Connecting a Siemens CPU315 to a Pro-face HMI over MPI RS-485

HMI and touchscreens Published 6 min read

Short answer

The CPU315's MPI socket is an RS-485 multi-point interface, so standard PROFIBUS Type A cable and quick connectors are the right link: data A on pin 8, data B on pin 3, termination on at both ends. Keep the CPU at its default MPI address 2 and 187.5 kbit/s, run GP-Pro EX's SIMATIC S7 MPI Direct driver, and point its PLC station at the CPU.

On this page
  1. Is the CPU315 MPI port actually RS-485?
  2. Which cable and connectors join the two ports?
  3. Where do the bus terminators go on the link?
  4. What do you change on the CPU315 before plugging in?
  5. How do you set the SIMATIC S7 MPI Direct driver in GP-Pro EX?
  6. Example: what does an S7-200 at 19.2 kbit/s cost the rest of the line?
  7. How do you prove the link before trusting the screens?
  8. Questions asked

Wire the CPU315's MPI port to the Pro-face panel with standard PROFIBUS Type A cable and quick connectors. That port is an RS-485 multi-point interface with the PROFIBUS pin map — data A on pin 8, data B on pin 3 — so the cable meant for PROFIBUS is the correct link even though no DP traffic runs on it. On the protocol side, run GP-Pro EX's SIMATIC S7 MPI Direct driver at the default 187.5 kbit/s and point it at the CPU's default MPI address 2. No custom cable and no PLC logic are required: the panel reads data through the CPU's standard communication connections once the station numbers and the rate line up. Below are the wiring, the settings on both sides, what an S7-200 on the same line costs in speed, and the checks that prove the link.

Is the CPU315 MPI port actually RS-485? #

Yes — every S7-300 CPU carries an RS-485 MPI interface on a 9-pin D-sub socket, and at the default rate the physical layer is identical to PROFIBUS, so standard PROFIBUS cable and connectors are the correct wire even though no DP telegram runs on it. Multi Point Interface means several stations — CPUs, programming devices, operator panels — share one cable on a token-passing basis, and the CPU ships with the port as standard.

What differs from a DP network is the protocol on the wire: MPI carries the S7 traffic that programming devices and operator panels use, and the Pro-face unit joins it as one more station. A programming PC can sit on the same port at the same time; the adapter wiring for that case is in connecting an HMI panel to an S7-300 MPI port with a PG.

Which cable and connectors join the two ports? #

Use PROFIBUS Type A cable (Siemens 6XV1830-0EH10) and a pair of PROFIBUS quick connectors (6GK1500-0FC10); the connector crimps onto the cable in seconds and its 9-pin plug goes straight into the CPU's MPI socket. The Siemens connector documentation keeps one wiring rule: connection A always goes on the green core, connection B always on the red.

Connection CPU315 MPI socket Type A core Pro-face side
Data A pin 8 green A (data +)
Data B pin 3 red B (data −)
Termination supply supply contact on the Siemens connector — never connect

The Pro-face side is where pin numbers stop being universal: serial pin assignments vary between HMI models, and some units bring RS-485 out on screw terminals instead of a 9-pin socket. Match by signal name from the model's connection drawing — green to A, red to B. One caution: the termination-supply contact on the Siemens connector feeds only Siemens' own active bus terminator; never land it on the panel.

  1. Crimp a 6GK1500-0FC10 onto each cable end, green core to A, red core to B.
  2. Plug one connector into the CPU315's MPI socket.
  3. At the panel, plug the second connector into its RS-485 port where the model's drawing matches the PROFIBUS pin map; on terminal-block models, land the two cores on the A and B terminals instead.
  4. Slide both termination switches ON for this two-node link.

Switch termination on at both ends of a two-node link: each quick connector carries a built-in terminator, so on a CPU315-to-panel run both switches sit ON, and only a longer multidrop drops the middle nodes to OFF. On a multidrop, the two devices at the physical ends of the cable terminate; everything between them does not.

Repeaters extend the run when needed: up to 9 RS-485 repeaters can sit in series, and each one counts as a node of the MPI subnet. A quick meter check catches most wiring faults before power-up — with both ends terminated, the A-to-B resistance reads about 110 Ω, and the measurement procedure with the meaning of each wrong reading is in how to check PROFIBUS termination when an HMI reads no data.

What do you change on the CPU315 before plugging in? #

Usually nothing: MPI address 2 at 187.5 kbit/s is the CPU's factory setting and exactly what the driver expects, so the job is to confirm both values in the hardware configuration and download it once to the CPU. Open the CPU's properties, go to the MPI interface page, and verify the station number and the rate; leave operator and programming communication enabled on that interface, then compile and download.

Two decisions go with this. If the project forces the CPU onto another station number, change it here, download, and mirror the new number in the panel driver. On a CPU315-2 DP, keep the HMI on the MPI interface and reserve the DP port for I/O and drives.

How do you set the SIMATIC S7 MPI Direct driver in GP-Pro EX? #

Open the project's device/PLC settings in GP-Pro EX, add the Siemens SIMATIC S7-300/400 series, select the SIMATIC S7 MPI Direct driver, keep its default line "MPI (1)... 187.5Kbps", and point the PLC station at 2. Everything else in the driver dialog stays at its defaults.

  1. In GP-Pro EX, open the project's device/PLC settings page.
  2. Add the manufacturer Siemens AG and the series SIMATIC S7-300/400.
  3. Select the SIMATIC S7 MPI Direct driver.
  4. Leave the rate at the driver default and set the PLC station number to the CPU's address.
  5. Transfer the project to the panel.

Example: what does an S7-200 at 19.2 kbit/s cost the rest of the line? #

If an S7-200 must share the subnet, the whole line drops to 19.2 kbit/s, and every telegram on it stretches 187.5 ÷ 19.2 = 9.77 — roughly ten times slower for the Pro-face panel. The CPU's MPI interface documents only two rates: the typical default and this slower one for S7-200 communication.

  • Rate ratio: 187.5 kbit/s ÷ 19.2 kbit/s = 9.77.
  • One bit at the default rate: 1 s ÷ 187,500 = 5.33 µs.
  • One bit with the S7-200 present: 1 s ÷ 19,200 = 52.1 µs.
  • Cross-check: 52.1 µs ÷ 5.33 µs = 9.77, matching the rate ratio.

Decision: keep a CPU315-to-panel link at the default rate, because the interface offers no third choice and 19.2 kbit/s taxes every node on the cable. If an S7-200 is unavoidable on the same line, expect screen updates about ten times slower and move the heaviest screens to another path; when a serial HMI does lag, the serial-side causes are covered in why an HMI freezes or updates slowly over serial.

Power down, measure about 110 Ω across A and B at either end, power up, then watch one value move in both directions — those checks prove the link before any screen goes live. The resistance reading settles the wiring before any software is touched.

  1. With the cable unpowered, a meter across A and B reads about 110 Ω; a far higher reading means one termination switch is off, and a near-zero reading means the two cores are shorted.
  2. Power up and confirm no bus-fault LED stays lit on the CPU.
  3. Create a small data block in the CPU with a few words and no logic; the panel reads it through the CPU's standard communication connections.
  4. Map a numeric display and a numeric input on a test screen to the block's first word, write a value from the panel, and confirm it in the CPU's monitor table.
  5. Modify the value at the CPU and confirm the screen follows.
  6. If nothing moves, check the three usual causes: the driver's station number against the CPU's, one identical rate at both ends, and the green core on A at both connectors.

Questions asked

Can two Pro-face panels share one CPU315 MPI port?

Yes. The S7-300/400 series supports the n:m connection, so several panels and CPUs can share one MPI subnet. Give every node its own station number, leave the CPU on its factory one, and switch termination on only at the two physical ends of the cable run. A repeater in the line also counts as one of the subnet's nodes.

Can the same cable run PROFIBUS DP instead of MPI?

Yes. MPI and PROFIBUS share the RS-485 physical layer and the same two data contacts on the 9-pin connector, so one Type A cable and the same quick connectors serve both. What changes is the CPU interface, the rate and the HMI driver: a DP connection uses the CPU's DP port and the PROFIBUS driver in GP-Pro EX instead of the MPI Direct one.

The panel shows no data after the first download, so what is wrong?

Almost always one of three things: a termination switch left off, a driver station number that does not match the CPU's 2, or two ends running different rates. Measure about 110 Ω across A and B, confirm both ends sit at the default rate, and check that the green core lands on A at both connectors.

Do you need an RS-485 repeater between the CPU315 and the panel?

No. A short two-node run needs only the termination built into the quick connectors. Add repeaters when the run must reach across cabinets or a segment needs isolation; up to nine can sit in series, and each one counts as a node of the MPI subnet when you budget the line.

Keep reading

  • Troubleshooting

    Connecting a Pro-face HMI to a Q02HCPU Over RS-232

    A Pro-face HMI and a Mitsubishi Q02HCPU communicate over RS-232 only when four things match: the Q-series driver in the HMI project, the exact port used (CPU or module), the cable wiring from both manuals, and identical serial settings on both ends. Verify all four from the documentation before changing any configuration.

    HMI and touchscreens

  • How-to

    Connecting an HMI panel to an S7-300 MPI port with a PG

    Yes: wire the panel's RS-485 port to the CPU's MPI/DP port and run the Siemens S7 MPI driver, with no communication module. Put a PROFIBUS connector with a PG socket on that port, hang the PC adapter on the socket, give every node a unique address and one common baud rate, and STEP 7 stays online while the panel runs.

    HMI and touchscreens

  • How-to

    Connecting One HMI Panel to Two PLCs Over Serial

    Yes. A two-port panel — one RS-232-only port, one selectable RS-232/RS-485 port — runs two PLCs: one point-to-point link per port, or both PLCs as separately addressed slaves on the single RS-485 bus. Give each link its own cable, driver and matching serial settings, and prove one link before configuring the next.