Adding Flowmeter and Sensor Graphics to an EasyBuilder Pro Screen

HMI and touchscreens Published 6 min read

Short answer

EasyBuilder Pro has no dedicated flowmeter or temperature-sensor object, and it does not need one. Put a picture from the Shape or Picture Library (or your own imported image) on the screen to identify the instrument, then add a separate numeric object bound to the device address for the live measurement — the picture never carries the data connection.

On this page
  1. Why the object list has no flowmeter
  2. Decide what each point on the screen shows
  3. Place the instrument graphic
  4. Bind the live value
  5. Worked example: one flowmeter and one temperature sensor
  6. Give the symbol a state only when a register backs it
  7. Where symbol artwork may come from
  8. When the graphic and the value misbehave separately
  9. Questions asked

EasyBuilder Pro has no object called a flowmeter or a temperature sensor, and you do not need one. An instrument point on the screen is two objects: a picture that identifies the hardware, and a numeric object bound to a device address that shows the measurement. The picture comes from the Shape Library or the Picture Library inside the editor, from Weintek's library downloads, or from artwork you own; the value comes only from the device connection. This walkthrough places both objects for one flowmeter and one temperature sensor, binds the values, scales them once, and separates a missing graphic from a dead tag.

Why the object list has no flowmeter #

The object palette in EasyBuilder Pro is data-driven: numeric objects, text objects and buttons read addresses, while the Shape Library and the Picture Library supply the visuals. There is no instrument category to search, so hunting for a "sensor object" in the object list fails by design. Weintek publishes additional picture and object libraries for EasyBuilder Pro and EasyBuilder X in the Library section of its download pages, and symbols there are grouped by appearance rather than by instrument type, so search by how the symbol looks, not by loop type. A generic meter or gauge carrying the right loop tag identifies the point better than a detailed replica with no tag. Build the point from two objects and stop searching for a third.

Decide what each point on the screen shows #

The operator needs Object Driven by
Recognize the instrument Picture from a library Nothing; static artwork
Read the measurement Numeric object Device address holding the value
Read the accumulated total Numeric object Device address holding the totalizer
See run, stop or fault state Multi-state picture Status word in the controller

Label every point with its loop tag. ISA-5.1 assigns the tag letters: F for flow and T for temperature lead the loop, I adds indication, Q adds totalization. FT-101 is the field flow transmitter; the panel value beside its symbol is FI-101; the totalizer display is FQI-101; the temperature indication is TI-101. The minimum for every measured point is the value object with its tag; the graphic is strongly recommended; state graphics come last and only with a real status source.

Place the instrument graphic #

  1. Open the Picture Library: on the View tab, in the Toolbar section, enable Picture. The pane that opens lists the libraries available to the project.
  2. Browse for a symbol that reads as the instrument at panel size, and drag it onto the screen.
  3. If nothing fits, fetch the extra libraries from the Library section of Weintek's download pages and add them to the Picture Library; a library that arrives as an flb file goes through importing flb symbol libraries into EasyBuilder projects.
  4. To use your own artwork, export it in a format the editor imports and place it as a picture; transparent backgrounds avoid a white box on a colored screen, covered in importing HMI images with a transparent background.
  5. Position the graphic where its value will sit beside it, sized for the panel's real resolution and clear of navigation keys and other objects' tap targets.

Bind the live value #

  1. Drop a numeric object next to the graphic.
  2. In the object's address settings set Device, Device type and Address — the word-address fields the objects chapter of the manual documents, with System tag and Index register as further options. Device is the controller configured for the project; Address is the register or tag holding the measurement.
  3. Set the format's integer and decimal counts to match the register's unit: tenths of a degree need one decimal, hundredths of a flow unit need two.
  4. Label the pair with its loop tag and its engineering unit.
  5. Scale once, in exactly one place; the next section shows the numbers.
  6. Treat the panel value as indication only. Alarms and interlocks belong in the controller, never in the display.

Worked example: one flowmeter and one temperature sensor #

The first three cases assume the controller already publishes engineering units; only the raw-count case changes that.

  • TI-101, temperature: the controller holds tenths of a degree Celsius in a 16-bit register. Register 423 with a one-decimal format reads 423 × 0.1 °C = 42.3 °C. The HMI applies no conversion; the format places the decimal point.
  • FI-101, flow: the controller holds hundredths of a cubic metre per hour. Register 1250 with a two-decimal format reads 1250 × 0.01 = 12.50 m³/h.
  • FQI-101, total: the controller holds a 32-bit total in litres, 178934 L. Shown directly it reads 178934 L; converted, 178934 ÷ 1000 = 178.934 ≈ 178.9 m³. Show litres unless operators work in cubic metres; if you convert, divide by exactly 1000 and keep one decimal.
  • Raw counts: a 4–20 mA temperature input scaled 0–16000 counts for 0–100.0 °C reads 70.0 °C at 11200 counts: 11200 ÷ 16000 = 0.700, and 0.700 × 100.0 °C = 70.0 °C.

Decisions: when other consumers need engineering units — alarms, logging, other panels — do that multiplication in the PLC and let the HMI display the result. Do it in the numeric object only when the controller hands you raw counts. Never in both.

Give the symbol a state only when a register backs it #

A multi-state object swaps its picture when a word register changes, which is how a flowmeter should look running, stopped or faulted — the mechanics are in switching HMI images with an integer variable value. An animated impeller must be driven the same way, through an address, as an EasyBuilder Pro animation loop that needs an address-driven position. Animate only what the controller reports: a rotor that spins forever tells the operator nothing and hides a stopped flowmeter.

Where symbol artwork may come from #

Weintek's own picture and object libraries are vendor-distributed at no charge from its download pages, and they cover this job. A third-party symbol package that exports images is optional, not required: run it only with a valid license from its manufacturer or an authorized distributor, and record the origin of every imported image in the project documentation. No extra tool is needed to put a temperature or flow value on a Weintek panel.

When the graphic and the value misbehave separately #

  • The picture is missing or distorted: a picture-resource problem — wrong format, wrong size or lost transparency. Fix it in the picture resource; the device is not involved.
  • The picture is fine but no number appears: no numeric object exists at that spot, or its address was never set. Add the object and bind it.
  • The numeric object shows a fault or a frozen value: the device side — driver type, station address, cable, controller state. If reads died after a project upgrade, check that the project's driver matches the panel runtime, the failure behind EasyBuilder Pro V5 to V6 upgrades that leave the HMI showing no response.
  • The value moves but is the wrong number: wrong register, wrong data type or double scaling. Re-check the address and the interpretation before touching the artwork.

Artwork and data never fail for the same reason: test them separately and you save an hour.

Questions asked

Are Weintek's extra libraries free, and do they work with more than one editor?

Yes. The picture and object libraries in the Library section of Weintek's download pages are free, and the same downloads serve EasyBuilder Pro and EasyBuilder X. You add a downloaded library to the Picture Library once on that workstation, and every project you edit there can use it afterwards.

Can I reuse one flowmeter graphic for every flow point?

Yes. Place or copy the same library picture as many times as needed, then give each numeric object its own address and each pair its own loop tag, such as FI-102 and FI-103. Copy the graphic-and-value pair together and re-address the copy; after pasting, verify every address, because a duplicated object keeps the old binding until you change it.

The panel shows ten times the flow I expect. Did I import the picture wrong?

No. Artwork has no effect on numbers. A value that reads ten or a hundred times high means the measurement was scaled in the controller and again in the numeric object, or the format's decimal count does not match the register's unit, such as hundredths displayed as tenths. Remove one of the two conversions or match the decimal count, and the number lands where it should.

Should the totalizer be resettable from the panel?

Only if the controller owns the reset command and your operating procedure allows an operator to issue it. A reset writes to the controller, so treat it like any setpoint write: give it a confirmation step and an access level. If totals feed billing or batch records, keep the reset out of operator hands entirely and clear totals from the controlled side.

Where does the engineering unit go if the numeric object shows only digits?

Put it in a small static text immediately to the right of the value, or fold it into the tag label, so the pair reads FI-101 in m³/h and TI-101 in degrees Celsius. Keep the unit text with the pair when you copy it to other flow points, because a number without its unit invites the wrong decision at 2 a.m.

Keep reading

  • Troubleshooting

    HMI Text Runs Off the Screen After Downloading the Project

    The panel and the project are both fine: the engineering PC's Windows display scaling is above 100%, so the downloaded layout lands past the panel edge even though the editor and offline simulation look correct. Set the scale to 100%, restart the PC, then redownload.

    HMI and touchscreens

  • Troubleshooting

    HMI Function Key Does the Wrong Action: Find the Hidden Object

    When an HMI function key performs an action you never assigned, the assignment exists in the project. On the affected screen, ungroup the visible artwork, move the static bitmap aside and inspect the concealed pushbutton: it carries its own function-key number and screen-change action. The simulator is reproducing the project faithfully; remove or reassign the hidden object, then put navigation on the function bar on a non-touch panel.

    HMI and touchscreens

  • How-to

    Using a VNC Viewer object on an HMI to display other panels

    The VNC Viewer object is a VNC client, so a display-equipped host running the required OS can show any panel or PC that runs a VNC server, not just its own family. On cMT-series hosts the session appears only on the panel's own screen, never through the cMT Viewer app and never in online simulation. Use WebView for remote access.