How to transfer an HMI project with a USB drive or SD card

HMI and touchscreens Published 6 min read

Short answer

Build the project with Build Download Files in EasyBuilder Pro onto a USB drive or SD card formatted FAT or FAT32, then insert the media into the cMT-X panel and choose Download to deploy the project or Upload to copy the panel's current project out. The HMI browser shows the drive as usbdisk and the card as pccard, and the panel's password authorizes either direction.

On this page
  1. Choose the direction before touching the media
  2. Format the media FAT or FAT32 first
  3. Build the download files in EasyBuilder Pro
  4. Download a project to the panel
  5. Upload a project from the panel
  6. When the window or the storage entry is missing
  7. What proves the transfer worked
  8. Questions asked

To move a project between EasyBuilder Pro and a cMT-X panel without a network cable, build the download files onto a USB drive or SD card formatted FAT or FAT32, then let the panel run the transfer: Download deploys the compiled project into the HMI, Upload copies the panel's current project out to the media. The build step lives on the Project tab as Build Download Files in EasyBuilder Pro 6.03.02.393 or later, and a plain file copy onto the card is not a substitute for it. On the panel, the inserted drive shows up as usbdisk and the card as pccard, and the same panel password authorizes both directions. Recipe records do not ride along with a project download: they leave the PC through Utility Manager, on the Publish menu, with Build Download Data for SD/USB Disk. Below are the decision table for the direction, both procedures step by step, and the checks for media that never appears.

Choose the direction before touching the media #

The two labels describe movement relative to the panel, not relative to the PC: Download always means into the HMI, Upload always means out of it. Selecting the wrong one turns a deployment into an extraction.

The job Direction Source Destination Build first?
Deploy a revised project onto the panel Download Download data on the media The panel Yes, with Build Download Files
Archive the project now running on the panel Upload The panel A folder on the media No
Replace a project but keep the old one Upload, then Download Panel, then media Media, then panel Yes, for the Download half

Worked example: a packaging line's cMT-X panel runs revision 3 while the engineering PC holds revision 5. Insert the card, select Upload, browse to pccard, enter the panel password, and the card now carries revision 3 as the archive copy. Take the card to the PC, copy that archive off, rebuild revision 5 onto the card with Build Download Files, bring the card back, and select Download for the revision 5 package. The panel then runs revision 5 while revision 3 survives on the office PC.

Neither direction validates the project contents: the transfer method and the PLC driver inside the project are separate decisions, as set out in why the transfer method and the PLC driver are separate choices. When the panel sits on the plant network, an Ethernet transfer is the alternative route, and its failure causes are covered in why an Ethernet project upload from an HMI panel keeps failing.

Format the media FAT or FAT32 first #

The vendor documents this media method for the cMT and cMT-X ranges on FAT or FAT32 media, so settle the file system before building. On the PC, open the drive's properties and read the file system entry: it must show FAT or FAT32. Anything else means a reformat, and formatting erases the media, so copy anything you need off the card first. Build only after the format is settled, because the build writes the package onto that media.

Build the download files in EasyBuilder Pro #

  1. Open the project in EasyBuilder Pro 6.03.02.393 or later.
  2. Open the Project tab and select Build Download Files; the project compiles first.
  3. When the build window opens, click Browser, select the USB drive or SD card in the Browse For Folder pop-up, and confirm with OK.
  4. Select Build and wait for the Download data created successfully pop-up.
  5. Select OK, then Exit.

The compiled package is what the panel reads. Dropping the editable project file onto the card by hand does not produce it, which is also why an edited project travels as a new runtime download rather than a patched file, as explained in why an HMI edit needs a new runtime download. If the project carries recipe records, publish them to the same media now: open Utility Manager, open the Publish menu, and run Build Download Data for SD/USB Disk with the drive or card as the destination. If the build fails, fix the compile error in the project before the media goes anywhere near the panel.

Download a project to the panel #

Before downloading, put the machine in a state where a swapped operator interface is safe: the download replaces the running project, and the screens change when it completes. Confirm the package on the media belongs to that panel and application.

  1. Insert the prepared USB drive or SD card into the panel, and the transfer window pops up.
  2. Select Download.
  3. Select the Project option and click the folder icon to open the browser.
  4. Open usbdisk for a USB drive or pccard for an SD card, and select the intended project package.
  5. Enter the panel's password and select Download.
  6. Leave the media in place until the transfer completes.

The password is the one configured on that HMI, and a panel whose password was changed rejects the factory value; the situations behind that prompt are laid out in when an HMI download asks for a username and password. If the configured password is lost, the way back is the vendor's documented reset procedure for that model or whoever administers the panel, not repeated attempts in the transfer window.

Upload a project from the panel #

  1. Insert the USB drive or SD card into the panel and select Upload in the transfer window.
  2. Select project and click the folder icon to choose the destination.
  3. Pick usbdisk or pccard, then select OK.
  4. Enter the panel's password and select Upload.
  5. When the transfer finishes, remove the media and copy the project files off it on the PC.

Upload needs no build step, because the project already lives on the panel and the media is only the destination. Treat the retrieved files as the panel's archive copy and store them apart from the download package, so nobody later selects the wrong file from the same card.

When the window or the storage entry is missing #

  • No transfer window on insertion: confirm the media reads on a PC, sits in the required file system, and is seated firmly; a wrong or unreadable format is the usual cause. Swap in different media before suspecting the slot.
  • Window opens but usbdisk or pccard is absent: the panel has not mounted the media, so re-seat it and then try another card or drive.
  • The build reported success but the panel finds no package: the build destination and the inserted device were not the same media, or a reformat after the build wiped the package. Rebuild straight onto the media as it is now.
  • The password is rejected: re-enter the panel's own configured password once, and if it is genuinely lost, use the vendor's documented reset path instead of retrying.

What proves the transfer worked #

After a download, the revised screens appear on the panel. If the old application still runs, the wrong package was selected or the transfer did not complete, so repeat the download with the correct file. If the new screens appear but values are missing or wrong, the transfer succeeded and the fault sits in the tag binding: check the object's tag, device, and address, and compare other objects on the same controller connection before rebuilding anything. After an upload, the destination folder on the PC holds the project files; verify them before the media is reused.

Questions asked

Is the USB or SD card method a replacement for the network transfer?

It is a parallel path, not a replacement. Use the media when the panel has no network connection to the engineering PC or when site policy keeps project writes off the network. The same compiled download data deploys over either path, and the PLC driver inside the project is unaffected by which one carries it.

Do recipe databases travel with the project download?

No. Recipe data is published separately: open Utility Manager, open the Publish menu, and run Build Download Data for SD/USB Disk, then browse to the card or drive as the destination. A project download through the transfer window does not carry recipe records with it, so publish the recipes to the same media before or after the project transfer.

What if the panel rejects the password during the transfer?

Re-enter the password configured on that panel; a unit whose password was changed does not accept the value the factory shipped with. If the configured password is lost, the recovery path is the vendor's documented reset procedure for that model or the administrator who set it, not repeated attempts at the transfer window.

Does the same card procedure cover the whole cMT range?

The vendor documents USB and SD downloads and uploads for both the cMT and cMT-X ranges, with the same file system requirement and the same build step. Older series can differ in the on-screen flow, so check the FAQ written for that series before assuming the same window pops up when the media is inserted.

Keep reading

  • Troubleshooting

    Why an HMI Fails USB Transfer From a USB 1.0 PC

    The panel never receives the project because Weintek terminals expose a USB 2.0 client for direct download, and a PC with only USB 1.0 falls outside that boundary. Load the compiled xob file from a FAT32 pen drive on the panel's USB host port, from SD card where fitted, or over Ethernet, and leave the DIP switches alone: boot loader mode updates firmware, it does not load projects.

    HMI and touchscreens

  • Troubleshooting

    Why an Uploaded HMI Copy Is Not an Editable Project

    Use an HMI runtime backup to restore device data. To edit the project, recover the original engineering files or use the vendor's source-upload function if the source was saved to the panel. If you have only the runtime backup, keep it for restore and plan a rebuild.

    HMI and touchscreens

  • Troubleshooting

    Why HMI Variable Values Reset After a Project Transfer

    HMI values reset after a transfer because the transfer's Initialize settings requested it, the variables were never marked retentive, or the editor's newer version forced a firmware update that initializes all variable memory. Clear [Variable Value] and [Backup Memory] under Initialize, mark operator values retentive, and retrieve the program plus current values with Shift + X before you transfer. Only the firmware-update path wipes retentive values; capture them first, because no setting protects them through it.