Licensing InTouch for three nodes and 2,500 tags

HMI and touchscreens Published 7 min read

Short answer

A standalone InTouch application needs no Application Server. License by runtime node: three nodes running Window Viewer means three tag-count licenses, and InTch-30-N-231 is the part for this count since it includes Communication Drivers Standard. SQL Server Express covers the alarm DB logger at this scale.

On this page
  1. Does a standalone InTouch application need Application Server?
  2. Which InTouch license part number covers 2,500 tags?
  3. How many licenses does a three-node InTouch setup need?
  4. Where should the I/O server run on each node?
  5. Is SQL Server Express enough for the InTouch alarm DB logger?
  6. How long can the InTouch data logger hold trend history?
  7. What should I confirm with the distributor before ordering?
  8. Questions asked

You need three tag-count licenses, not one, and no Application Server. A standalone InTouch application — the kind built in Window Maker and run by Window Viewer — installs without Application Server or a Galaxy, so leave those components off all three Windows 10 nodes. InTch-30-N-231, the 2,500-tag-count InTouch license that includes Communication Drivers Standard, is the part that covers this application, bought through the local AVEVA distributor. SQL Server Express runs the alarm DB logger at this scale. The sections below take each decision in the order you meet it, with the arithmetic for the two capacity questions.

Does a standalone InTouch application need Application Server? #

No. A standalone InTouch application is a set of files held in the directory file system, built in Window Maker and run by Window Viewer, and it has no dependency on Application Server or a Galaxy; leave those components unselected on all three nodes.

The InTouch HMI Application Manager creates and manages standalone applications directly, and a standalone project can also hold Industrial Graphics. Install Window Maker and Window Viewer on the engineering workstation, Window Viewer on the other two nodes, and do not select the Application Server development components anywhere.

Application Server earns its place only when you want Galaxy-hosted objects, templates, or Application Server-managed alarm sources. Pulling a standalone application into a Galaxy later is possible, but it is an administration step you choose, not a prerequisite you inherit.

The reading that settles it: if every tag lives in the Tagname Dictionary and reaches the controller through I/O access names, the project is standalone and this question is closed.

Which InTouch license part number covers 2,500 tags? #

InTch-30-N-231 is the part that fits: the 2,500-tag-count InTouch license, and it includes Communication Drivers Standard, so each node can run its own communication driver. Buy it through the local AVEVA distributor, who holds the current part list and the capability description for each license.

Two facts decide the tier. The tag-count license tiers against I/O tags; memory and system tags are treated as the license documentation specifies, so read the Tagname Dictionary's I/O count as the number that must sit under the cap. And an application already at 2,500 I/O tags fills this tier completely: there is no headroom, and an exceeded tier is a runtime failure, not a build-time warning.

If planned additions take the I/O count past 2,500, order the next tier up at the same time. The bundled drivers matter more than they look here — because InTch-30-N-231 includes Communication Drivers Standard, every node can host its own local I/O server, which is the architecture this layout should run.

How many licenses does a three-node InTouch setup need? #

Three: one tag-count license per node that runs the application. The engineering workstation, the panel-door touchscreen computer, and the operator workstation in the second building each run Window Viewer, so each needs its own license — three in total.

Node What runs there License decision
Engineering workstation Window Maker development, Window Viewer runtime, DDE server One InTch-30-N-231 — development and runtime on one node
Panel-door touchscreen computer Window Viewer runtime, same application One InTch-30-N-231
Operator workstation, second building Window Viewer runtime, same application over the fiber link One InTch-30-N-231

Three nodes × one license each = three InTch-30-N-231 licenses on the order. A single tag-count license does not entitle three simultaneous runtimes of the same application; the count follows nodes, not projects. If one computer drove every screen instead, the license count would collapse with the node count — that trade-off is covered in running one HMI interface on multiple touchscreens from one PC — but with three machines in two buildings, three licenses is the decision.

The panel-door node is a touchscreen computer running the HMI runtime at the machine, which is the job industrial panel PCs are specified for. One safety note belongs here: keep interlocks and stops in the controller, because a node that stops over licensing leaves an operator blind, and no HMI license tier substitutes for hardwired or PLC-resident safety functions.

Where should the I/O server run on each node? #

Run a local I/O server on each node. The bundled Communication Drivers Standard makes that possible, it keeps every operator screen independent of the engineering workstation, and the trade-off is more simultaneous client connections on the Tricon CX communication module.

Configuration Where the I/O server runs Effect
Local server per node Each node runs its own driver and reaches the Tricon CX through the switch Every screen survives loss of the engineering workstation; more simultaneous connections on the controller
Central server Only the engineering workstation talks to the controller; the other nodes reach it across the network One controller connection; every remote screen depends on the engineering workstation being up

Choose local servers on the panel computer and the remote operator station: engineers reboot, patch, and open the development workstation in Window Maker, and an operator screen should not depend on that. Before committing, read the Tricon CX communication documentation for how many simultaneous client connections the communication module accepts — this layout asks for three — and keep every node on the same switch fabric, with the fiber link carrying the same traffic.

On each node, open the I/O access names the application uses and confirm the node, application, and topic resolve on that machine, then ping the controller communication module. A failure there is network, not tags; if the connection is good and one tag reads badly, the fault is in that tag's item name, data type, or scaling. The wider split — which jobs belong on a server in the cabinet and which on panels at the machine — is covered under headless HMI server versus operator panel selection.

Is SQL Server Express enough for the InTouch alarm DB logger? #

Yes, at this scale. SQL Server Express runs the alarm DB logger, and Microsoft caps one Express database at 10 GB on SQL Server 2016 through 2022; a 2,500-tag application at a typical alarm volume uses a fraction of that, so Express is the decision.

Worked example, with illustrative inputs — 5,000 alarm and event rows per day, where every alarm, return-to-normal, and acknowledgement is a row, at 500 bytes per row including index overhead:

  • 5,000 rows/day × 500 B/row = 2.5 MB per day
  • 2.5 MB/day × 365 days = 912.5 MB ≈ 0.9 GB per year
  • 10 GB ÷ 0.9 GB per year ≈ 11 years before the Express cap bites

Install Express on the node with the most reliable power — the engineering or operator workstation, not the panel computer — point the alarm DB logger at it, and schedule the purge so retention ages out on purpose. AVEVA's own requirements draw the line far above this application: above 50,000 I/O per node a Windows Server operating system is required, and SQL Server Express is not supported in that large-installation band. A 2,500-tag node sits at five percent of that threshold.

How long can the InTouch data logger hold trend history? #

As long as the disk budget allows: with no AVEVA Historian, retention is a rate calculation, not a fixed cap. At 200 logged tags on a 10-second cycle, history grows about 35 MB per day, so 100 GB of disk holds roughly eight years of trend data.

No fixed tag-count ceiling for the logger appears in the documentation gathered here; the practical limits are node loading and disk. A 2,500-I/O node sits inside the small-application band of 1–25K I/O per node, so the hardware is not the constraint — the disk is. Size it with the same arithmetic:

  • 200 tags × 6 samples/minute = 1,200 samples/minute
  • 1,200 samples/minute × 1,440 minutes/day = 1,728,000 samples/day
  • 1,728,000 samples/day × 20 B/sample ≈ 35 MB/day — treat 20 B per stored sample as a planning figure, not a spec
  • 100 GB ÷ 35 MB/day ≈ 2,900 days ≈ 8 years

Decision: budget the disk, set retention so data ages out deliberately, and log only the tags the trends actually plot. If the plant later needs compressed, fast-query history across thousands of tags, that is the separate Historian product, chosen for that job.

What should I confirm with the distributor before ordering? #

Five things, all resolvable in one distributor email: the part number against your release, the license count per node, the tag-counting basis, the growth tier, and the supported Windows build.

  1. Confirm InTch-30-N-231 against your release — 2023 R2 SP1 P02 here — and ask for the current capability matrix.
  2. Get the three-license, three-node count in writing, including development and runtime together on the engineering workstation.
  3. Ask how memory and system tags are treated, and tier against the I/O count from the Tagname Dictionary.
  4. If planned additions push the I/O count past 2,500, settle the next tier now, not at commissioning.
  5. Confirm each node's Windows 10 build is on the release's supported operating system list.

Questions asked

What actually happens on screen when a node exceeds its licensed tag count?

The failure appears at runtime, not at build time: the node stops running the application properly while another node with the identical project runs normally, which sends people chasing tags and drivers when the cause is licensing. The fix is the next tag-count tier, not deleting tags the operators use to squeeze under the cap.

Does the DDE server on the engineering workstation need its own license?

No. The communication driver or DDE server process is not licensed separately: driver capability ships inside the node's InTch-30-N-231 through Communication Drivers Standard. You license runtime nodes, not driver processes, so the engineering workstation's single license covers its development tools, its runtime, and its DDE server together.

Do memory tags count against the 2,500-tag license?

The number that tiers the license is the I/O tag count from the Tagname Dictionary. Memory and system tags are treated as the license documentation specifies, so count I/O tags first: if that count alone is 2,500, the tier is already full, and the next new I/O tag requires the next tier no matter how few memory tags exist.

Should the alarm database live on the panel-door computer?

It can, but it should not. The panel computer is power-cycled with the panel and is the least dependable host for a database that other nodes write to. Put SQL Server Express on the engineering or operator workstation — the machines with the most reliable power — and point the alarm DB logger there across the switch and fiber.

If one PC drove all three screens, would one license be enough?

Yes — license count follows runtime nodes, so collapsing three nodes into one computer collapses three licenses into one, at the cost of every screen depending on that single machine. That one-interface-many-screens arrangement is an architecture decision you make before licensing, not a workaround you apply afterward.

Keep reading

  • Explainer

    What a SCADA Operator Interface Must Do: Core Functions

    A SCADA operator interface carries six functions: acquisition and display of binary and analog data, alarm and event recording, a history database of process values, measurand processing for derived values, presentation through graphics, lists and reports, and command handling from binary commands to recipes. Keep alarm and event records separate from the history database: one records occurrences, the other retains values.

    HMI and touchscreens

  • Selection guide

    How to Select Lightweight HMI Software for Modbus I/O Control

    Select on three gates in order: a driver that speaks Modbus RTU (and Modbus TCP if the LAN path is required), a tag license at least 20 percent above your counted total, and a runtime that runs the exported project on a clean PC. A 56-device floor plan counts 154 tags, so a 150-tag edition already fails. Prove one floor plan, one popup, one live indicator and one write before you pay.

    HMI and touchscreens

  • How-to

    Activating a WebIQ Designer trial license for project conversion

    WebIQ Designer never runs without a license, and a successful connection to 127.0.0.1:17123 proves neither login rights nor license state. Request a trial license — a shorter one through the vendor's license store or a 30-day one through its trial sign-up — activate it for the environment you connect to, and convert the v2.16.3 project on a working copy in Designer v2.17.

    HMI and touchscreens