Selection guide
Building Tablet and Phone Supervision From a SoMachine Basic Program
Short answer
Yes — Vijeo Designer is the engineering tool that builds the HMI project linking your SoMachine Basic ladder data, and Vijeo Design'Air is the app each tablet or phone runs to view that project. Buy one Vijeo Designer single license from Schneider Electric or an authorized distributor; the app builds nothing on its own, and the HMI target that serves it is chosen against the documented release notes.
On this page
- Is Vijeo Designer the solution for sharing supervision on tablets and phones?
- What do I need to buy for this setup?
- Which checks come before paying for the license?
- Where does a licensed Vijeo Designer installer come from?
- How does the HMI project read the SoMachine Basic program's data?
- How do the tablets and smartphones connect to the HMI?
- Can the mobile app replace the machine's operator panel?
- How do I verify the whole supervision chain before commissioning?
- Questions asked
Your SoMachine Basic ladder program already runs the machine; it holds no supervision layer and puts nothing on a tablet or phone. That takes two Schneider Electric products with separate jobs: Vijeo Designer, the paid engineering tool that builds the HMI project and maps controller data into it, and Vijeo Design'Air, the app each mobile device runs to view that project. This article picks the pair, sizes the licensing, and lists the checks to make before and after the purchase.
Is Vijeo Designer the solution for sharing supervision on tablets and phones? #
Yes, plus one more piece: Vijeo Designer builds the HMI project that maps your controller data, and Vijeo Design'Air is the app a tablet or phone runs to view that project — neither SoMachine Basic nor the app alone produces operator screens. The work divides like this:
| Piece | What it does | Where it runs | How you get it |
|---|---|---|---|
| SoMachine Basic | Your existing ladder logic; no operator screens | Engineering PC | Already installed on your PC |
| Vijeo Designer | Builds the HMI project: screens, tags mapped to controller addresses, alarms, user levels | Engineering PC | Paid single license from Schneider Electric or an authorized distributor |
| HMI target | Runs the published project and holds the connection to the controller | At the machine | Part of the design; pick from the documented target list |
| Vijeo Design'Air | Client that views the running project | Each tablet and smartphone | App store; Google Play carries the Android app |
The app is a viewer, not a builder. With no published project to connect to it has nothing to display, so the engineering license comes first and the app last.
What do I need to buy for this setup? #
One Vijeo Designer single license covers the engineering side whatever the number of mobile devices, because every tablet and phone views the same published HMI target. Worked example — a packaging line that wants supervision on three tablets and two smartphones, with one HMI terminal at the machine:
- Devices: 3 tablets + 2 smartphones = 5 app installations.
- Engineering: 1 single license on 1 engineering PC, reference VJDSNDTGSV62M for version 6.2; a 6.3 single license is listed alongside it.
- Terminal path: 1 license + 0 extra for the installations = 1 software license.
- PC-hosted path: the screens run on a PC at the machine instead, adding the Vijeo Designer Runtime single license: 1 + 1 = 2 software licenses.
A single license lives on one engineering PC at a time. If the PC-hosted path is the plan, the runtime can sit on a touchscreen computer at the machine, and industrial panel PCs are the hardware class for that.
Which checks come before paying for the license? #
Three gates: the HMI target family you plan to use must appear on the mobile-access list in the documentation for the release you buy, the driver must cover the controller your SoMachine Basic program runs on, and the engineering PC must meet that release's stated prerequisites.
- Record the controller reference and the SoMachine Basic project version first; both come out of the project properties before you contact anyone.
- Ask the distributor to name in writing the HMI target family and the software release that serve the mobile option, and read the manufacturer's product documentation for the same answer.
- Match the engineering PC's operating system against the release notes before the installer arrives.
Order nothing until the target and the release are named in writing in both places.
Where does a licensed Vijeo Designer installer come from? #
From Schneider Electric or one of its authorized distributors — the full engineering product is paid software sold as a single license, and that channel supplies the installer and the activation together. The manufacturer's product pages list the 6.2 and 6.3 single-license products under those references.
Take installers only from the manufacturer or the distributor. The same rule covers the smaller Basic variant of the tool: getting Vijeo Designer Basic 1.1 from the official source shows the pattern. An installer from anywhere else is an unverifiable binary on a PC that will sit next to a production controller.
How does the HMI project read the SoMachine Basic program's data? #
Through a driver: in the project you create an equipment entry for the controller, set its communication parameters to match the controller port, and build tags that point at the addresses your ladder program already uses.
- List what the operator needs — process values, setpoints, command bits, alarm states — each with the fixed address it already carries in the ladder program.
- Create the equipment for the controller and match the communication parameters on both sides: protocol, station address or IP, and for a serial link the baud rate and format.
- Build tags on those addresses, then one test screen with a single numeric display and a single button.
- Verify online: the displayed number matches the value in SoMachine Basic's online view, and a written setpoint appears there without the logic overwriting it.
If the controller link is serial, building the RS-232 Modbus cable between an HMI and a controller covers that wiring. For the screens-and-tags side generally, what HMI programming covers from screens to controller tags walks the same ground.
Give command bits to the ladder program, not to the HMI: the button sets, the logic clears under its own interlocks, so two writers never fight over one bit.
How do the tablets and smartphones connect to the HMI? #
Install Vijeo Design'Air on each device — Google Play is the documented Android source — and point it at the published HMI target on the same network segment first; routing across subnets or the internet comes after the local test passes.
- Enable the mobile-access option in the project as the documentation for your exact target describes; that setting lives with the target's properties in the engineering tool.
- Put the device and the target on one network segment and enter the target address in the app.
- The gate is simple: the test screen from the previous section appears on the device.
- Before commissioning, set user accounts and access levels so a view-only mobile user cannot reach start/stop or setpoints.
Treat the path to the machine like any control network: segment it, and authenticate every user who can write.
Can the mobile app replace the machine's operator panel? #
No — keep at least one station at the machine: the app depends on the network, the battery and the published target being alive, so phones and tablets are an added view layer, not the primary interface. The operator who clears a jam needs a screen that survives a dropped Wi-Fi link. Emergency stop and safety functions stay in hardwired or safety-rated devices, never on a phone screen.
If the local panel itself is the question on an existing machine, replacing a local HMI with a phone app on a PLC covers that trade.
How do I verify the whole supervision chain before commissioning? #
Four tests on the live system: a changed controller value must appear on both the HMI and the tablet, a tablet setpoint must land in the controller register, a view-only login must be rejected on write, and a pulled cable must show a communication fault rather than frozen values.
- Change a value at the controller and confirm it on the HMI screen and on the tablet.
- Send a setpoint from the tablet as an authorized user and confirm the controller register changes.
- Log in as a view-only user and confirm the write is rejected.
- Pull the network cable at the HMI, confirm a communication fault rather than frozen values, restore it and confirm recovery without a restart.
Commission only when all four pass, and repeat them after any change to the project or the target.
Questions asked
Can I move the Vijeo Designer license to another engineering PC later?
Yes. The license is single — one engineering PC at a time — and the documented transfer runs through the Vijeo Designer License Manager tool with a USB flash drive: release it on the old PC, then activate it on the new one. Plan the move outside commissioning windows so the project is never without its engineering station.
Is there an evaluation mode before we buy the license?
Yes, documented ones. The installer offers Demo, Trial and Limited Edition modes for evaluation; what each mode allows and for how long comes from Schneider Electric's current terms, so check them before scheduling real work on a trial. Full, unrestricted engineering needs the activated single license.
What is HMI License Manager V2?
It is the newer license-management tool, shipped with Vijeo Designer V6.3 SP3. If your engineering PC runs that release, use the manager its installer provides rather than an older copy, and follow the transfer procedure documented for that exact version.
What if the target I want is not on the mobile-access list?
Change the target or the release before you buy. The documentation for each Vijeo Designer release lists which targets support the mobile-access option, and a target outside that list cannot serve the app today. Waiting for a later update to add a target is not a plan; pick a pairing that is already listed.