Backing Up an M172 Controller and HMIST6400 Runtime Files

HMI and touchscreens Published 5 min read

Short answer

Yes. The M172 keeps its compiled application on the controller, and you can pull it with the engineering software, over FTP, or to a USB pendrive through a system function; the HMIST6400 saves its compiled project from the hardware menu. Neither file is editable source, and the HMI project runs only on the firmware tied to its EOTE version, so record that firmware with the backup.

On this page
  1. What the backup gives you
  2. Confirm the hardware before copying
  3. Back up the controller
  4. Back up the HMIST6400 terminal
  5. Firmware is the matched-set condition
  6. Prove the package before you need it
  7. The decision, unit by unit
  8. Questions asked

Yes on both units, and the backups will restart production after a failure — they just will not give you editable source. The M172 controller holds its compiled application files on the device, and you can extract them with the engineering software, over FTP, or to a USB pendrive through a system function. The HMIST6400 saves its compiled project from the terminal's hardware menu. The one condition that decides what the HMI copy is worth is firmware: the project needs the firmware tied to the EOTE version it was built with, and that firmware changes with every EOTE version. Save the project and its firmware as one matched set and prove the set on a spare, and a load-and-go recovery is covered.

What the backup gives you #

A compiled backup is a deployment artifact. It puts the same running program back on the same kind of hardware, which is exactly what disaster recovery needs, and it yields nothing editable: no screen changes, no tag changes, no logic changes. Those live in the engineering tool's source project on whichever PC built the application. If the source is already gone and future changes are the real worry, how to recover an HMI program when the source file is lost is the separate hunt; the compiled copy does not substitute for it. The split is not unique to HMIs — on drives, the same rule is why drive backups still require the saved engineering project rather than whatever can be pulled off the unit.

Confirm the hardware before copying #

Read the labels first. The M172 family carries TM172 order references, so extraction guidance written for TM172 is guidance for the controller labelled M172; confirm the exact reference on the label and in the software's connection view so you know the routes below apply. This family is engineered in SoMachine HVAC, which the vendor also uses for firmware updates and for application downloads over Ethernet, a USB cable, or a USB stick.

Reading Where it comes from Why it matters
Controller reference Product label and connection view Confirms the compiled-file routes apply
Terminal reference HMIST6400 label and hardware menu Defines what a replacement must be
Installed HMI firmware Terminal hardware menu The value the compiled project must match
EOTE version of the project Engineering records for the build Identifies the firmware generation the project needs

Back up the controller #

The compiled application sits on the controller, and the discipline is the same as how to back up a PLC program the right way: use the vendor's tooling, store a versioned copy, prove it loads.

  1. Connect with the engineering software and record the controller identity and system information it displays.
  2. Extract the compiled files by one of three routes: from the software, over FTP to the controller's file area, or to a USB pendrive through a system function. Choose the route you can repeat during a failure — software when the engineering PC and connection are controlled, FTP for a scriptable copy, USB as the path that needs no PC.
  3. Copy the complete compiled set with file names and directory structure unchanged; do not rename, edit, or selectively copy runtime files.
  4. If USB is your restore path, keep the CREDEN file with the set: the vendor's M172 procedures require it before the controller accepts an application loaded from a USB stick.
  5. Add the controller firmware to the package. It is published as a .bin file in the vendor site's firmware update section and loads from the same USB stick.
  6. Label the package with the controller reference, date, route used, and who ran it.

Back up the HMIST6400 terminal #

  1. Open the terminal's hardware menu and run the function that saves the compiled project.
  2. From the same menu, record the installed firmware version exactly as displayed.
  3. Record the EOTE version the project was built with, from the engineering records.
  4. Store the project file and the two version records together; they are one recovery unit, not three loose items.

The menu save yields the compiled project the terminal runs — the deployment copy, which is the right artifact for replacement and restart.

Firmware is the matched-set condition #

The practical warning from this platform: the project always needs the right firmware, and the required firmware moves with every EOTE version. A compiled project copied without its firmware context can refuse to start on a replacement terminal whose model number is correct.

So the backup is not the project file alone; it is the project plus the firmware revision plus the EOTE version, carried as one set. When the recorded firmware is not at hand, getting the right firmware file for a legacy HMI panel covers finding it through the vendor. Do not resolve a mismatch by trying firmware revisions at random on production hardware: put the recorded firmware on the spare, or use a spare that already carries it, and test. Preparing and testing the spare before any failure is the stronger strategy, because it converts compatibility from an assumption into a demonstrated result.

Prove the package before you need it #

For a line with two controllers and two terminals, the recovery package holds 2 × 1 controller sets + 2 × 3 terminal items (compiled project, firmware record, EOTE record) = 8 manifest entries.

Check completeness with numbers, using one controller set pulled by FTP as an illustrative example: the controller's file listing shows 3 files totalling 1,246,080 bytes; the workstation copy also totals 1,246,080 bytes; 1,246,080 − 1,246,080 = 0 bytes of difference, and matching checksums confirm the copy. A manifest count of 8 of 8 entries then says the package is complete.

Complete is not the same as working. Bench-load the controller set, and load the HMI project on a spare terminal carrying the recorded firmware, then confirm screens and live values before you call any of it a backup. Keep that proof off the running line: a download that fails halfway can leave a controller without its application.

The decision, unit by unit #

  • The two M172 controllers: back them up from the compiled files on the device, plus the firmware .bin. This meets the load-and-go requirement.
  • The two HMIST6400 terminals: save the compiled project from the hardware menu and record the firmware and EOTE version with it. Yes, workable, as a matched set.
  • Editable source: not obtainable from either artifact. Treat these copies as the disaster-recovery floor, and recover or rebuild the source projects as a separate effort.
  • Spares: prepare one terminal with the recorded firmware now; after the failure is too late to discover a mismatch.

Questions asked

Can I edit the screens later from the saved HMIST6400 compiled project?

No. The hardware-menu save produces the deployment copy the terminal runs; edits require the source project in the HMI engineering tool on the PC that built it. Keep both if the source turns up. If it is gone, treat the compiled copy as the recovery artifact and plan the rebuild as its own project.

Which controller extraction route should I use first?

Use the engineering software when the workstation and its connection are in hand, because it also shows the controller identity and system information you need on the record. Use FTP when you want a repeatable copy without the engineering tool. Keep the USB pendrive route, which runs through a system function, as the fallback that needs no PC, and keep the CREDEN file with that set.

Do I need the CREDEN file in the backup package?

Yes, if loading from a USB stick is the controller restore path you plan to use. The M172 procedures require that credentials file before the controller accepts an application from USB storage. Store it with the recovery set and control who can reach it, because it exists to govern what loads into the controller.

The spare terminal has newer firmware than the recorded one. Which do I load?

Match the recorded firmware first. The project is proven against the firmware tied to its EOTE version, so bringing the spare to that revision reproduces the working combination. If you need newer firmware, do it later as a separate change with the project reloaded and retested, never during the recovery.

How often should these backups be refreshed?

After every accepted program change on either unit, and at least once a year even when nothing changed, because media and records age. Each refresh re-records the terminal firmware and the EOTE version, since a silent engineering-tool upgrade is the usual way a project and its recorded firmware drift apart.

Keep reading

  • Troubleshooting

    Why an Uploaded HMI Copy Is Not an Editable Project

    Use an HMI runtime backup to restore device data. To edit the project, recover the original engineering files or use the vendor's source-upload function if the source was saved to the panel. If you have only the runtime backup, keep it for restore and plan a rebuild.

    HMI and touchscreens

  • Troubleshooting

    Why FactoryTalk View Studio Cannot Save the Tag Database

    Build a small test project first. If it creates a runtime, the workstation is fine and the fault is in your application — most often a parameter-file name whose extra space does not match its GoToScreen button assignment, because saving a display never validates that reference. If every project fails, check the real project path for a OneDrive-redirected Documents folder, then write access, roll-up patches, a full shutdown, and finally a FactoryTalk Linx or RSLinx reinstall.

    HMI and touchscreens

  • Troubleshooting

    OP15 project recovery: ComText, ProTool or ProSave

    Recovering a project from a Siemens OP15 starts with the panel's generation, not software preference. First-generation OP5 and OP15 hardware belongs to ComText, second-generation hardware belongs to ProTool, and firmware version 2.2 draws the line. ProSave is not in the decision: it writes a backup image, not an editable project, and the OP15 is not on its supported-device list.

    HMI and touchscreens