How to Enter Configuration Mode on a Touch HMI

HMI and touchscreens Published 5 min read

Short answer

On a touch-only operator terminal you enter Configuration Mode by cycling power and pressing the small filled box that appears briefly in the lower-right corner during startup, while hold-both-arrow-keys instructions apply to keypad terminals with physical keys. An application button labeled GoTo Config. Screen reaches the same menu without a reboot.

On this page
  1. Match the Method to the Terminal Face
  2. Enter Configuration Mode on a Touch-Only Terminal
  3. What the Keypad Instruction Actually Means
  4. If the Startup Box Never Appears
  5. Record the Terminal Identity Before Copying Anything
  6. Transfer Media: the Limit Comes From the Terminal
  7. Copy the Application to the Replacement
  8. Dead Ends That Waste Time
  9. Questions asked

On a touch-only operator terminal you enter Configuration Mode by cycling power and pressing the small filled box that appears briefly in the lower-right corner of the screen while the unit boots. The hold-both-arrow-keys instruction belongs to the keypad variant of the same family, which has physical left and right arrow keys on its bezel; a touch faceplate has no hard keys, and no on-screen arrows will ever appear to fill the gap. The second documented route is a GoTo Config. Screen button built into the application, usually on a protected maintenance screen. Both methods are in the PanelView standard terminals user manual, publication 2711-UM014, and the touch method works only if you watch the right corner from the beginning of power-up.

Match the Method to the Terminal Face #

The manual covers several interface types of one terminal family, so the deciding inspection is the bezel, not the screen. Missing arrow keys are not a fault; they mark a variant.

What you see Documented way into Configuration Mode
Touch face, no hard keys Press the filled box in the lower-right corner during power-up, or the application's GoTo Config. Screen button
Physical left and right arrow keys on the bezel Press and hold both arrow keys together
A PanelView Plus generation unit Startup box draws in the lower left; on Plus 7 Standard, open Terminal Settings, choose Startup Options, and set On Startup to Go to Configuration Mode

All three rows reach the same configuration menu; only the trigger differs.

Enter Configuration Mode on a Touch-Only Terminal #

Schedule the restart first: while the terminal reboots, the machine has no operator interface, so do it with the process idle or a person at the machine controls.

  1. Check the running application for a GoTo Config. Screen button, sometimes labeled Go To Configuration Mode, before you touch power. It opens the same menu with no reboot when your sign-in level exposes it.
  2. Confirm the bezel carries no physical arrow keys, then cycle power to the terminal.
  3. Watch the lower-right corner from the moment power is applied.
  4. Press the filled box the instant it draws; it is on screen only briefly.
  5. If the production application opens anyway, the startup window has passed. Power-cycle again and press earlier; installers report it routinely takes several attempts.
  6. Confirm the configuration menu opens and navigates without the application relaunching. If you only needed to prove access, exit without saving changes.

What the Keypad Instruction Actually Means #

On the keypad variant the left and right arrow keys are hard keys on the terminal face, and pressing and holding them together takes the unit out of its application and into the configuration menu. That combined hold is the procedure documented at page 72 of publication 2711-UM014, and the same manual gives the touch terminal its startup box instead. Nothing about the keypad method translates to a touch face.

If your application has a button that is present but dead when pressed, that is an application-level fault rather than a Configuration Mode access problem; fixing Goto Display buttons locked by HMI global connections covers that class of failure.

If the Startup Box Never Appears #

Identify the family from the nameplate first, then watch the corner its documentation names: lower right on the 550-class touch terminal, lower left on PanelView Plus generation units. Beyond that, two documented outs exist on the Plus side:

  • Plus 7 Standard terminals have a menu path that needs no box: open Terminal Settings, choose Startup Options, and set On Startup to Go to Configuration Mode.
  • Where the box never draws and the shortcut key does nothing, the documented recovery runs through safe mode, and the startup options include a Detect safe mode request at startup setting that has to be enabled for that route to answer.

On a 550-class unit whose box never appears across several watched power-ups, press earlier in the boot sequence; the box is on screen for a shorter time than a normal reaction takes.

Record the Terminal Identity Before Copying Anything #

Configuration Mode is also where you collect what a replacement needs. Write down, while the original unit still runs:

  • The complete catalog number from the nameplate. That number, not the 550-touch shorthand, identifies the fitted communication options, memory, and transfer paths.
  • Every revision and version number the configuration screens display.
  • The current communication settings, before anything changes.
  • Which ports and card slots are physically present.

A connector on the housing does not prove a transfer path; the catalog number plus the configuration menu does.

Transfer Media: the Limit Comes From the Terminal #

One installation's terminal rejected the only card on hand, a 64 GB CompactFlash, while its Configuration Mode screens reported 64 MB as the limit. The arithmetic behind that rejection:

  • 64 GB × 1,024 MB/GB = 65,536 MB
  • 65,536 MB ÷ 64 MB = 1,024
  • 65,536 MB − 64 MB = 65,472 MB of excess capacity

The card exceeded the terminal's stated maximum by a factor of 1,024, and no reformat or partition change closes a gap that size. The decision: treat the capacity message your own unit displays as the requirement, and source media at or under it for your complete catalog number, or move the application across a transfer path the documentation for that catalog number lists.

Copy the Application to the Replacement #

Proving menu access and recovering the application are separate jobs; finish the first before planning the second. With the identity recorded, use the transfer method documented for that exact catalog number, and confirm the target terminal accepts the recovered application before the failing unit comes off the machine. For the wider swap, planning an HMI terminal replacement from an older operator panel walks the compatibility checks, and if the documented path is a serial upload, how to upload an HMI program without the right cable pinout covers the wiring.

Dead Ends That Waste Time #

  • Waiting for on-screen arrow keys to appear. They exist only as hard keys on the keypad variant.
  • Pressing after the application has loaded. The box is a boot-time target; power-cycle and press earlier.
  • Changing PLC network settings to fix a missed startup window. That solves nothing and creates a second fault.
  • Applying a Plus-family USB batch-file procedure to a 550-class terminal. Different hardware and runtime; procedures do not transfer between families.
  • Buying media by connector shape. Capacity and format limits come from the terminal's own message and its catalog number.
  • Pulling the failing unit before recording the catalog number, revisions, communication settings, and physical ports.

Questions asked

Why does the manual tell me to hold arrow keys my terminal does not have?

That procedure is for the keypad variant of the same terminal family, which has physical left and right arrow keys on its bezel. The complete catalog number on the nameplate distinguishes the fitted interface type. A touch variant uses the power-up box in the lower-right corner or the application's GoTo Config. Screen button instead.

The application always finishes loading before I can press the box. What am I doing wrong?

You are reacting to the box instead of anticipating it. Start watching the lower-right corner before you apply power, and press the instant the filled box draws, because it is visible only briefly. If the production screen opens, the window has passed; power-cycle and press earlier. Several attempts are normal on these terminals.

Can I copy the application to the newer terminal through the Ethernet port?

Only if the documentation for your complete catalog number lists Ethernet as a transfer path for the application; a connector on the housing is not proof. First record the catalog number, revision information, and communication settings from Configuration Mode, then follow the documented method. The configuration-menu communication screens show which options that unit actually has.

Why did the terminal reject a 64 GB CompactFlash card?

Because the terminal itself reported 64 MB as its limit. Sixty-four gigabytes is 64 times 1,024, or 65,536 MB, which is 1,024 times that maximum, and no reformat closes a gap that size. Read the capacity message your unit displays and buy media at or under it for your complete catalog number.

Is there a way into Configuration Mode without powering the terminal down?

Yes, when the application developer included a GoTo Config. Screen button and your sign-in level exposes it; it is typically placed on a protected maintenance screen. Ask the integrator which screen holds it. Without that button, the touch terminal's only documented route is the power-up box, which requires a restart.

Keep reading

  • Troubleshooting

    Fixing Goto Display Buttons Locked by HMI Global Connections

    While the Global Connections remote display number is active — its DINT tag still holding 21 — FactoryTalk View ME disables every other form of navigation, so Goto Display buttons stay dead whether or not the popup is visible. Write 21 with a one-shot on bit A and let a startup macro on display 21 reset the tag to 0; the popup stays up and the buttons respond.

    HMI and touchscreens

  • Troubleshooting

    Why an HMI Transfer Fails in Initial Start Mode Despite Ping

    Ping success proves only that the panel's IP stack answers. On a new Magelis XBTG in Initial Start Mode, run three checks in order: build in the engineering version that still supports the target (Vijeo Designer 6.2 for XBTG), clear the license so the download command activates, then load runtime and application over one transport at a time.

    HMI and touchscreens

  • Explainer

    Designing HMI Screens for Clear Operator Decisions

    High performance HMI design under ANSI/ISA-101.01-2015 makes abnormal conditions easier to spot than normal operation: normal running renders flat and gray, saturated color appears only on deviations, and every icon, font and color follows one documented project style. Verify the style mechanism on a single screen before scaling to the full library.

    HMI and touchscreens

Reaching HMI Config Mode With No Startup Square