Deploy a WinCC 6.2 Project on a Separate Runtime PC

HMI and touchscreens Published 5 min read

Short answer

Install WinCC 6.2 on both machines: Runtime installs with the same setup, so there are no separate runtime files to carry. License the desktop PC that activates the project, copy the whole project folder to it, register the folder in AutoStart, and build the job as a Single-User Project.

On this page
  1. What Runtime is in a WinCC 6.2 installation
  2. Pick the project type before you configure anything
  3. Deploy the project to the runtime PC
  4. Where the license sits, and how many you need
  5. When the copied project will not activate
  6. If the runtime PC is reformatted
  7. Questions asked

Install WinCC 6.2 on both machines. Runtime is not a separate product you export from the laptop: it installs together with WinCC from the same 6.2 setup, so the desktop PC gets Runtime when you install WinCC on it, and there are no runtime files to hunt for and carry across. Put the license on the desktop, the machine that activates the project; keep the laptop as the engineering station; copy the whole project folder over and register it once in AutoStart. For one laptop and one desktop, build the job as a Single-User Project.

What Runtime is in a WinCC 6.2 installation #

One WinCC setup installs two functions: the engineering environment — WinCC Explorer, Graphics Designer, tag logging and archive configuration — and Runtime, the activated project that draws the pictures, polls the PLC and writes the archives. That single fact settles the file question: nothing called runtime files exists outside the installation, so the desktop needs the WinCC 6.2 installation itself.

The project folder is the only engineering deliverable. In a default installation it sits under Program Files/Siemens/WinCC/WinCCProjects, with pictures, scripts, the database and the archive folders inside it. Copy that folder whole. Anything the project references from outside the folder — a picture or script kept elsewhere on the laptop disk — travels separately, on you. Other SCADA packages force the same choice between selected files and the full folder, and the trade-offs are laid out in application deployment: files to copy versus the full folder.

Pick the project type before you configure anything #

The type chosen at creation fixes the station architecture, and changing it later means restructuring the project.

Project type Built for One laptop and one desktop
Single-User Project One station does engineering and operation Choose this
Multi-User Project A server project that several stations work on Only when more operator stations follow
Client Project A station connecting to a project hosted on another station Not this job

Multi-user and client architectures need a reachable, running server project and licensing to match. Two machines where only one operates is a Single-User Project — commit to it.

Deploy the project to the runtime PC #

The full sequence, laptop to desktop:

  1. Install WinCC 6.2 on the desktop PC, the exact version the laptop runs. A project created in a newer version does not open in an older one, so both machines stay on 6.2 until you deliberately migrate.
  2. Open the Automation License Manager on the desktop PC and transfer the WinCC license keys onto it.
  3. On the laptop, deactivate Runtime and close the project in WinCC Explorer, so the database and files are consistent at the moment of copying.
  4. Copy the whole project folder from Program Files/Siemens/WinCC/WinCCProjects on the laptop to the same path on the desktop. The folder, not a single project file — pictures, archives and the database live in its subfolders.
  5. On the desktop, open Start > All Programs > Simatic > WinCC > AutoStart and set it to the copied project folder.
  6. Reboot the desktop. AutoStart activates Runtime with that project at every system start.
  7. If WinCC Explorer reports a computer-name mismatch on the copied project, the project still carries the laptop's name: open the Computer properties in the project on the desktop, set the desktop's own name, and activate.

None of this is a 6.2-only trick; a WinCC project folder runs on another PC without a rebuild in later versions too, so the same copy-and-register steps carry forward when you upgrade.

Where the license sits, and how many you need #

The license is a third object, separate from the software and the project, and it belongs on the machine that activates the project. A key on the engineering laptop does not license the desktop, and the project copy does not carry it. Transfer the keys between machines with the Automation License Manager.

Count the job: 2 WinCC installations (laptop plus desktop), 1 station activating in production (the desktop), so 2 − 1 = 1 key, resident on the desktop. If you also want to activate on the laptop during commissioning, remember the key licenses one machine at a time — move it back and forth, or add a second key only when both stations must activate simultaneously. That is the entire arithmetic; nothing else in this deployment is licensed per copy.

The delivery medium (a yellow diskette in older deliveries, flash media later) is only the carrier the keys shipped on. When that medium is gone, what the license manager accepts instead — manually copied license folders, and which flash media it reads — is covered in license manager behavior for copied license folders and USB/flash media. If the runtime PC is later virtualized, the medium has to reach the VM.

When the copied project will not activate #

  • No license found: open the Automation License Manager on the desktop and confirm the key actually arrived on that machine.
  • Computer-name mismatch: apply the fix from step 7.
  • Project will not open at all: version mismatch — the rule from step 1.

If the runtime PC is reformatted #

A key stored on a disk is tied to that disk: formatting destroys it, and reinstalling WinCC does not bring it back. Reinstall WinCC including the license manager component, look for the medium or backup the keys were moved to before the format, and transfer them back. If neither exists, the remaining route is Siemens support with the certificate of license from the purchase. Before any future format, move the key to a separate medium with the Automation License Manager and return it afterwards.

Questions asked

Can I test on the laptop and run production on the desktop with a single license?

Yes, but only one machine at a time. The key licenses the machine it sits on, so it must be on the desktop while the desktop activates, and back on the laptop only while you activate there for testing. Move it with the Automation License Manager. When commissioning genuinely needs both stations activating at once, that is the point where a second key enters the count.

Our runtime PC stays on the loading screen after a power cut. Is that related to the copy?

No, that is a different failure mode. Activation loads the project database, pictures and archives, and an abrupt power loss can leave the database or the file system inconsistent. Copy the project folder somewhere safe first, run a disk check on the project drive, then read the diagnostic output for the project. Also check that the drive holding the archives is not full and that the PLC answers from the desktop.

Can the desktop run the project without AutoStart?

Yes. AutoStart only registers the project so Runtime activates automatically at every system start; you can activate the same project manually from WinCC Explorer whenever you choose. Keep AutoStart configured whenever the station must come up running unattended after a power restore, because that is precisely the situation it exists for.

Will this deployment stand in the way of a later move off 6.2?

No. The project folder you copied is the input a newer WinCC takes through its project migrator, which is the direction that works: older projects open in newer versions, never the reverse. Migrate on a copy, keep the 6.2 original untouched, then repeat the same copy-and-register steps on the upgraded runtime PC.

Keep reading

  • How-to

    Running a WinCC 7.0 project on another PC without a new build

    No. WinCC has no compile-to-EXE option: the destination PC needs WinCC Runtime of version 7.0 or higher, installed and licensed, and you transfer the project files to it. A newer WinCC opens and converts the project; an older release will not open it.

    HMI and touchscreens

  • Comparison

    WinCC vs WinCC Flexible for small PC SCADA applications

    WinCC Flexible can build a small SCADA application that runs on a PC, but only the Advanced edition does it — Standard stops at operator panels. Treat two decisions separately: the Advanced engineering license buys the PC runtime capability, and each PC that runs the finished application still needs its own runtime license. Beyond single-station scope, the WinCC family is the SCADA tool.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC Runtime Reports Project Is Locked and How to Recover

    "Project is locked" in WinCC Runtime is an ownership conflict, not a license fault: a live session, or a stale ProjectOpened.lck left behind by a crash or power loss, still claims the project. Close every session that could own it, back it up, then clear the lock with reset_wincc.vbs or by removing ProjectOpened.lck; on a client, open the project by its UNC path.