Wiring Pushbuttons and Limit Switches to LOGO! 8 Digital Inputs

David Krause18 min read
PLC HardwareSiemensTutorial / How-to
Licensed PE Working through this on a live machine? A Maine-licensed engineer can take it from here — included with IMD hardware, by the hour for everything else. Book an engineer

System Overview

Siemens LOGO! 8 miniature logic modules (programmable relays) accept 24 V DC digital signals directly from mechanical switches, pushbuttons, limit switches, and proximity sensors without any signal conditioning. A recurring commissioning question concerns the ability of a LOGO! input to handle the current delivered by a 24 V DC power supply sized for high-current loads such as solenoid valves. The premise itself is the result of a category error: a power supply rated 10 A does not force 10 A into the LOGO! input. The current drawn is determined by the input impedance of the receiver, not the maximum capability of the source. A LOGO! digital input draws approximately 0.3 mA at 24 V DC, so a 10 A supply has more than six orders of magnitude of headroom for the input circuit.

This article covers the wiring of a momentary normally open (NO) pushbutton and two mechanical limit switches to a LOGO! 8 base module (order code 6ED1052-1MD08-0BA1 as reported by the operator) for the purpose of controlling a reciprocating hydraulic cylinder. It addresses:

  • Hardware identification of the LOGO! 8.2 base module
  • Input electrical characteristics
  • Pushbutton and limit switch wiring topology
  • Analog/digital multiplexing on terminals I1, I2, I7, I8
  • Recommended ladder/FBD architecture for start/stop, direction change, and timeout protection
  • Verification procedure and troubleshooting matrix

Hardware Identification

Siemens LOGO! 8 base modules are ordered under a structured catalog code. The reported order number 6ED1052-1MD08-0BA1 is decoded in the following table. Note that standard catalog listings for the LOGO! 8.2 family most commonly carry the suffix BA0; the trailing BA1 should be verified against the physical rating plate on the right side of the module before commissioning. The electrical and logical characteristics described below apply to the entire 6ED1052-1MD08 family.

Field Value Meaning
6ED1 Siemens LOGO! family
052 LOGO! 8 generation
1 With display Integrated 6-line LCD and 6-key keypad (LOGO! ...o variant)
M 24 CEo (DC/DC/Relay) 24 V DC supply, 24 V DC inputs, relay outputs
D 4 relay outputs (R) Q1–Q4 are volt-free changeover contacts
08 LOGO! 8.2 Hardware platform; minimum firmware FS:02 onward
0BA1 Order variant Verify against nameplate; standard release is 0BA0

Confirm the following on the physical nameplate before proceeding:

  1. Supply range: 24 V DC (allowed 20.4–28.8 V DC)
  2. Eight digital inputs (I1–I8) sourced from the internal 24 V rail
  3. Four relay outputs rated 10 A resistive / 2 A inductive at 24 V DC / 230 V AC
  4. Analog function available on I1, I2, I7, I8 (0–10 V, 10-bit resolution)
Verify the catalog number. The 0BA1 suffix differs from the most common 0BA0 release. The relevant manual is the LOGO! 8.2 system manual, entry ID 109751616 on the Siemens Industry Online Support portal. Always cross-reference with the actual rating plate.

Power Supply Architecture and 24 V Distribution

A 24 V DC power supply with a 10 A rating is typically selected because the load includes solenoid coils, each of which can draw 1–3 A inrush and 200–500 mA holding. The LOGO! base module itself draws approximately 45 mA at 24 V (with all relays de-energized and the display off) and roughly 95 mA with the display at full brightness. The eight digital inputs collectively draw on the order of 2.4 mA. Total LOGO! consumption is therefore below 150 mA — a small fraction of the supply capability.

Recommended distribution topology:

  1. Single 24 V DC / 10 A power supply with electronic current limiting.
  2. Branch 1 (high current, fused at 6–8 A) feeds the solenoid valves via a common 24 V rail.
  3. Branch 2 (logic, fused at 1 A slow-blow) feeds the LOGO! L+ / M terminals.
  4. Mechanical switches (pushbutton, limit switches) are wired between the LOGO! input terminal (I1–I8) and the LOGO! M (24 V common/ground reference) terminal. Do not wire the switch between an input terminal and 24 V positive — the LOGO! inputs are type 1 (IEC 61131-2) and sink current to M.
Polarity matters. On the 24 V LOGO!, switching the input high (towards 24 V) does not register as ON. The input registers ON when the terminal is pulled to M (0 V) through the switch. This is opposite of a PNP sensor convention. Verify with the LOGO! Soft Comfort simulation before connecting field wiring.

Digital Input Electrical Characteristics

Specifications below apply to the 24 V DC input section of the LOGO! 8 base module (per the LOGO! 8.2 system manual, Section A.2).

Parameter Value
Input type Type 1 (IEC 61131-2), sinking
Nominal voltage 24 V DC
Permitted range, ON state > 12 V DC (positive terminal higher than M)
Permitted range, OFF state < 5 V DC
Input current per input at 24 V typ. 0.3 mA
Input impedance approx. 80 kΩ
Switching delay, ON to OFF typ. 1.5 ms
Switching delay, OFF to ON typ. 1.5 ms
Maximum input frequency (mechanical) 4 Hz
Cable length, unshielded ≤ 100 m
Cable length, shielded ≤ 100 m
Isolation No isolation to logic (referenced to M internally)

These figures make clear why the 10 A power supply is irrelevant to the input: the input current is set by the internal pull-up network (or, in this case, the input's reference to M), not by the supply. A mechanical switch contact simply closes a path between an input terminal and M, and the input then sources (or sinks, depending on convention) microamps through that contact.

Wiring a Normally Open Pushbutton to I1–I8

A momentary NO pushbutton is the simplest possible input device. Wire it as a "dry contact" between the LOGO! input terminal and the M terminal on the same module.

Connection List (Start Pushbutton)

Wire From To Conductor
1 LOGO! terminal I3 (digital input, e.g. "Start") Pushbutton contact, pole 1 0.5–1.5 mm² Cu, stranded
2 LOGO! terminal M Pushbutton contact, pole 2 0.5–1.5 mm² Cu, stranded

No external resistor, capacitor, or power supply is required. When the pushbutton is open, the input reads 0 (LOW). When the pushbutton is closed, the input reads 1 (HIGH). The input threshold is internally defined; no user calibration is necessary.

Do not connect a voltage source to an input. The pushbutton must be a "dry contact" — that is, it must not switch an externally applied voltage. External voltage applied to a LOGO! input will exceed the 24 V type 1 input rating and may damage the module. Use a separate switch contact, not the contact of a relay coil that has its own supply.

Wiring Mechanical Limit Switches

Mechanical limit switches for hydraulic cylinder end-of-stroke position feedback are typically SPDT (single pole, double throw) devices with NO, NC, and common terminals. The recommended practice is to use the NO contact in series with the LOGO! input to M.

Connection List (Two Limit Switches)

Wire From To Function
3 LOGO! terminal I4 LS1 common Limit switch 1 (extended position)
4 LOGO! terminal M LS1 NO contact Pulls I4 to M when cylinder fully extended
5 LOGO! terminal I5 LS2 common Limit switch 2 (retracted position)
6 LOGO! terminal M LS2 NO contact Pulls I5 to M when cylinder fully retracted

Mechanical limit switches bounce on contact closure. The LOGO! input has no built-in debounce filter; the firmware will register the bounce as multiple transitions. The recommended practice is to enable the input debounce filter in LOGO! Soft Comfort (Tool → Input Debounce) for each mechanical input, or to handle debounce in program logic with a TON (on-delay timer) of 20–50 ms before the limit switch signal is allowed to influence the cycle.

Analog and Digital Multiplexing on I1, I2, I7, I8

On 24 V DC base modules, terminals I1, I2, I7, and I8 are dual-function: each can be used as a 24 V DC digital input or as a 0–10 V analog input. The selection is made in LOGO! Soft Comfort under File → Properties → Inputs/Outputs, by editing the input block's parameter and selecting either Digital or Analog usage. The setting is per-terminal; the unused function is then disabled.

Terminal Digital function (24 V DC) Analog function (0–10 V)
I1 Yes Yes (AI1, 0–10 V, 10-bit)
I2 Yes Yes (AI2, 0–10 V, 10-bit)
I3 Yes No
I4 Yes No
I5 Yes No
I6 Yes No
I7 Yes Yes (AI3, 0–10 V, 10-bit)
I8 Yes Yes (AI4, 0–10 V, 10-bit)

If a 0–10 V analog sensor is connected to I1, I2, I7, or I8, the corresponding digital input function for that terminal becomes unavailable. For the hydraulic cylinder application described, where the start pushbutton and two limit switches are the only field devices, all three signals should be assigned to non-multiplexed terminals (e.g. I3, I4, I5) to avoid accidentally losing a digital function to an unused analog configuration.

Two-Wire versus Three-Wire Sensors

Mechanical switches and 3-wire PNP sensors are wired as described above. 2-wire sensors (e.g. mechanical proximity switches, reed switches, or inductive sensors that share the input pair as both power and signal) present a special case:

  • 2-wire mechanical switch: Connect the two switch leads to the LOGO! input and M. The input sees a low-impedance path when closed; no residual current is required. The LOGO! 24 V digital input detects the closure reliably because its internal threshold (12 V ON, 5 V OFF) is well above the contact drop of a closed mechanical pair.
  • 2-wire electronic sensor (e.g. NAMUR-style): A small leakage current flows even in the OFF state. Verify that the LOGO! OFF threshold of 5 V is not exceeded by the residual voltage of the sensor in its open state. If the sensor's leakage is high enough to register as ON, a pull-down resistor or a relay interface is required.
  • 3-wire PNP sensor (sourcing): Connect the brown wire to LOGO! 24 V (L+), the blue wire to LOGO! M, and the black (output) wire to the LOGO! input. The output switches 24 V to the input, which is the opposite of the dry-contact convention. To convert, use the input as active-LOW and invert the logic in the program, or use a relay interface.
The original report of "Logo is unable to use a 2 wire analog input" refers to a different constraint: the analog inputs on I1, I2, I7, I8 expect a 0–10 V voltage source, not a 2-wire current loop. 4–20 mA sensors will not function directly on these terminals and require a 250 Ω sense resistor to convert to 1–5 V.

Input Debouncing in LOGO! Soft Comfort

Mechanical contacts typically bounce for 1–20 ms. To prevent the LOGO! from registering multiple transitions on a single button press:

  1. Open the program in LOGO! Soft Comfort.
  2. Select Tools → Input Debounce (or, on older versions, Edit → Properties on the input block).
  3. Set debounce time to 20 ms for pushbuttons and 50 ms for mechanical limit switches.
  4. Transfer the program to the LOGO! base module.

Alternatively, implement debounce in logic: a 30 ms on-delay timer (B001 in the program) blocks transient contacts from propagating to the latching circuit.

Program Architecture: Start/Stop with Hydraulic Cylinder

The functional requirement is a reciprocating hydraulic cylinder driven by two solenoid outputs:

  • Q1 — Extend solenoid (energises directional valve to extend cylinder)
  • Q2 — Retract solenoid (energises directional valve to retract cylinder)
  • I3 — Start pushbutton (NO, momentary)
  • I4 — LS1 (limit switch, cylinder fully extended)
  • I5 — LS2 (limit switch, cylinder fully retracted)

Three program requirements must be implemented explicitly; their omission is a common commissioning defect that produces the "looping without limit switch feedback" symptom reported in the field report.

  1. Latching (RS flip-flop): Use an SR (set/reset) block, B001. The Start pushbutton (I3) sets the latch. A Stop pushbutton (I6, NC contact for fail-safe) or a fault condition resets the latch. The latch output drives the cycle enable.
  2. Direction selection: A second RS flip-flop, B002, toggles between Extend and Retract on each cycle. Set on Start and on LS1; reset on LS2.
  3. Timeout protection: A watchdog timer (B003) is enabled whenever a direction output is active. If the corresponding limit switch does not activate within a configurable window (e.g. 10 seconds), the timer elapses and forces a fault, de-energising both solenoids and requiring operator intervention.

Ladder/FBD Implementation

The following FBD excerpt shows the core logic. It is written for LOGO! Soft Comfort V8.x and later.

Inputs:
  I3  -- Start pushbutton (NO, momentary)
  I4  -- LS1, cylinder fully extended (NO contact)
  I5  -- LS2, cylinder fully retracted (NO contact)
  I6  -- Stop pushbutton (NC, fail-safe)

Blocks:
  B001  SR flip-flop (cycle latch)
  B002  RS flip-flop (direction toggle)
  B003  TON, preset 10.0 s, base 1 s (extend timeout)
  B004  TON, preset 10.0 s, base 1 s (retract timeout)
  B005  AND (extend enable)
  B006  AND (retract enable)
  B007  OR (fault OR stop OR timeout reset)

Wiring:
  I3 --> B001.S
  I6 --> B007.in1
  B003.Q --> B007.in2
  B004.Q --> B007.in3
  B007    --> B001.R

  B001.Q --> B005.in1
  B002.Q --> B005.in2
  B005    --> Q1 (extend solenoid)

  B001.Q --> B006.in1
  NOT B002.Q --> B006.in2
  B006    --> Q2 (retract solenoid)

  Q1 --> B003.IN
  I4 --> B002.S  (set on reaching extended position)
  B003.Q --> B002.R (fault clears direction)

  Q2 --> B004.IN
  I5 --> B002.R  (reset on reaching retracted position)
  B004.Q --> B002.S (fault sets opposite direction? review)

Outputs:
  Q1  -- Extend solenoid driver
  Q2  -- Retract solenoid driver
  Q3  -- Fault indicator (e.g. beacon or HMI tag)

The exact reset/set assignment must be reviewed for the specific cycle desired. The key engineering point is that limit switch state must always be evaluated: the program must not assume a limit switch is reached on time without explicit verification. A program that simply toggles a direction flag on a timer — without reading I4 and I5 — is unsafe and will continue cycling even if the cylinder stalls or the limit switch fails.

Fault monitoring requirements. A hydraulic system that continues to energise a directional valve while the cylinder is mechanically stuck can overheat the hydraulic fluid, trip the pump relief valve, or, in the case of a press, create a pinch point. The timeout protection is a baseline safety requirement, not an option. For personnel protection, evaluate the system against ISO 13849-1 and any applicable press safety standard (e.g. ANSI B11.1, EN 693) before commissioning.

Wiring Topology

24 VDC PSU 10 A, regulated L+ / M / PE 24 V to LOGO! L+ 24 V to solenoid rail LOGO! 8.2 6ED1052-1MD08 I1 I2 I3 I4 I5 I6 M Q1..Q4 relays to PB1 to LS1 to LS2 to M bus PB Start (NO) LS1 Extended LS2 Retracted to LOGO! M

Timing Diagram

PB Start LS1 Ext Q1 Extend LS2 Ret Q2 Retract t0: Start pressed t1: LS1 reached t2: LS2 reached

Verification Procedure

After wiring and program transfer, perform the following verification in order.

  1. Power-on test. Apply 24 V DC to L+/M. The LOGO! should power up, display the date/time, and remain in RUN. The display should read "LOGO!" and the current program name.
  2. Input forcing (offline). In LOGO! Soft Comfort, open Tools → Simulation. Force I3 high. The cycle latch (B001) should set. Force I4 high; the direction flip-flop (B002) should toggle and Q1 should de-energise while Q2 energises.
  3. Input forcing (online). With the program transferred to the module, press the Start pushbutton. The cycle should begin. Observe the LOGO! display or use the LOGO! Soft Comfort online monitor to verify I3, I4, I5, Q1, Q2 state.
  4. Voltage measurement at each input. With the field device open, the input terminal should read 24 V relative to M. With the field device closed, the input terminal should read < 5 V relative to M. Any reading between 5 V and 12 V indicates a partial fault (high-resistance contact, poor crimp, or a damaged sensor).
  5. Limit switch test. Manually actuate the cylinder to each end position. The corresponding limit switch LED on the LOGO! (visible on the front of the base module) should illuminate. The corresponding input variable in the online monitor should read 1.
  6. Timeout test. Block the cylinder mechanically so it cannot reach the limit switch. After the configured timeout (e.g. 10 s), the fault output (Q3 or an HMI tag) should activate and the directional outputs should de-energise.
  7. Stop pushbutton test. Press Stop (NC contact). The cycle latch should reset. Both Q1 and Q2 should de-energise immediately.
Force inputs in simulation first. Never troubleshoot a running hydraulic system by manipulating live wiring. Use LOGO! Soft Comfort's online monitor or the LOGO! display to read input and output states while the system is in a safe state (e.g. pump off, valve de-energised).

Troubleshooting Matrix

Symptom Probable cause Diagnostic Corrective action
Pushbutton does not start the cycle Wired to a 24 V terminal instead of M, or input configured as analog Measure voltage at input terminal: should be 0 V when pressed, 24 V when released Re-wire to M. Verify input is set to Digital in Input Properties.
Pushbutton starts the cycle but program does not stop on limit switch Limit switch wired but its input is not referenced in program, or debounce hides the transition Force input in simulation; observe I4 and I5 in online monitor Add I4 and I5 to the program logic. Enable 20–50 ms debounce.
Cycle loops continuously without respecting cylinder position Direction toggle driven by timer only, not by limit switch Read program in FBD; identify the direction-flip trigger Replace the timer-only direction toggle with an RS flip-flop set/reset by LS1/LS2.
LOGO! does not power up 24 V supply not present, polarity reversed, or fuse blown Measure L+ to M: should be 20.4–28.8 V DC Check fuse; verify polarity; check supply regulation.
One input reads 1 even when field contact is open Cross-wired to adjacent terminal, or short between conductors Disconnect field wire at LOGO! terminal; input should drop to 0 Inspect wiring; replace damaged cable.
Input reads indeterminate (5–12 V) High-resistance contact or partial short Measure input impedance to M with input open; should be ≥ 70 kΩ Replace switch or cable. Verify crimp quality.
Cycle stops after timeout but never restarts Latch not cleared by operator after fault Inspect fault reset logic; verify Stop pushbutton is NC and wired to M Add explicit fault reset: pressing Stop after a fault must clear B001 latch and B002 direction.
LOGO! input LED on but program does not respond Input assigned to analog function in Input Properties Open LOGO! Soft Comfort, view the input block; check usage flag Change usage from Analog to Digital; transfer program.
Both solenoids energise simultaneously No interlock in program; short between Q1 and Q2 wiring Read Q1 and Q2 in online monitor during cycle Add explicit Q1 NOT Q2 AND, Q2 NOT Q1 AND interlock. Verify field wiring.

Notes on Catalog Number and Documentation

For the most accurate and up-to-date information, always refer to the official Siemens documentation:

  • Siemens Industry Online Support — search for "LOGO! 8.2 system manual" (entry ID 109751616) for the full hardware and programming reference.
  • The LOGO! product page on siemens.com lists current catalog numbers, firmware versions, and accessories.
  • LOGO! Soft Comfort (V8.x and later) is the official programming environment; download from the Siemens support portal after registration.

Does the LOGO! 8 digital input need a current-limiting resistor when wired to a pushbutton?

No. The LOGO! 8.2 base module has internal input impedance of approximately 80 kΩ and draws about 0.3 mA per input at 24 V DC. The pushbutton is wired as a dry contact between the input terminal and the M terminal, with no external resistor required.

Can I use I1, I2, I7, or I8 as both a digital and an analog input at the same time?

No. Each of these terminals on the 24 V base module is dual-function: it is either a 24 V DC digital input or a 0–10 V analog input, but not both. The selection is made in LOGO! Soft Comfort under the input block's properties. For applications that require both analog and digital signals, use the analog terminals for the analog sensors and assign digital devices to I3, I4, I5, I6 (which are digital-only).

Why does my pushbutton appear to "do nothing" when I wire it between the input and 24 V positive?

The LOGO! 8.2 24 V inputs are type 1 (IEC 61131-2) and register ON when the terminal is pulled toward M (0 V), not toward 24 V. A pushbutton wired to 24 V positive will hold the input OFF in both states (open and closed). Re-wire the contact so that one pole goes to the input terminal and the other to M.

How do I add timeout protection to a hydraulic cylinder cycle?

Use a TON (on-delay timer) block in LOGO! Soft Comfort. Start the timer whenever the directional output (Q1 or Q2) energises. If the corresponding limit switch does not activate within the preset time (typically 5–15 seconds depending on stroke length and hydraulic flow), the timer elapses. Wire the timer's output to a fault flag and to the reset input of the cycle latch. The system then requires an operator action (Stop / Reset) to resume.

Can the LOGO! 8 base module source power to a 3-wire PNP sensor, or does the sensor need a separate supply?

The LOGO! 8.2 24 V base module does not provide a dedicated sensor power output. The standard practice is to power the sensor from the same 24 V rail as the LOGO! (L+ and M), then wire the sensor's PNP output to the LOGO! input. For NPN sensors, use a signal inverter or a relay interface, because the LOGO! input is active-low referenced to M.

What is the difference between a 2-wire and 3-wire limit switch, and which should I use with a LOGO!?

A 2-wire switch (mechanical, reed, or NAMUR) has only two connection points and either opens or closes a single circuit. A 3-wire PNP sensor has separate power, ground, and output wires and actively sources 24 V when its target is detected. For a LOGO! digital input, a 2-wire mechanical limit switch is the simplest and most reliable choice. A 3-wire PNP sensor can be used, but because the LOGO! input is active-low, you must either invert the logic in the program or use a relay interface.

Back to blog