uptime is mandatory and any update window is unacceptable, the standard Siemens recommendation is a redundant WinCC server/client pair: the standby server is updated while the primary carries runtime, then a controlled failover. This is a much larger architectural change and is typically scoped into the project from the start, not retrofitted for a single update.
11. Field-Proven Caveats
- Always work from a copy. Even with backups, do the first update on a clone of the customer PC (disk image or a test bench with the same WinCC version) before touching the live machine. The clone catches 90% of surprises (MCP version mismatch, missing DLLs, VBA reference drift) before they happen on the production system.
- Tag name parity is a hard contract. Treat the list of TagLogging and AlarmMessage tag names as an API between the engineering revision and the deployed runtime. Renames require a written migration plan: dump the old data, transform, re-import under the new name — there is no in-place rename that preserves segment history.
- Don't mix ArchiveManager folders from different projects. The folder is keyed implicitly to the project database; cross-project pasting will produce read errors and potential data corruption. Each WinCC project owns exactly one ArchiveManager.
- User archive views may need manual refresh. After re-attaching RT.mdf, User Archive table views in the Graphics Designer sometimes need to be re-opened to pick up the current row pointer; a page refresh (F5 on the active picture) is usually sufficient.
- Segment encryption keys. If the customer project uses encrypted segments (configured in Archive Manager → Properties), the key is stored in the project database. After merging, the new project picks up the existing key automatically, but on a clean re-deploy the segments will become unreadable. Always re-attach before opening the new MCP for the first time when encryption is enabled.
12. References Used in This Procedure
For the official Siemens FAQ on data backup of WinCC projects (TagLogging, Alarm Logging, and project databases), see entry 29488044 in the Siemens Industry Online Support: Siemens Industry Online Support entry search. The same article documents which files belong to a complete backup and the recommended order for restoring from backup.
For project versioning and migration beyond the v7.0 to v7.x path, consult the WinCC V7.x documentation set on the same portal, in particular the WinCC Information System chapters on Project Administration and WinCC Project Migrator.
Can I just copy the entire new engineering project folder over the old one and keep the history?
No. A full folder copy will overwrite the ArchiveManager folder and the RT.mdf/RT.ldf files with the engineering copies, which are empty or have only the engineering-side test data. You must selectively copy only the folders and files that the engineer changed (GraCS, Library, PAS, ScriptLib, Textbibliothek, the .MCP) and preserve ArchiveManager, RT.mdf, and RT.ldf from the customer PC.
What files contain TagLogging and AlarmMessage history?
TagLogging and AlarmMessage history is stored in the ArchiveManager folder as compressed/encrypted segment files (.dtl) plus the Archive Configuration database. The runtime alarm queue and user archives are also kept in the SQL Server runtime database files <Project>RT.mdf and <Project>RT.ldf. Both ArchiveManager and the MDF/LDF pair must be preserved.
Do I need to detach the SQL Server database before copying RT.mdf?
Yes. The MDF and LDF files are locked by the SQL Server service while it is running. Either stop the service or detach the database in SQL Server Management Studio (right-click → Tasks → Detach, with Drop Connections) before copying. Copying locked MDF files produces an inconsistent image that may refuse to re-attach.
What happens if the new project renamed one of the TagLogging tags?
The historical segments are keyed by tag name. A renamed tag in the new project will not match the old segment file, and the old data will appear as orphaned. To recover, either revert the tag name to match the original or accept that the historical data for that one tag is lost. Always diff tag names between the old and new archive configurations before merging.
When should I use WinCC Project Migrator instead of the manual merge?
Use Project Migrator when the source and target WinCC versions differ (for example, v6.2 to v7.4). Migrator handles the MCP and engineering database conversion automatically. For same-version engineering updates where only pictures, scripts, and dynamics changed, the manual merge procedure described in this article is faster and avoids losing the ArchiveManager contents that Migrator would otherwise treat as stale.