Setting PanelView 600 Time and Date From the SLC Clock

HMI and touchscreens Published 6 min read

Short answer

A PanelView 600 never follows the SLC 5/03 clock on its own: map year, month, day, hour, minute and second control tags in PanelBuilder 32 to six SLC integer words, and move the SLC clock fields into them every scan. When only the year is wrong, compare the displayed year with the register value — a difference of exactly 2000 is the two-digit year, fixed by one add or subtract in the SLC math.

On this page
  1. Why the SLC clock never reaches the terminal
  2. Assign the six control tags in PanelBuilder 32
  3. Move the SLC 5/03 clock fields into those words
  4. Worked example: year word reads 26 while the SLC clock is on 2026
  5. Set the clock by hand when the panel does not follow the SLC
  6. Verify the sync on the running panel
  7. Questions asked

The PanelView 600 never inherits the SLC clock. A healthy link and a correct SLC 5/03 clock change nothing on the terminal: its built-in time and date function reads the terminal's own clock, and only two things write that clock — control tags filled by the controller, or a manual set on the Date/Time screen in Configuration Mode. The fix is six control tags in PanelBuilder 32, one each for year, month, day, hour, minute and second, pointed at six SLC integer words, with SLC logic moving its clock fields into them every scan. Expect one trap: some PanelView and SLC combinations carry the year in two digits, which leaves the terminal 2000 off, and one subtraction tells you whether that is your problem.

Why the SLC clock never reaches the terminal #

The PanelView 600 is a tag-binding terminal: it polls values from the controller and displays what the poll returns. The time and date it shows come from its internal clock, not from that poll. The documented path for a controller to set terminal time is the control tag function — the PanelBuilder 32 reference (publication 2711-GR003D-EN-P) defines control tags as the tags the controller uses to change the current screen, the time, or the date. Until a time and date control tag is mapped and written, the SLC 5/03 and the panel are two independent clocks that happen to share a network.

Do not confuse the sync path with the Time/Date entry among the application settings. That entry formats how the date and time appear on the terminal; it changes what the clock looks like, never where it comes from.

Assign the six control tags in PanelBuilder 32 #

  1. Open the application in PanelBuilder 32 and open Application Settings, then the Control Tags tab.
  2. Create one control tag per field: year, month, day, hour, minute and second.
  3. Point each tag at its own integer word in the SLC. Six consecutive words in the integer file you already use for panel data work fine.
  4. Write the mapping down as a table — year to the first word, month to the second, and so on. The SLC moves must match this table exactly, because a swap here updates every field and still leaves two of them wrong.
  5. Assign all six. A field with no tag keeps whatever the terminal's internal clock last held, which is how a display ends up with a fresh time beside a stale date.

The one-tag-per-field pattern is common across operator panels; configuring day, hour, minute and second clock tags in the PLC walks through the same structure on another terminal family.

Move the SLC 5/03 clock fields into those words #

  1. In the SLC program, read the six clock values from the 5/03's realtime clock in the status file.
  2. Move each field into the word its tag points at, in the order of your mapping table.
  3. Make the moves unconditional so they run every scan. The terminal polls its tags, so the words must hold current values at every poll; a one-shot move leaves every poll after it reading stale numbers.
  4. Keep the transfer one-directional. Never aim a panel write at the SLC clock registers: a timed write from a PanelView into them corrupts the SLC clock, the reverse failure covered in stopping a PanelView timed write from corrupting SLC clock registers.
  5. Watch the six words online until they tick with the SLC clock. Judge the display only after the words are proven live.

Worked example: year word reads 26 while the SLC clock is on 2026 #

Inputs for the bench case, each from a live read:

  • SLC 5/03 clock year: 2026, checked against a known reference.
  • Integer word the year tag reads: 26, read live while the moves run — the SLC side of this combination carries the year in two digits, the case the field warns about.
  • PanelView built-in display: year shows 26.

Rule in words: when the word holds a two-digit year and the terminal takes four digits, add 2000 in the SLC math before the move. In the reverse direction — terminal working in two digits, SLC in four — subtract 2000. One subtraction tells you which case you are in: true year minus word value.

The arithmetic:

2026 − 26 = 2000. A difference of exactly 2000 is the fingerprint of the two-digit versus four-digit mismatch; a wrong tag address does not produce it.

26 + 2000 = 2026. The word now carries the four-digit year the terminal expects, and the display follows on the next update.

Decision: a difference of exactly 2000 means fix the format with one add in the SLC logic (one subtract in the reverse case), not on the terminal screen. Any other difference is a mapping or move-logic problem, and an offset would only hide it.

Set the clock by hand when the panel does not follow the SLC #

  1. Add a temporary button to the application that jumps to the terminal configuration screen.
  2. Select Date/Time from the Configuration Mode menu and reset the date and time, the path the PanelView Standard Operator Terminals User Manual (publication 2711-um014) gives for this.
  3. Return to the application and check the built-in time and date function that originally showed the fault.

One access note belongs here: the same configuration screen holds the terminal's address and other important parameters, so a button left on a production screen lets an operator change far more than the clock. Use maintenance-only navigation and remove the button afterward.

Choose manual only when nothing timestamps against the panel clock. If alarms or datalogging carry timestamps, the SLC is the time source and the tags are the answer. Once the tags are assigned and written, the controller owns the clock, and a manual Date/Time edit no longer sticks. Where a PC rather than the PLC holds the master clock, setting HMI clock time from PC and PLC daily covers the same daily-write pattern for that arrangement.

Verify the sync on the running panel #

What you see Where the fault is What to do
The six words never change with the SLC clock Move logic missing or aimed at the wrong words Fix the moves, then recheck every address against the mapping table
The words tick correctly, the display stays wrong Control tag addresses do not match the words Reopen the Control Tags tab and reassign each tag
Every field matches except the year, off by 2000 Two-digit year meeting a four-digit terminal Apply the offset in the SLC math as in the worked example
Display correct after a manual set, wrong again later Terminal running on its own clock, no tag sync Map the tags, or accept the manual set as scheduled maintenance

Questions asked

Does the PanelView 600 pick up the SLC 5/03 clock once communication is working?

No. The built-in time and date function reads the terminal's internal clock, and the SLC writes nothing to it until time and date control tags are mapped in PanelBuilder 32 and filled by SLC logic. Until then the two clocks run independently, so the display stays wrong no matter how healthy the communication is.

Why fix the year in the SLC logic instead of on the terminal's Date/Time screen?

Because once the six control tags are assigned, the controller is what changes the terminal's time and date. The SLC keeps moving current values into the words, so a manual edit on the Date/Time screen is pulled back to whatever those words hold. If no tags are assigned, a manual set is the legitimate path and it stays until the clock drifts.

Do the SLC moves need to run on every scan?

Yes. The terminal polls its tags and displays whatever the six words hold at each poll, so the words must stay current. A one-shot or event-triggered move freezes the words at old values, and the display follows the frozen numbers while the real clock runs on. Six one-word moves per scan are trivial processor load.

The six words track the SLC clock but the display still shows the wrong time — what next?

Reopen Application Settings and the Control Tags tab and check each of the six tags against your mapping table, one field at a time. A tag aimed at the neighboring word is the usual find: the display updates, but two fields are wrong or one never changes. Also confirm the screen object is the terminal's time and date function rather than a display of the raw words.

Keep reading

  • Troubleshooting

    Stop a PanelView Timed Write Corrupting SLC Clock Registers

    The PanelView's time-status write transmits a two-digit year, so S:37 drops from 2006 to 6 after every update. Point the time and date status tags at an integer file and let ladder logic add 16#2000 to the year before moving the set into S:37 through S:42, or clear the tag entries on the Status Tags tab of the Terminal Setup dialog to stop the write completely.

    HMI and touchscreens

  • Troubleshooting

    Fixing PanelView 600 DH+ errors 208 and 685

    Errors 208 and 685 on a PanelView 600 talking to a ControlLogix 5555 over DH+ are address failures, not cable failures: the HMI requests PLC/SLC file numbers the controller has not mapped. Assign each requested file number a controller-scoped array long enough for every requested element and bit, and skip the BTR/BTW block-transfer logic - it does not fix HMI addressing.

    HMI and touchscreens

  • How-to

    Set a Premium PLC Clock From a Magelis HMI Over Unitelway

    In Vijeo Designer, open the Unitelway equipment in the I/O Manager, add a Dialogue Table with start address %SW50 and the Configure the PLC clock function, and clear the Include editor project option before transfer, because packaging the editor project is what aborts the download with an abnormal program termination. Keep the editable project on the engineering workstation and verify the PLC clock with its own read.

    HMI and touchscreens