Replacing a CP5611 PCI Card in a New WinCC Station

HMI and touchscreens Published 7 min read

Short answer

Yes. Keep the project's channel, connection and tag addresses exactly as they are and change only the PC-side interface: install a USB or PCI Express PROFIBUS adapter the channel supports, then select it in SIMATIC PG/PC Interface and in the WinCC connection. A converter on the Ethernet port is the one option that can force tag rework, so leave it for distance or shared-access cases.

On this page
  1. What changes and what stays
  2. Record the baseline before you disconnect anything
  3. Choosing between a USB adapter, a PCI Express card and a gateway
  4. Checking throughput for a 32-bit PCI card at a 33 MHz bus clock
  5. Swapping the station step by step
  6. If the new station does not communicate
  7. Questions asked

You can move this station to a new branded computer and keep every tag address, provided you own the editable WinCC project. The CP5611 is only the PC's physical interface on the bus: a tag is bound to its controller address through the WinCC channel and that channel's connection, and neither lives in the card. Put a USB or PCI Express PROFIBUS adapter that the channel supports into the new PC, select it in SIMATIC PG/PC Interface and in the WinCC connection, and the project communicates again. The Ethernet-to-PROFIBUS converter is the one route that can drag the channel and the addresses with it, so it is the third choice. The risk that actually bites is WinCC 6.0 on new hardware, not the card.

What changes and what stays #

In WinCC, the channel is the driver that exchanges data with the controller, and each tag points at a controller address through one connection of that channel. The CP5611 belongs to neither: it is the interface the PC uses to reach the wire, carrying MPI and PROFIBUS DP traffic. That separation is the whole trick behind this migration, and it is the same architecture you rely on when running WinCC PC runtime over a PROFIBUS card: the channel owns the addressing, the card is only the transport.

Between the application and the hardware sits one more assignment. An access point is the named slot through which an application picks a PC interface, and SIMATIC PG/PC Interface maps each access point to an installed interface. After the swap, exactly two selections in the whole system change: the interface assigned to your access point in SIMATIC PG/PC Interface, and the interface named inside the WinCC connection. Every tag address stays as it was.

Record the baseline before you disconnect anything #

  1. Back up the editable project — not just a runtime backup — and keep that copy separate from the commissioning copy you will restore later.
  2. In the project, write down the channel the active connection uses, its connection parameters, and the addresses of two test tags: one value that changes on its own, such as a counter or clock, and one steady value you can recognize.
  3. In SIMATIC PG/PC Interface, record which access point the project uses and which interface is assigned to it.
  4. Record the bus settings from their dialogs: transmission rate, the PLC's station address and the PC's own station address.
  5. Photograph the bus connector positions and the termination switches before unplugging the cable.

Choosing between a USB adapter, a PCI Express card and a gateway #

First the physical fact: PCI and PCI Express are different interfaces. The CP5611 is a conventional PCI design — a 32-bit card on a bus clocked no faster than 33 MHz, and the later CP 5611 A2 stayed a 32-bit PCI card as well — so it does not fit a PCIe slot and no new branded PC offers it a home. A clone board with a PCI slot would work electrically, but your branded-computer policy rules that out, and the interface swap makes it unnecessary.

Option Fits when Tag edits
USB PROFIBUS adapter the new PC has no slot to spare, or you want one adapter for commissioning and runtime none — reselect the interface only
PCI Express PROFIBUS card the station is a slotted industrial PC none — the same two selections
Ethernet-to-PROFIBUS converter the station must sit beyond the bus cable run, or several PCs share one bus access possibly many — a different channel and address mapping

For one station next to its bus, take the USB adapter; take the PCI Express card when the computer is a slotted industrial PC; leave the converter for distance and shared access, because it is the only option that can end in a channel change and tag rework. If the replacement doubles as the machine-side operator screen, choose the interface first and match the computer to it — industrial panel PCs are the category to compare for a touchscreen station at the machine.

Before buying any adapter, verify three things on the vendor's support pages: the driver supports the new PC's operating system; the SIMATIC NET version the adapter needs is compatible with the WinCC version you will run; and the adapter is released for runtime process-data traffic on your channel — programming-device download support alone does not run an HMI station.

The older problem is WinCC 6.0 itself. New branded PCs ship with operating systems a 6.0-era communication stack was never qualified for, so plan the software at the same time as the card: move to a currently supported WinCC with the vendor's project migration, the approach described for reusing a legacy HMI program and graphics in a new runtime, or keep the old stack unchanged in a VM on the new PC and pass the USB adapter through, the same mechanism used for running a USB license dongle in VMware for WinCC.

Checking throughput for a 32-bit PCI card at a 33 MHz bus clock #

The inputs, each with its source:

  • 32 bits per PCI transfer — the documented bus width of the CP 5611 A2 card.
  • 33 MHz — the documented maximum PCI bus clock the card is designed for.
  • 12 Mbit/s — the highest PROFIBUS DP transmission rate in the standard.
  • 480 Mbit/s — the USB 2.0 line rate.

The rule in words: a bus moves bits per transfer multiplied by transfers per second; compare that peak with the highest rate the field bus can demand.

The arithmetic:

32 bit/transfer × 33,000,000 transfer/s = 1,056,000,000 bit/s, which is 1056 Mbit/s or 132 Mbyte/s of peak PCI capacity. 12 Mbit/s ÷ 1056 Mbit/s = 0.011, so the heaviest PROFIBUS load uses about 1.1% of the old card's bus capacity. 480 Mbit/s ÷ 12 Mbit/s = 40, so even the slowest realistic attach point carries forty times the field bus maximum, and a PCI Express slot starts higher still.

The decision: any candidate whose link exceeds your bus rate — every USB or PCI Express option does, by at least forty times — passes on speed. Reject adapters only for a missing slot or missing documented driver and channel support. Nobody needs to hunt a faster card; throughput was never the constraint, even on the old PCI slot the CP5611 came from.

Swapping the station step by step #

  1. Build the new station while the old one still runs: install the operating system, the chosen WinCC version and its communication software from authorized media, and move the licenses with the vendor's licensing tool — what RT and RC keys mean and how a key moves is covered in moving a WinCC runtime key.
  2. Install the adapter's driver in the documented order, connect the adapter, and confirm the operating system lists it without an error and that SIMATIC PG/PC Interface offers it as a choice.
  3. Restore the project backup into a working copy, or run the vendor's project migration if the WinCC version changes.
  4. In SIMATIC PG/PC Interface, assign the project's access point to the new adapter and enter the bus settings from the baseline: same transmission rate, same PLC station address.
  5. Give the new PC the old station's bus address only after the old computer is off the bus; two devices with one address disturb the whole segment.
  6. In the WinCC project, open the connection and select the new interface wherever the channel names it. Leave the channel, the connection parameters and every tag address untouched.
  7. Do the cutover with the machine in a state where a missing HMI is safe — the link is down while you work. Reconnect the bus cable and the termination exactly as photographed, then start the runtime.
  8. Check the two test tags: the changing one updates, the steady one reads its known value, and the connection state stays fault-free.

If the new station does not communicate #

  • Every tag shows bad or invalid quality: the access point or the WinCC connection still names the old interface. Make both selections again; the addresses are not the problem.
  • Nothing communicates and the adapter reports bus errors: the transmission rate or a station address differs from the baseline, or the termination is missing at the point where the new PC now sits on the segment.
  • Two stations answer at once: the old PC is still connected with the same bus address. Disconnect it before blaming the migration.
  • One tag is wrong while its neighbours are live: that tag's address or scaling, not the interface swap — fix the tag, not the hardware.

Keep the old computer complete until the new station has run a full production cycle. Rollback is reconnecting the old box, which is exactly why the baseline notes and the separate backup exist.

Questions asked

Do the tags change when the CP5611 is replaced by a USB adapter?

No. A tag's address is bound to the channel and its connection, not to the card in the PC, so as long as the same channel supports the new adapter the addresses stay. The channel, the connection parameters and the tags all survive; the hardware change itself touches nothing in the project file.

Can the CP5611 go into the new computer anyway?

Only into a conventional PCI slot. The card is a 32-bit design with a 33 MHz bus-clock limit, and PCI Express is physically and electrically a different interface, so a PCIe-only machine cannot take it. The successor CP 5611 A2 is also a 32-bit PCI card, so a newer card of the same number does not solve the slot problem — the change has to be to USB or PCI Express.

Is the Ethernet-to-PROFIBUS converter the cleaner solution?

For one station, no. It adds a device to configure, needs its own power supply, becomes an extra failure point between the HMI and the PLC, and depending on how it presents the controller it can force a different WinCC channel and address rework. Take it only when the station must sit beyond the cable length your transmission rate allows, or when several PCs must share one bus access.

Is WinCC 6.0 itself a problem on a new branded PC?

Usually yes, and it is a bigger risk than the card. New PCs come with operating systems a 6.0-era communication stack was never qualified for, so either move to a currently supported WinCC with the vendor's project migration, or keep the old environment in a virtual machine and pass the USB adapter through. The interface swap procedure is the same in both cases.

What exactly do I verify before buying the replacement adapter?

Three checks against the vendor's support entries: the adapter's driver supports the new PC's operating system; the SIMATIC NET version it requires is compatible with the WinCC version you will run; and it is released for runtime process-data traffic on the channel you use. Programming-device download support alone does not qualify an adapter to run an HMI station.

Keep reading

  • How-to

    Run WinCC 7.0 PC Runtime over a PROFIBUS card

    No panel-versus-PC switch exists: launch WinCC Runtime on the PC, but the PROFIBUS link only works after the card driver is installed, the PC interface points at that card, and the WinCC connection carries the PLC's station address, rack and slot — then a moving tag value proves the link.

    HMI and touchscreens

  • How-to

    Replacing an old HMI when no project files exist

    There is no free configuration software for a legacy Magelis or PanelMate panel that arrived without it, so choose one of three licensed routes: buy the matching engineering package, hire an integrator who owns it, or have a distributor upload and print. If no editable project can be recovered, capture the running application, map every tag against the live controller, and rebuild on confirmed writes.

    HMI and touchscreens

  • How-to

    Replacing a Fleet of PanelView 550 Terminals on DH-485

    There is no direct swap: the PanelView 550 is Silver Series, so each terminal is a migration. The PanelView Plus 6 600 keeps the 550 cutout but needs a third-party DH-485 adapter; a Plus 6 700 takes the 2711P-RN6 but modifies the cutout. Audit all 25 catalog numbers, convert one application in FactoryTalk View Studio ME, pilot one machine, then buy the fleet.

    HMI and touchscreens