Show operator changes in a WinCC V7.0 Runtime audit screen

HMI and touchscreens Published 6 min read

Short answer

WinCC V7.0 shows operator changes to ordinary tags with no extra ActiveX control: copy the table view from the system alarm operation page into a PDL and enable the Operator message property on each tag that must report. Login and logout appear once system messages are on in Alarm Logging. Only User Archive changes need the Audit Viewer 7.2 add-on and its configured audit database.

On this page
  1. Do you need a special ActiveX file for an audit screen in WinCC V7.0 Runtime?
  2. How do you put operator tag changes on a Runtime screen?
  3. How do you add login and logout records to the same table?
  4. What does a User Archive audit need instead?
  5. How do you prove the screen works with a counted test?
  6. Why does the copied alarm table stay empty?
  7. Questions asked

You do not need a special ActiveX file to show operator changes on a WinCC V7.0 Runtime screen. Ordinary tag changes are logged through Alarm Logging and displayed by a table view copied from the system alarm operation page into your own PDL, with the Operator message property enabled on every tag that must report. Login and logout appear once system messages are switched on in Alarm Logging. Only User Archive changes need the separate Audit Viewer 7.2 add-on with its configured audit database. Below is the procedure, a counted test that proves each path, and the fixes for a table that stays empty.

Do you need a special ActiveX file for an audit screen in WinCC V7.0 Runtime? #

No, not for operator changes to ordinary tags: WinCC V7.0 logs them through Alarm Logging, and a table view copied from the system alarm operation page displays them on any PDL screen without an extra control. Only one record source needs extra software: changes to User Archive tags, which the Audit Viewer 7.2 add-on covers. Everything else is displayed by an object the project already owns.

Records you need What displays them What you configure
Operator changes to ordinary tags Alarm table view copied from the system alarm operation page The Operator message property, tag by tag
Login and logout The same alarm table view System messages in Alarm Logging
User Archive tag changes Audit Viewer screen installed by the add-on Audit Viewer 7.2 and its audit database

Whatever the source, a usable audit answer names the tag, the value, the user and the time — the fields that how HMI audit trails record tag changes with user and time explains.

How do you put operator tag changes on a Runtime screen? #

Copy the table view from the project's alarm operation page into your PDL, then enable the Operator message property on every tag whose changes must appear; the property works per tag, so each one needs it. Placing the table alone shows nothing extra — each change must first enter the operator-message path.

  1. Open the project in Graphic Designer and open the system page @Alarm, the alarm operation screen every project carries.
  2. Select the table view on that page and copy it.
  3. Open or create the PDL that will hold the history and paste the table view into it.
  4. In Tag Management, open the properties of each tag an operator can write and enable Operator message.
  5. Save the screen and hook it into the Runtime navigation so operators can reach it.

PCS 7 projects build their audit trail on this same operator-input mechanism, which configuring WinCC operator input messages in PCS 7 audit trails covers for that context.

How do you add login and logout records to the same table? #

Enable system messages in the Alarm Logging editor: logins and logouts travel as system messages, not as per-tag operator messages, so the same copied table shows them once that switch is on.

  1. Open the Alarm Logging editor of the project the Runtime station uses.
  2. Enable system messages and save the configuration.
  3. Start Runtime, log in with a test account, then log out again.
  4. Open the alarm operation page or your copied table and confirm both entries appear in the order you performed them.

The two switches are independent: a working tag-change display proves nothing about login reporting, so test them separately.

What does a User Archive audit need instead? #

User Archive records need the separate Audit Viewer 7.2 add-on: its installation adds an Audit Viewer screen to the ActiveX controls, and the viewer reads the audit database you configure for it. Enabling Operator message on ordinary tags never pulls User Archive records into the alarm table — that data lives in its own audit database.

  1. Confirm the requirement really is User Archive changes; otherwise stay with the alarm-table method.
  2. Install Audit Viewer 7.2 from its media with its license, then the documented update: the readme has you run AuditViewer_V72_00_Upd1.exe from the Support directory on the product DVD.
  3. In Graphic Designer, place the Audit Viewer screen that now appears among the ActiveX controls onto the target PDL.
  4. Configure the audit database the viewer is to read.
  5. Make one controlled User Archive change and confirm its record appears.

The viewer is an installed product component with licensing, media and database configuration resolved as one package — never a loose control file copied and registered from another computer. The Audit documentation also gives the viewer its own Windows-rights requirement for the user running it. In the TIA Portal generation the viewer keeps exactly this optional add-on role, which why the WinCC Audit Viewer is an optional add-on in TIA Portal explains.

How do you prove the screen works with a counted test? #

Run a counted test: five changes on tags with the property enabled must produce five rows, one change on a tag without it must produce none, and a login plus logout must add two. Make the writes with test tags whose values can move without touching the process, or on an offline station — never on a running line.

Example: enable the property on 12 tags and pick 5 of them. Change each of the 5 once from Runtime: 5 changes × 1 message = 5 operator-message rows. Change one tag that has the property off: 1 change × 0 = 0 rows, which proves the selection is selective rather than the table logging everything. With system messages on, log in and log out once each: 1 + 1 = 2 system-message rows. Expected total in the test window: 5 + 0 + 2 = 7 rows.

Note the start time and the account name before the test so those rows can be told apart from live plant alarms.

Why does the copied alarm table stay empty? #

In almost every case the table object is fine and the message never existed — the cause is a per-tag property left off, a message class not admitted, a filter, or a change that no operator made.

  • Tag changes show but no logins: system messages are still off, or a display filter excludes that message class.
  • Logins show but a tag change is missing: that tag's Operator message property is off — check the tag, not the display.
  • Nothing at all: the change came from the controller or a script rather than an operator, so no operator message exists; that is the same gap behind why HMI operation records miss PLC start stop transitions.
  • Older entries gone: the alarm list keeps a bounded number of rows, the reason covered in why WinCC shows only 1000 messages in the alarm list.
  • A blank table is never proof that an ActiveX control is missing; fix the property, the message class or the filter first.

Decide by record source and commit: operator tag changes get the copied alarm table with the per-tag property, login and logout get the same table with system messages on, and User Archive changes get Audit Viewer 7.2 with its configured audit database.

Questions asked

Which Windows rights does the Audit Viewer need?

The WinCC Audit documentation requires the Windows user who runs the Audit Viewer to be a member of the user group SIMATIC HMI; that requirement is documented for Audit V7.5 SP2, so set it for the 7.2 package on your V7.0 station before the first test. A missing membership blocks the viewer independently of database configuration, so add the Runtime account to the group first.

Will a change written by the controller show up in the table?

No. Operator messages record changes an operator makes at the HMI, so a value the controller writes itself never produces one. If controller-side changes must be traced too, log those tags to an archive with logging on change, or configure a message triggered by the tag, instead of waiting for an operator message that will not come.

Is the Audit Viewer included in a standard WinCC installation?

No. Audit Viewer 7.2 is an optional add-on with its own license and installation media, so a plain V7.0 station does not offer the viewer screen among the ActiveX controls until the add-on is installed. Have the license and the media on hand before promising User Archive audits on the operator screen.

Do the records disappear when the operator closes the audit screen?

No. The entries belong to the message system, not to the screen instance, so closing and reopening the PDL leaves them available in the table. Verify this during commissioning by closing the screen after the counted test and confirming the same rows are still shown when it opens again.

Keep reading

  • Troubleshooting

    Why WinCC Runtime Deactivates When the Alarm Report Fails

    Runtime deactivates because the copied project's Alarm Logging message sequence report job has no valid printer or file output on the new PC, and the stored computer name no longer matches. A missing MPI cable does not shut Runtime down. Fix the print job, set a default printer, correct the computer entry, and run Project Migrator on a copy when moving from 6.0 to 7.0.

    HMI and touchscreens

  • Troubleshooting

    Why WinCC 7.5 Runtime Fails Under a New Windows User

    Runtime failing under a newly created Windows account while Explorer opens is a Windows security-context problem, not a WinCC project problem. Put the account in the SIMATIC HMI group, sign out fully, verify effective access to the project, and after an Admin password change update the logon identities of services and scheduled tasks.

    HMI and touchscreens

  • How-to

    How to Show Only a PLC Connection Alarm in WinCC Flexible

    Yes, but on WinCC flexible 2005 you do it with a dedicated application alarm driven by the connection status, not by filtering the system-alarm stream: the 2005 alarm view selects whole alarm classes, not single messages. Decide first whether the operator must see communication loss or a CPU in STOP, since a stopped PLC can still communicate, and keep the unfiltered system-alarm view on a maintenance screen.

    HMI and touchscreens

How to Run makepic for Crimson 2.0 CompactFlash Images