IMDTouchKnowledge BaseShop main store

Troubleshooting

Fixing a WinCC 5.1 to 6.2 migration that will not log in

HMI and touchscreens Published 8 min read

Short answer

The Project Migrator finishing without errors proves database conversion only. The missing login dialog comes from the Siemens Verkehrssteuerung V3.0 suite (VSTStart) and the WinCC Chipcard Terminal that were never installed on the new machine, while the lost SIMATIC S5 PMC Ethernet channel must be carried over from 5.1, because a CP 1613 with a SIMATIC S7 channel does not recreate the S5 155H link.

On this page
  1. What the clean conversion proved — and what it did not
  2. The startup suite behind the missing login dialog
  3. The chipcard terminal, the captions and the printer
  4. The S5 PMC Ethernet channel and the CP card
  5. The sequence that isolates each fault
  6. Counting what the migrator never installs
  7. Where the version ladder goes next
  8. Questions asked

A WinCC 5.1 project that reaches its main picture on WinCC 6.2 SP3 but never shows its login dialog is not a failed conversion. The Project Migrator finished without errors because it converts project data — pictures, libraries, configuration — and installs none of the programs the project starts. The missing login traced to the Siemens Verkehrssteuerung V3.0 suite (VSTStart and its companion programs) and the WinCC Chipcard Terminal, neither of which was installed on the new machine; removing them on the old Windows NT computer reproduced exactly the same stop at the opening picture. Separately, the SIMATIC S5 PMC Ethernet channel to the S5 155H disappears in the 5.1-to-6.2 jump and must be carried over from 5.1, because a CP 1613 with a SIMATIC S7 channel does not recreate that link. Fix the two faults independently and stop re-running the migrator.

What the clean conversion proved — and what it did not #

The source system was three synchronized SCADA computers running WinCC 5.1 on Windows NT 4.0 SP6 with CP 1413 cards, project files on D: (the project file D:\Projem\Projem.MCP) and WinCC under C:\Siemens. The migration bench was a Windows XP Professional SP3 32-bit guest in VirtualBox on a Windows 10 host: Message Queuing and IIS enabled, SQL Server 2005 SP1 Standard installed, then WinCC 6.2 SP3, then the Sybase7 setup from the installation's OPTIONS folder, which asked for the WinCC 5.1 Control Center CD and completed after a reboot.

The Project Migrator ran with the project selected plus Pictures and Libraries, Configuration data, RT data, dBase archive(s) and Swapped-out data marked. Every convert step completed without errors. WinCC Explorer, opened as Administrator, loaded the migrated project, runtime opened its SQL database, and the main picture drew with its clock. Those observations prove the project opens and part of its infrastructure starts; they prove nothing about the application layer. Nothing in the fault traced to the Turkish XP edition, so reinstalling Windows in another language would not have moved anything.

Observed on the XP machine What it actually tells you Next check
Main picture and clock appear Picture display and part of runtime run The application startup list
Login dialog never opens The authentication sequence never starts Verkehrssteuerung V3.0 and VSTStart
Button captions read TEXT Captions are not resolved or assigned Text resources, selected language, startup actions
Not Active appears, controls dead A display state, not a running application The component that sets that state
Printer warning at startup Logging output lost its LPT printer Windows printer configuration
S5 PMC Ethernet reads not installed under Tag Management The referenced channel is unavailable Carry the channel from 5.1
Run-time error 429 after copying VST files An automation object could not be created Install via setup so components register

The startup suite behind the missing login dialog #

The working computers launch programs from Program Files\VST — Siemens Verkehrssteuerung V3.0, including VSTStart — alongside the WinCC runtime. The decisive test ran on the old machine: with those programs removed, the original installation stopped at the opening picture with no login dialog, the same failure the migrated machine showed. That comparison isolates the cause before you buy or move any hardware.

Migration converts project data into the format the destination version reads; it is not an installer for external executables, registered controls, printer configuration or operating-system services that live outside the project directory. Restoring the D: drive image preserved the project location but not the installed suite under Program Files\VST. A project action that starts one of those programs survives migration while the program itself is absent — which is exactly what the login stop reported.

Copying the VST folder to the new machine and launching it from Startup produced run-time error 429. In COM automation, that error means a required automation object could not be created: a missing component, incomplete registration, an incompatible version, or a missing dependency. An OCX is an ActiveX control; a file copy does not perform the installation that registered it and laid down its supporting files. The legitimate path:

  • Record every executable the working system launches — path, launch order, arguments. Expected result: a startup list containing the VST programs, not only WinCC Runtime.
  • Obtain the authorized Verkehrssteuerung V3.0 package and its operating-system compatibility statement from Siemens or the responsible system supplier.
  • Install it through its documented setup so the components register. Expected result: no 429 on startup.
  • If 429 persists, use the failing executable's own diagnostics to name the object it cannot create. Expected result: a specific missing component, not an undifferentiated WinCC fault.
  • Restart the runtime. Pass condition: the login dialog appears and initialization continues past it.

The chipcard terminal, the captions and the printer #

The old installation also runs the WinCC Chipcard Terminal, a Control Panel application on the NT machines that talks to an RS232 reader on COM1, reached through a USB-to-serial adapter on the new machine. The old system displayed its login dialog and accepted password login with the physical reader disconnected, so the reader is not the gate — the installed terminal software is part of the authentication application. Restore the documented authentication components; do not remove the access checks to make the picture interactive.

Treat the button captions reading TEXT as the same startup fault until the suite is installed; if captions still read TEXT after a clean startup, trace the text resources and the selected language separately. The printer warning is expected on a machine with no LPT port, because the project logs to printers that used to hang off LPT; it is a Windows printer-level fix and has nothing to do with the login fault.

The S5 PMC Ethernet channel and the CP card #

The controller is an S5 155H reached over SIMATIC S5 PMC Ethernet through CP 1413 cards. After the 5.1-to-6.2 migration that channel is dropped and Tag Management shows it as not installed. The working fix on this system was to carry the S5 PMC Ethernet channel from the 5.1 installation into the 6.2 machine; after that the migration was complete and the project communicated with the S5 155H. Adding a SIMATIC S7 channel on a CP 1613 does not recreate the link, because a working adapter and the correct application protocol are two separate requirements. The CP 1613 is the Industrial Ethernet PCI adapter that replaces the CP 1413 in this role; a PROFIBUS card such as a CP 5612 does not carry an Ethernet S5 link at all. Whether the CP 1413 itself runs under XP with 6.2 stayed untested here, so the committed path is the CP 1613.

The card can wait. The project opens without any CP card and reports only a connection error, and the old machine showed its login dialog with the CP 1413 pulled from its slot. Defer the communication hardware until the application starts and logs in.

The virtualization boundary is hard: the CP 1613 could not be passed through to the VirtualBox XP guest on the Windows 10 host, and the working arrangement was a separate physical computer running XP with the CP 1613 in a PCI slot. Use the virtual machine to verify conversion, startup and login; give every station that needs the card a physical machine with a PCI slot. For the stations themselves, industrial panel PCs and touchscreen computers are the class that hosts a WinCC runtime or SCADA client at the machine; only the CP station is locked to a physical slot. Once both projects were migrated, the SCADA-to-SCADA Ethernet synchronization came back through WinCC's communications configuration.

The sequence that isolates each fault #

  1. Work from the drive image or backup and leave the original installation untouched — the documented migration guidance says to back up the source project before converting anything.
  2. On the old machine, remove the Verkehrssteuerung startup programs and confirm the login stop reproduces. This proves the dependency before any reinstall.
  3. On the old machine, pull the CP 1413 and confirm the login dialog still appears. This clears the card and the reader as login blockers.
  4. Inventory every executable the working system launches, with path, order and arguments.
  5. Install Verkehrssteuerung V3.0 and the WinCC Chipcard Terminal from authorized media through their setups — never by folder copy.
  6. Restart the runtime and take the login dialog as the pass condition.
  7. Carry the SIMATIC S5 PMC Ethernet channel from the 5.1 installation and confirm Tag Management no longer reads not installed.
  8. Move the CP 1613 to the physical XP machine and confirm the S5 155H tags update.
  9. Stop re-converting. Once the fault is isolated outside the project database, another migrator run cannot change it.

Counting what the migrator never installs #

Worked example for this fleet, using the numbers of the working installation:

  • Synchronized SCADA stations: 3
  • External items per station that conversion never touches: Verkehrssteuerung suite (1) + WinCC Chipcard Terminal (1) + S5 PMC Ethernet channel (1) + LPT printer configuration (1) = 4 items per station
  • Items the Project Migrator installs of these: 0
  • CP adapters to seat: 1 per station; PCI slots on the intended i7 Windows 10 host: 0 (PCIe and PCIe x1 only)

Arithmetic, with units:

  • Manual items = 3 stations × 4 items per station = 12 items
  • Installed by conversion = 0 items; manual remainder = 12 − 0 = 12 items
  • CP adapters = 3 stations × 1 adapter = 3 adapters; PCI slots available = 0; machines needing a different host = 3 − 0 = 3 machines

The count assumes the three stations are synchronized copies with identical peripherals; one extra printer or a second channel on any station adds 1 item to that station only. The decision it forces: plan twelve manual items and three physical PCI hosts before the fleet is finished, and treat the conversion run as the smallest part of the job.

Where the version ladder goes next #

Siemens' documented path makes 6.2 the gateway: the official migration documents cover V4 to V6.2 and 6.2 upward, any 6.x project must sit at 6.2 before converting higher, and 7.2 is the recommended intermediate step on the way to 7.5. From 6.2 SP3 the next conversion is the WinCC Explorer menu item "Tools > Convert Project Data". Leave the project at 6.2 SP3, healthy and logging in, before attempting the next jump; the jump after that follows the same convert-then-verify pattern as migrating a WinCC 7.0 project from Windows XP to Windows 7, and when the ladder reaches 8.0, why WinCC 8.0 runtime deactivates after a V7.5 migration covers that step's own failure mode.

Questions asked

Can the missing CP card or the disconnected chip card reader explain the missing login dialog?

No. On the old installation the login dialog still appeared with the CP 1413 pulled from its slot and the chip card reader disconnected from RS232, and password login worked without a card. That makes the card and the reader non-blockers for login. Buy the communication hardware only after the installed software brings the login dialog back; the missing pieces were the Verkehrssteuerung suite, the WinCC Chipcard Terminal application and the S5 PMC Ethernet channel.

Why does copying the VST folder to the new machine end in run-time error 429?

Run-time error 429 means an ActiveX or COM automation object could not be created. Copying a folder does not register OCX controls, does not install their supporting files, and does not reproduce the setup that wrote the registry entries on the old machine. Install Verkehrssteuerung V3.0 from the authorized media through its documented setup so registration happens, and if 429 persists, use the failing executable's own diagnostics to name the object it cannot create.

What replaces the SIMATIC S5 PMC Ethernet channel on WinCC 6.2 with a CP 1613?

Nothing replaces it. After the 5.1 to 6.2 jump the channel reads not installed under Tag Management, and adding a SIMATIC S7 channel on the CP 1613 does not speak to an S5 155H. Carry the S5 PMC Ethernet channel from the working 5.1 installation into 6.2, then confirm the channel no longer reads not installed and the S5 tags update. The CP 1613 is the Industrial Ethernet PCI adapter for this link; a PROFIBUS card such as a CP 5612 does not carry it.

Can the CP 1613 be passed through to the VirtualBox XP guest on a Windows 10 host?

No. Passing the PCI card into the VirtualBox guest did not work, and the working arrangement was a separate computer running Windows XP directly with the CP 1613 in a PCI slot. Use the virtual machine to verify the conversion, the startup sequence and the login dialog, and plan one physical machine with a PCI slot for every station that needs the card. Each of the three synchronized SCADA computers needs its own adapter and slot.

How should WinCC licenses be moved off the old SCADA computers?

Use the vendor's Automation License Manager to transfer the licenses from the old machines to the new one. Copying license files into the installation's bin folder is not a documented transfer, and the absence of a license error does not prove the transfer is valid. Do this before the old computers are retired, because a license that never left a machine correctly has to be recovered from that machine while it still runs.

Keep reading

  • How-to

    Migrating a WinCC 7.0 Project From Windows XP to Windows 7

    Install WinCC 7.4 on Windows 7, reinstall cleanly if the SP1 package fails, migrate the project through 7.2 with Project Migrator, license the runtime for 1024 tags because 128 runs demo mode, and replace the CP 5611 card with a CP 5612, which has 64-bit SIMATIC NET support. Each gate fails separately, so test each one.

    HMI and touchscreens

  • How-to

    Reuse a legacy HMI program and graphics in a new runtime

    You cannot import a vendor HMI project into a PC HMI or SCADA runtime, and you cannot layer the new runtime on top of the panel. Run the new runtime beside the panel on the same PLC, carry over only the tag addresses and exported images, rebuild screens, alarms and users fresh, then strip write access from the old panel so the audit trail covers every operator write.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC 8.0 Runtime Deactivates After a V7.5 Migration

    The pop-up means an unhandled exception terminated a runtime component, so the whole project leaves runtime. Read the first exception in PDRTSh.log at the stop timestamp, then activate a blank project on the same machine: if it also stops, repair the installation or Windows build against the WinCC 8.0 Update 7 readme; if it runs, bisect the migrated content.

    HMI and touchscreens