Troubleshooting
Fix WinCC HResult 0x8004610a when a project will not open
Short answer
Restore the Windows user rights the station had before the failures: in a documented WinCC V6.0 SP2 case, an IT rights change produced 0x8004610a on one project and 0x80046127 on another, and rolling the rights back cleared both. Check the read-only attribute on the project database when files came from CD, and the mcp.ini network entries for the vendor-documented network-card cause, before suspecting a damaged database.
On this page
WinCC is telling you the project database is unreadable, and in the resolved V6.0 SP2 case it was not: an IT change to the station's Windows user rights produced HResult 0x8004610a on one project and 0x80046127 on another, and restoring the previous rights opened both with no database repair. Work the station before the project: confirm what changed on the computer, roll back the rights, then check the read-only attribute on the database file and the entries in mcp.ini. Treat "damaged database" as the last conclusion, not the first.
What the two codes showed on one station #
Both codes came from a single WinCC V6.0 SP2 computer that had been running normally. The runtime was stopped, a second project was selected, and the open failed with HResult 0x8004610a; reopening the original project then failed with 0x80046127. The same first code has been seen with a follow-on dialog reporting that the .MCP file could not be loaded, which is how the failure presents on screen.
| Code | Seen when | Cleared by |
|---|---|---|
| 0x8004610a | Opening the second project after stopping the runtime | Restoring the previous user rights |
| 0x80046127 | Reopening the original project | The same rights rollback |
Two different projects failing at the same step is station evidence, not project evidence. A damaged database explains one project; it does not explain why the untouched original project stopped opening in the same session.
Restore the user rights first #
- Establish the change. Ask what was altered in the station's Windows accounts, groups or folder rights, and when. In the confirmed case the change came from plant IT, and the rollback target was the configuration that existed while both projects opened correctly.
- Roll the whole configuration back. The case record does not name the individual permissions or groups involved, so restore the known-good set as it was rather than guessing single settings.
- Test both projects. Open the project that reported 0x8004610a, then the original that reported 0x80046127. Both opening without their HResult messages confirms the diagnosis.
- Record the working rights set so the next IT change has a defined rollback point.
Windows-account changes trip WinCC on newer versions too: when WinCC 7.5 runtime fails under a new Windows user, the repair again sits at the Windows account layer rather than in the project.
Check order when rights were not changed #
Work this list in order once you have ruled the rights change out; every step maps to a documented or reported cause for 0x8004610a.
- Read-only attribute on the database file. A reported case copied a project to CD and back to the hard disk; the database file stayed write-protected from the optical copy, and clearing the attribute let the project open. Check the file's properties whenever the project arrived through a CD, a DVD or any read-only medium.
- Network card and mcp.ini. The vendor's HResult documentation for WinCC V8.x, V7.x and V6.x attributes 0x8004610a to WinCC not finding a network card, and the documented action is to open the mcp.ini file and delete the entries so WinCC rebuilds them.
- File availability and access. The same documentation lists, under its first option for this code, files that are not available, damaged, invalid or cannot be accessed: confirm the project folder sits on a mounted volume and that the account running WinCC can open the files.
- Computer name inside the project. A reported V6.0 fix changed the computer name in the project's Computer properties to the current station name, after which the project opened.
- Database attach state. A reported fix for 0x8004610a:(null) ran sqltool.exe and detached all WinCC databases on the machine, which cleared the error there; back up the project before using it.
Opening the .mcp through SIMATIC Shell on a client PC instead of on the server is a separate failure path — the WinCC server-client configuration that resolves HRESULT 0x8004610a is its own diagnosis. If the whole list fails, the project files themselves become the suspect: work the HMI project recovery and backup sequence before anything rewrites the database.
Worked isolation: two projects, two codes, one rights change #
Inputs, each from the confirmed case:
- Station: 1 WinCC V6.0 SP2 computer that had opened both projects normally.
- Projects failing at open: 2 — the alternate project and the original.
- Distinct HResult codes observed: 2 — 0x8004610a and 0x80046127.
- Station-level changes between the last good open and the first failure: 1 — the Windows user-rights change made by plant IT.
- Database repairs performed during the entire case: 0.
Rule in words: when every project on one station fails at the same open step and exactly one station-level change separates working from failing behavior, the fault lives in the layer that change touched. Independent per-project faults would need one cause per project and no shared trigger.
The arithmetic:
- Projects failing before the change: 0 of 2.
- Projects failing after the change: 2 of 2.
- Rollbacks applied: 1.
- Projects opening after the rollback: 2 of 2.
- Databases repaired: 0 of 2.
One change predicts every failure and one rollback clears every failure, with zero database work in between.
Decision: at two or more projects failing at open on one station, stop troubleshooting the projects and troubleshoot the station; if rolling back the last station change restores every project, the databases were never damaged. With only one project failing, a per-project cause is back on the table and the read-only attribute and file-access checks lead the list.
What not to do #
- Do not copy a default runtime database from the WinCC system directory over the project's runtime database. That step was suggested in the case discussion but never confirmed, names no validated file set, and overwrites runtime data. Back up the entire project folder before any step that touches the database — that copy is the recovery point.
- Do not guess individual permission settings the record does not name; restore the known-good configuration as a whole.
- Do not close the case on "damaged database" while two projects fail on one station.
Questions asked
Does HResult 0x8004610a always mean the project database is damaged?
No. The vendor's HResult documentation for V6.x through V8.x lists files that are not available, damaged, invalid or cannot be accessed, and separately a missing network card traced through the mcp.ini entries. In the confirmed V6.0 SP2 case two projects threw 0x8004610a and 0x80046127, and both opened after a user-rights rollback with zero database repairs.
Is a reboot enough to clear the error?
A reboot was proposed in the original case and did not clear it; the station kept failing until the previous user rights were restored. Use a reboot only to rule out a process holding the database open, and judge it by whether the same project then opens.
What causes 0x80046127, the code on the original project?
In the confirmed case it appeared on the original project after the same rights change and cleared with the same rollback, so treat it first as a second symptom of the station fault. If it survives the rollback and the attribute check, the causes summarized here do not cover it, so take the full case history to Siemens support rather than replacing the database.
What does detaching databases with sqltool.exe achieve?
One reported fix ran sqltool.exe on the affected machine and detached all WinCC databases, which cleared 0x8004610a:(null) there so the next open attaches them fresh. It is a reported fix, not part of the confirmed rights case: back up the project first and use it only after rights, the read-only attribute and mcp.ini have all been checked.
How do I stop IT changes from breaking the station again?
Treat any change to Windows accounts, groups or folder rights on a WinCC station as a controlled change: capture the working rights set beforehand, schedule the work, then verify a project opens and runtime starts afterward. In the confirmed case nobody linked the rights change to the failures until both projects were already down.