IMDTouchKnowledge BaseShop main store

Troubleshooting

Importing a ProTool .lib library into WinCC Flexible

HMI and touchscreens Published 5 min read

Short answer

WinCC flexible cannot import a ProTool .lib object library, and no utility converts .lib files to the .wlf format it expects. Plan the OP270-to-TP177 migration around reusing an existing .wlf library and rebuilding the remaining objects in the TP177 project, then verify each object on the panel.

On this page
  1. Two library formats, one documented bridge
  2. Why renaming the extension is not a conversion
  3. Working the OP270 .lib to a TP177 project in WinCC flexible 2005
  4. Rebuilding and verifying in the TP177 project
  5. If the ProTool project is gone
  6. The screens are a separate job
  7. Keep the rebuild a one-time cost
  8. Questions asked

WinCC flexible cannot import a ProTool .lib object library, and no utility converts a .lib file into the .wlf format WinCC flexible expects. Renaming the extension does not convert the content, so the library has no route into the tool as a library. The one documented bridge between the two packages runs at project level: a ProTool project file (.pdb) opened in WinCC flexible 2008 SP3 or later, converted by the built-in converter. For the case at hand — an OP270 library headed for a TP177 project in WinCC flexible 2005 — the decision is to reuse objects from an existing .wlf library where one exists, rebuild the rest in the TP177 project, and verify every object on the panel before calling the migration done.

Two library formats, one documented bridge #

WinCC flexible keeps its reusable screen objects in libraries that carry the .wlf extension. ProTool, the engineering package behind panels such as the OP270, keeps them as .lib files. The two are different file families from different tools, and the toolset reflects that split: WinCC flexible has no importer for ProTool libraries, and no conversion or adaptation utility turns a .lib into a .wlf. The missing import removes the direct route; the missing converter removes the automated fallback, so neither belongs in the plan.

The documented route between the packages works one level up. The built-in converter (PdnConv.dll) opens a ProTool project file — the .pdb — and converts the project, from WinCC flexible 2008 SP3 or later. That route consumes a project, not a standalone library, so a .lib that arrives on its own is outside its scope.

Why renaming the extension is not a conversion #

Copying the file and changing .lib to .wlf edits the label only. The bytes inside stay in ProTool's library structure, and WinCC flexible reads .wlf structure, so the renamed copy is still not a WinCC flexible library and is not a route. Leave the original name in place as well: the extension is the only marker of which package wrote the file, and a folder of .wlf-named files that no tool opens makes the next migration harder, not easier.

Working the OP270 .lib to a TP177 project in WinCC flexible 2005 #

Inputs, all from the job itself:

  • Source file: one .lib object library, built for an OP270.
  • Engineering tool: WinCC flexible 2005, which works with .wlf libraries.
  • Destination panel: a TP177.
  • Candidate routes into a WinCC flexible library: three — direct import, library format conversion, project-level conversion.

The rule in words: a route counts only when the tool documents it. Direct import counts only if WinCC flexible can open .lib files. Format conversion counts only if a utility produces .wlf from .lib. Project conversion counts only if the file in hand is a .pdb project.

The arithmetic, route by route:

  • Start: 3 candidate routes.
  • Direct import: refused — WinCC flexible cannot import ProTool libraries: 3 - 1 = 2.
  • Format conversion: no utility converts or adapts .lib to .wlf: 2 - 1 = 1.
  • Project conversion: consumes a .pdb, and a standalone .lib is not a project: 1 - 1 = 0.

Result: 0 documented paths from this .lib into WinCC flexible 2005.

The decision, with its threshold: at 0 documented paths, the plan is reuse-then-rebuild — populate the TP177 project from any .wlf library already on hand and rebuild the remaining objects in WinCC flexible 2005. If you also hold the original ProTool project as a .pdb, the count for that file is 1 and the built-in converter is the route; the standalone .lib still has none.

Rebuilding and verifying in the TP177 project #

Work the rebuild in this order:

  1. Search for a .wlf first. The libraries installed with WinCC flexible and the ones saved alongside your earlier projects are quick to check, and anything found there is reuse rather than rebuild.
  2. Version-check a borrowed library. WinCC flexible from version 2005 on can save projects and libraries in the format of an earlier WinCC flexible version, so a .wlf made in a newer release is saved down to the 2005 format from that newer release before this installation opens it.
  3. Read the original where it can be read. .lib is ProTool's format, so a station with ProTool installed opens the library and displays the objects; record geometry, colors and text from that view.
  4. Rebuild object by object in the TP177 project, keeping the ProTool object names so each one stays traceable to the OP270 screens that used it.
  5. Verify on the target. Place each rebuilt object on a TP177 screen, connect it to the TP177 project's tags, and exercise it in simulation or on the panel. The migration is finished when the object runs on the TP177, not when a library file exists.

If the ProTool project is gone #

A standalone .lib with no .pdb behind it has no conversion route, so search for the project file or an archive of it before anything else — the converter is the only documented bridge and it needs the project. If the .lib genuinely is the only survivor, treat it as a drawing to rebuild from. A panel whose project was never archived is the same problem one step earlier, and How to Recover an HMI Program When the Source File Is Lost walks that recovery from the panel side.

The screens are a separate job #

Libraries are one part of a ProTool-to-WinCC flexible move. The screens travel through the project converter when a .pdb exists, and they are rebuilt alongside the objects when it does not; the checks worth making as legacy screens come across a panel change are laid out in Importing legacy HMI screens when migrating to a new panel.

Keep the rebuild a one-time cost #

Whatever comes out of the rebuild by hand, save it into a .wlf library of your own before the project goes into service, so the next WinCC flexible project reuses it instead of redrawing it. The same argument holds a level down in the controls: keeping reusable blocks in a library rather than inside a single project is what makes the next machine cheaper, which is the case made for reusing user-defined instructions instead of rebuilding them on the PLC side.

Questions asked

Can ProTool open a .wlf library made in WinCC flexible?

Nothing documents that direction either. The documented statements cover .lib files arriving in WinCC flexible; they say nothing about ProTool reading .wlf, so treat the formats as one-way and keep each library with the package that wrote it. If you need the same objects in both tools, maintain one library per tool rather than expecting a single file to serve both.

Does the project converter bring the .lib objects into the converted project?

The built-in converter that runs when a ProTool project file is opened in WinCC flexible 2008 SP3 or later converts the project; the documented statements do not extend that to standalone .lib libraries. Open the converted project and check it for each object you actually need, then rebuild or borrow from a .wlf library whatever did not arrive.

Why not configure the TP177 with ProTool instead?

The panel decides the tool: the TP177 is configured in WinCC flexible, so its project can only use .wlf-side objects no matter how good the old ProTool library is. Keep ProTool in the picture only as the viewer that displays the original .lib objects while you rebuild them for the TP177 project.

Is there a batch conversion for several .lib libraries at once?

No. With no utility converting or adapting .lib files to .wlf, each library is a manual job: view the objects in ProTool where possible, rebuild them or find .wlf equivalents, and verify them on the TP177. On a multi-panel migration, schedule the library rebuilds as their own line items instead of planning an automated step that does not exist.

Keep reading

  • How-to

    How to migrate a WinCC flexible project to TIA Portal

    One TIA Portal installation replaces both STEP 7 Classic and WinCC flexible, but the two project types move differently: the STEP 7 V5.x project is imported, and the WinCC flexible 2008 project is migrated through an intermediate release because the newest TIA Portal versions no longer offer that migration. Verify the exact S7-300 CPU and panel against the device lists and license STEP 7 and WinCC Comfort separately.

    HMI and touchscreens

  • How-to

    Importing a PLC Tag CSV into an Existing HMI Tag Database

    A PLC tag CSV imports only when its columns match the format your HMI software documents — .csv for one package, .xlsx for another. Never import into the production project: run it on a copy, use the tag count to tell merge from replace, spot-check one revised address, and confirm each affected tag against live PLC values before download.

    HMI and touchscreens

  • Troubleshooting

    Why COROS COMED Rejects S5L Files Before a WinCC Migration

    The COMED error means the editor cannot decode the file's internal structure: the S5L lists came from another editor or COROS release, or were renamed. Open them in the COROS version that created them, then import through the WinCC Dynamic Wizards, reconciling every variable against the recovered source count.

    HMI and touchscreens