Explainer
Feasibility of connecting an Omron NS5 HMI to a Modicon PLC
Short answer
Yes, the link is feasible without Vijeo Designer. The NS5 has no Schneider-named driver, but the Modbus entries under its serial Generic Protocol can poll a Modicon PLC configured as a Modbus server; match roles, framing, speed, parity, station address and cable, and prove it read-only before buying a replacement panel.
On this page
- Why a missing Schneider driver is not the blocker
- What the Modicon side has to supply
- The settings that decide the first exchange
- Worked example: wire time for one 10-register read at 19200 baud, 8-E-1
- Cable and electrical interface
- Commission read-only, then earn the writes
- If the check fails, what to change instead
- Questions asked
Yes, the link is feasible, and you do not need Vijeo Designer or a Schneider-named driver to make it. The NS5 host list has no Modicon entry, but the Generic Protocol choice in the serial port dialog exposes Modbus entries, and Modbus is what a Modicon PLC serves on its serial ports. Configure the panel as the Modbus client, configure the Modicon port as the Modbus server, and line up transmission mode, speed, parity, station address and cable. Nothing has to be bought to find out: the panel and its engineering software are already on site, so the reuse case deserves one afternoon of verification before any replacement panel is quoted.
Why a missing Schneider driver is not the blocker #
The NS-series host connection manual documents a Generic Protocol setting for the serial port, and its condition is that the connected equipment conforms to the Modbus serial line protocol - the manufacturer's name never enters that condition. The absence of a Modicon entry in the host list only means no driver ships with Modicon-specific conventions baked in. The Modbus entries that appear under Generic Protocol in the serial port dialog, and again in the Serial B drop-down when you add a second host, are what decide the question.
Role comes first among those decisions. In a polling link the panel initiates every request and the PLC answers: in Modbus terms the NS5 is the client and the Modicon is the server, the pairing older documentation calls master and slave. Two devices both set to initiate exchange nothing, and two responders wait in silence, so this one setting decides more than the driver name does.
On a Schneider panel the equivalent step is adding a Modbus RTU driver and external variables in Vijeo Designer; on the NS5 you select the Modbus entry under Generic Protocol instead. The shape of the work is identical: pick the protocol, set the serial parameters, point the panel at the PLC's station address.
What the Modicon side has to supply #
Identify the exact CPU and any communications module from the nameplate and the existing project, and confirm which port is free. A port already serving another master is not available, and reassigning it is a change to a running machine, so save the current PLC project and its communication settings before touching anything.
The chosen port must be configured as a Modbus server at a known station address; that setting lives in the PLC's port configuration, not in the panel, and it is the one PLC-side change this project needs.
If the only free interface on the Modicon is Ethernet, none of the serial work above applies. The job becomes what you must configure on the PLC side for Modbus TCP, a separate set of settings that has to be verified on its own before any panel is chosen for that path.
The settings that decide the first exchange #
Modbus serial devices run one of two transmission modes, RTU or ASCII, and the protocol guides state the rest plainly: the baud rate, parity and stop bits must be set so all devices on the line share the same values. Everything the first exchange depends on fits in one table.
| What must match | Where the setting lives | Pass condition |
|---|---|---|
| Transmission mode | Generic Protocol entry and PLC port setup | RTU at both ends, or ASCII at both ends |
| Role | Panel host setup and PLC port setup | NS5 initiates, Modicon answers |
| Speed, parity, data bits, stop bits | Serial settings on both ports | Identical values |
| Station address | PLC server address, panel host entry | Panel targets the address (1 to 247) the PLC occupies |
| Data coverage | PLC memory map, driver address formats | Every tag needed is readable; writes only where intended |
A shared protocol name satisfies none of these rows on its own, which is why the feasibility answer is yes once verified, not yes on the strength of a name.
Worked example: wire time for one 10-register read at 19200 baud, 8-E-1 #
The question behind "is it feasible" on a running machine is usually whether the link is fast enough, so size the wire before believing any refresh number.
Inputs:
- Line speed: 19200 bit/s. The Modbus over Serial Line specification published by Modbus Organization in 2006 names 9600 and 19200 as the speeds serial devices must accept, so 19200 is a defensible planning number until the actual port is read.
- Character frame: 11 bits - 1 start, 8 data, 1 even parity, 1 stop - the RTU layout in the same specification.
- Transaction: the read-holding-registers service, request frame 8 bytes and response frame 5 bytes plus 2 bytes per register, per the Modbus application protocol layout.
- Registers per poll: 10, an illustrative input for a typical first tag block, not a measured value from any machine.
- Update requirement: 1 s, an illustrative target for an operator screen.
- Frame separation: a silent interval of at least 3.5 character times after the request and again after the response.
Rule in words: wire time per cycle equals request bits plus response bits divided by line speed, plus two silent intervals, with bytes converted to bits at 11 bits per byte.
Arithmetic:
- Request: 8 B x 11 bit/B = 88 bit, and 88 bit / 19200 bit/s = 4.58 ms
- Response: (5 + 2 x 10) B = 25 B, 25 x 11 bit/B = 275 bit, and 275 / 19200 = 14.32 ms
- One silent interval: 3.5 x 11 bit = 38.5 bit, and 38.5 / 19200 = 2.01 ms, so two of them = 4.01 ms
- Cycle: 4.58 ms + 14.32 ms + 4.01 ms = 22.9 ms, a wire ceiling of 1000 / 22.9 = about 43 transactions per second
One 10-register poll therefore costs about 23 ms of wire time at those settings. Against the 1 s example target, the budget holds up to about 40 such blocks (40 x 22.9 ms = 916 ms); above roughly 40 blocks per second the line itself is the limit, so raise both port speeds or poll fewer registers per cycle. Above 19200 baud the specification fixes the silent interval at 1.75 ms, so faster ports shrink the frames but not the gaps.
The 22.9 ms is the wire's minimum only. The Modicon's measured response delay, the panel driver's poll scheduling, a retry after a failed CRC check and the screen's own refresh all add time on top, so confirm the real cycle with a counter in the PLC that the panel displays, and timestamps on the changes, before blaming the serial line.
Cable and electrical interface #
Wire to the pinouts printed in both port manuals. One panel on one PLC port is a point-to-point RS-232 link built to those two drawings; a port that already sits on a multidropped network takes that network's documented two-wire RS-485 termination and biasing instead, and resistors added because communication failed usually make things worse.
Never pick straight-through or crossed by connector shape. Where the two ports are different electrical interfaces, the fix is the appropriate converter, not a new pin assignment, and the converter's settings join the matching table above. Check the finished lead for continuity and unintended shorts against the wiring schedule before either end is connected.
Commission read-only, then earn the writes #
Build one host and one numeric object on a single known PLC value you can watch in the PLC programming software, with operator writes disabled. A plausible number on screen proves nothing by itself: change the value at the PLC and confirm the panel follows, which separates a valid response from the last retained value.
A working link that shows the wrong figure is a mapping problem, not a wiring problem. Check whether the driver wants a zero-based offset where you typed the register reference, confirm the memory area, and for 32-bit data check signedness and word order - the same reference-versus-offset trap that comes up when fixing Modbus TCP addressing errors between an HMI and a PLC.
Expand the tag list in small groups while watching the communication status. Turn writes on last, after the PLC-side permissions and interlocks are reviewed, and prove the first writes on the bench or against spare outputs; never learn a write fault on a machine that can move.
If the check fails, what to change instead #
Run the NS5 test first. The panel and its engineering software are already on site, so verification costs an afternoon and no purchase, and its result tells you what to buy, if anything. The NQ route is the same test one step earlier in the buying process: the NQ engineering tool can be downloaded, so confirm its driver list offers the same match against your Modicon port before any NQ5 or NQ3 is ordered. Nothing here proves an NQ variant compatible - the check does.
If the Modicon port cannot be made to serve what the NS5 speaks, change the architecture rather than hunting for another cable: choosing a PC-based HMI runtime for a Modbus TCP PLC settles the software side, and industrial panel PCs put that runtime at the machine instead of a second proprietary terminal and a second engineering package.
Questions asked
Do I need Vijeo Designer on the Modicon side for this to work?
No. Vijeo Designer engineers Schneider operator panels, and you are configuring an Omron panel with the Omron software you already hold. The Modicon only has to serve Modbus on one serial port, which is PLC port configuration, not HMI software. Vijeo Designer enters the job only if you decide to buy a Schneider panel to replace the NS5.
Would an NQ5 or NQ3 be a safer choice than the NS5?
Not proven, and not cheaper to find out. The NQ engineering tool can be downloaded, so open it and confirm its driver list offers the same match against your Modicon port before any hardware is ordered. Until that check passes, the NS5 already in stores is the better first attempt, because the verification work is identical either way.
What cable does the NS5 to Modicon link need?
There is no universal part number: wire to the pinouts in both port manuals. For one panel on one PLC port, a point-to-point RS-232 lead built to those two drawings is the normal answer. On an existing RS-485 multidrop, follow that network's documented termination and biasing rather than inventing a second scheme. Do not choose straight versus crossed by connector shape.
The connection is up but the displayed value is wrong - is the driver faulty?
Usually not. A valid response carrying the wrong number points at mapping: the driver may expect a zero-based offset where you entered a register reference, the memory area may differ, or signedness and 32-bit word order may be interpreted differently at each end. Change a test value at the PLC and watch whether the panel follows before touching wiring.
Can the panel's Ethernet port reach the Modicon instead?
Only if the panel's project offers an Ethernet driver your Modicon port actually answers, and that is a separate check from the serial one. The Generic Protocol Modbus entries discussed here are serial. If Ethernet is the only free interface on the PLC, plan the Modbus TCP side as its own task before choosing hardware for it.