How-to
Restore a KTP400 Basic .psb backup with ProSave
Short answer
A .psb file is a ProSave device backup of one panel, not a WinCC project, so WinCC and the migration tool ignore it by design. Restore it with ProSave, and only onto the same HMI device type: a first-generation KTP400 Basic Mono backup will not restore onto a second-generation KTP400 Basic, which needs the migrated engineering project instead.
On this page
The .psb file in your backup folder is a ProSave device backup — a complete image of one panel — and not a WinCC project, which is why WinCC and the migration tool never list it. Restoring that image is ProSave's job. Restore also carries one hard rule: the image lands only on the same HMI device type it was taken from. A first-generation KTP400 Basic Mono backup will therefore not populate the second-generation KTP400 Basic you have already bought; it will bring an identical replacement panel back to life. The new panel is fed from the engineering project, not from this file.
What a .psb file is, and what it is not #
ProSave's backup function copies the panel as a unit: the firmware image and the runtime project exactly as they run on that one device. The .psb exists so that same panel can be recovered after a failure — it is the counterpart of the restore function, nothing more.
An engineering project is a different object. For a first-generation basic panel it lives in WinCC flexible as an .hmi project, or packed as a project archive, and that is what a migration consumes. A device image is never an input to a project migration, and renaming the extension converts nothing. The same boundary explains why a PSB backup cannot run in WinCC flexible PC runtime: a PC runtime loads a project, not a panel image.
The device-type rule that decides the restore #
The rule is enforced by the tool: a .psb restores to the same HMI device type recorded inside it. In ProSave you set the device type yourself on the "General" tab, and the restore compares that selection with the backup's recorded type. A mismatch is refused.
Your case in one line: KTP400 Basic Mono PN, a first-generation WinCC flexible panel, and KTP400 Basic, the second-generation TIA panel, are different device types. Same screen size and family name do not change that. Assign each file its job now — the .psb revives an identical replacement, and the second-generation panel receives a migrated project. For the specific mono-to-color jump there is a documented walkthrough of migrating a KTP400 Basic Mono PN .psb backup to a color KTP400, and it starts from this same limit.
Restore the .psb with ProSave #
One warning first, because it is the only irreversible step here: a restore overwrites the complete contents of the target panel — project, recipes and logs included. Back the target up first if it holds anything you need.
- Put ProSave on a PC that can reach the panel. ProSave installs with the WinCC engineering software — the WinCC flexible installation for first-generation basic panels — and starts from the Windows Start menu.
- On the "General" tab, select the HMI device type the backup was taken from. The exact type, not a similar one.
- Set the connection the panel supports: PN/IE with the panel's IP address for Ethernet panels, or the serial settings for devices that transfer over a serial port.
- Open the restore function, set the file filter to
*.psbso the backup becomes visible, and browse to the file. If it does not appear, the filter or the path is wrong — renaming the file fixes nothing. - Start the restore. The panel reboots into transfer mode, the image is written, and the panel restarts into runtime on its own.
- Leave the power alone until that restart happens; interrupting the write leaves the target without a complete image.
A worked restore with the numbers #
You source an identical KTP400 Basic Mono PN as the like-for-like replacement. The addresses below are illustrative — substitute yours.
- Panel: 192.168.0.10 with subnet mask 255.255.255.0 → 192.168.0.10 AND 255.255.255.0 = 192.168.0.0
- PC: 192.168.0.1 with subnet mask 255.255.255.0 → 192.168.0.1 AND 255.255.255.0 = 192.168.0.0
Both compute to 192.168.0.0, so the transfer path is a single subnet. Ping the panel once to prove the path before opening ProSave. The device type selected in ProSave equals the type inside the backup, so the restore completes and the replacement boots into the old application.
The panel you already bought fails the same comparison: its device type, second-generation KTP400 Basic, does not equal the backup's recorded type, and re-selecting a lookalike type does not change the comparison. The practical sequencing follows from the two lines above: restore the .psb onto an identical panel to run the line now, and move the application to the new panel through the project route once the project exists.
Getting the application onto the second-generation panel #
The supported route is the engineering one: take the original WinCC flexible project — the .hmi file or its archive — migrate it forward in TIA Portal, and download it to the new panel. No supported tool converts a .psb into that project.
Where projects usually surface: the engineering PC that last touched the line, the project archive folders, the integrator's handover media, and older backups that may hold more than the .psb — verifying HMI project data is inside a platform backup is worth doing before you declare the project lost.
If the project exists nowhere, you are rebuilding, and the rebuild is the moment to choose the platform: redraw the application in TIA onto the new panel from the machine's requirements, or move to a PC-based HMI on industrial panel PCs at the machine. Either way, replacing an old HMI when no project files exist is the decision path to follow.
Proving the restore worked #
- ProSave reports the restore finished, with no transfer error.
- The panel leaves transfer mode and reaches runtime on its own restart.
- The expected screens are present and navigation between them works.
- Two or three tags tied to the PLC change on screen while the process runs.
- Recipes and logs are what the line expects, because they arrived inside the image.
A finished transfer plus runtime plus that functional check is the full proof a restore can give. It proves recovery only — no project appears on the engineering PC from this operation.
Questions asked
Can I convert the .psb backup into an editable WinCC project?
No. A .psb is the panel image, firmware plus the runtime project as loaded, and no supported tool converts an image back into engineering data. This trap usually starts when someone runs a ProSave backup where a project archive belonged; the file to collect for the future is the .hmi project or its archive from the engineering PC.
Can the panel restore the .psb without a PC?
On panels with a USB port, yes. The service and commissioning area of the panel itself offers backup and restore to a USB stick, with no PC software in the loop, and it obeys the same device-type limit: the stick image goes back onto the same panel type it came from.
Does the .psb backup also contain the PLC program?
No. The image covers the HMI device only: its firmware, the runtime project and panel-held data such as recipes and logs. The PLC program is archived separately from the controller with the PLC vendor's own tool, and a complete line handover needs both files.
Which ProSave installation do I need?
ProSave arrives with the engineering software: the WinCC flexible installation covers the first-generation basic panels, and the TIA Portal installation covers the second generation. Either way you start it from the Windows Start menu and select the exact device type of the backup on the General tab.
ProSave refuses a device mismatch on a panel that looks identical. What do I check?
Compare the exact device-type strings, because generation, mono or color display and the interface variant each count as a different type. If the strings truly match and the refusal repeats on a second connection, the backup was probably taken from a different device type than its file name suggests. Check the records of the panel it came from before retrying.