IMDTouchKnowledge BaseShop main store

Explainer

Sizing 18 AWG Wire for a 24 VDC HMI Power Feed

Electrical and power Published 6 min read

Short answer

On voltage drop, 18 AWG is comfortably adequate: a 50 W, 24 VDC terminal draws 2.08 A, and over a 5 ft route, 10 ft of copper out and back, 18 AWG drops about 0.20 V, or 0.85% of 24 V. The gauge is approved only when the terminal documentation accepts it, the DC branch overcurrent device rating matches it under UL 508A Table 38.1, and the measured terminal voltage stays inside the documented input range.

On this page
  1. What the terminal actually draws
  2. Which table governs this DC control feed
  3. Count both conductors or you halve the answer
  4. Worked example: 18 AWG on a 5 ft feed to a 50 W door-mounted terminal
  5. What the voltage drop cannot approve
  6. Wiring the feed to a door-mounted terminal
  7. Verifying the installed circuit
  8. Questions asked

Yes on the arithmetic, with two conditions attached. A 50 W terminal on 24 VDC draws 2.08 A, and a 5 ft route — 10 ft of copper once the return conductor is counted — drops 0.20 V in 18 AWG, 0.85% of the supply and 0.42 W of heat. Electrically that is trivial, and the gauge carries this load with wide margin. But a generic ampacity chart does not approve the wire, and neither does a small drop. In a UL 508A panel the control-circuit conductor is sized from the rating of the overcurrent device feeding it, per Table 38.1, and the terminal documentation has to accept the conductor at its lugs. Pass both checks and install the 18 AWG; fail either one and the fix is 16 AWG or a smaller branch device.

What the terminal actually draws #

The 50 W nameplate works out to about 2 A at the input. That is an estimate from nameplate power, not a measurement and not a guaranteed maximum: the terminal's installation sheet gives the input voltage range, the maximum input demand and any startup behavior, and those figures outrank the estimate. The branch also carries whatever else shares it, so the conductor and its protection are chosen for the branch total, not for the terminal alone. If this feed is part of a broader terminal change, put the power budget in the same plan as the screen and driver choices: planning an HMI terminal replacement.

Which table governs this DC control feed #

Inside a UL 508A industrial control panel, power-circuit ampacities come from Table 28.1, and power-circuit conductors are not smaller than 14 AWG — that floor appears plainly in published UL 508A panel design guides. Your feed is not a power circuit. A DC supply to an operator terminal is a control circuit, so the 14 AWG power-circuit minimum does not reach it.

Control-circuit conductor cross-section is determined from Table 38.1, and the input to that table is the amperage of the overcurrent protective device feeding the control circuit — not the load current. NFPA 79 covers the machine wiring beyond the panel. The ampacity numbers floating around, 10 A and higher for short runs, come from chassis-wiring tables that assume free air and a stated insulation rating; a bundled panel harness inherits none of those conditions. Read the rating off the installed DC branch device. That number plus the table is the approval path, and it is why two panels can honestly reach different answers on the same wire.

Count both conductors or you halve the answer #

Current leaves the supply through one conductor and returns through the other, so the resistance that matters is both. Five feet from a panel-mounted supply to a door-mounted terminal is 10 ft of copper. Eighteen AWG copper runs 9.75 Ω per 1,000 ft at the table's reference temperature, rising about 0.4 percent per degree C of copper warming — immaterial at this current. The common shortcut, counting 5 ft of copper only, gives 0.10 V of drop and 0.21 W of loss: not wrong arithmetic, half the circuit.

Worked example: 18 AWG on a 5 ft feed to a 50 W door-mounted terminal #

Inputs:

  • Terminal power: 50 W at 24 VDC, from the installation documentation.
  • Supply: that voltage, taken at the source.
  • Route: 5 ft one way, panel supply to door-mounted terminal, so 5 ft out plus 5 ft back = 10 ft of copper.
  • Conductor: 18 AWG copper at 9.75 Ω per 1,000 ft.

Rule in words: divide power by voltage to get current; multiply resistance per foot by the total loop feet to get circuit resistance; multiply current by that resistance to get the drop; square the current and multiply by the same resistance to get the heat in the copper.

Arithmetic:

  • I = 50 W ÷ 24 V = 2.083 A
  • R loop = (9.75 Ω ÷ 1,000 ft) × 10 ft = 0.0975 Ω
  • V drop = 2.083 A × 0.0975 Ω = 0.203 V
  • Drop as percent = 0.203 V ÷ 24 V × 100 = 0.85%
  • P loss = (2.083 A)² × 0.0975 Ω = 0.42 W

Result: 0.203 V lost in the copper, 0.85% of the supply, 0.42 W of heat split between the two conductors.

Decision: against a 3% branch drop budget — the usual design target, an informational figure rather than a mandate — 3% of the supply is 0.72 V, and 0.72 V ÷ 0.0975 Ω = 7.4 A before this loop reaches the limit. Your load is under a third of that, so voltage drop does not constrain this feed at all, and that is exactly why the drop number cannot be the approval. Keep the 18 AWG when the terminal's lug range includes it and the DC branch device rating is one Table 38.1 permits for 18 AWG copper. If either check fails, the fixes are 16 AWG or a smaller branch device, chosen by what the panel documentation and the table allow.

What the voltage drop cannot approve #

Three decisions sit outside the 0.85%, and each one can fail while the drop stays tiny:

  • Upstream protection. A small conductor lugged onto a large DC bus through an oversized breaker is unprotected at any load current. The device rating read from the panel is the input to Table 38.1; the terminal's draw never enters that decision.
  • Conductor and insulation. UL 508A panels are typically wired with MTW or UL 1015 hook-up wire, and the insulation temperature and voltage ratings, the panel's internal temperature and how the harness is bundled all move the allowable ampacity away from a bare-chart number.
  • Termination. The terminal documentation states the accepted wire sizes, strip lengths and tightening method; a conductor the lug will not hold is not installed, it is parked.

Isolate the branch and prove zero volts before putting a tool on those terminations.

Wiring the feed to a door-mounted terminal #

The route crosses the hinge, so it flexes every time the door swings. Give the pair slack in an arc, secure it independently to the fixed panel and to the door, keep it off sharp edges and moving hardware, and swing the door through its full travel while watching for pinch points. The equipment grounding conductor is a separate conductor with its own rules: 14 AWG green does not substitute for the DC return, and the DC return does not substitute for ground unless the documentation says so explicitly.

Verifying the installed circuit #

Measure the DC voltage at the source and at the terminal input, during power-up and again running. The difference is the real drop, connection resistance included, and the pass line is the terminal's documented input range, not a percentage you assumed. Record the route length, conductor type and device rating with the panel documentation so the next person does not re-argue the question from charts.

Questions asked

Does the 14 AWG grounding conductor make 18 AWG power conductors acceptable?

No. The grounding or bonding conductor does a different job from the 24 VDC supply and return pair, and its size follows bonding rules rather than the load calculation. A larger ground never compensates for a smaller supply conductor, and the grounding conductor must not carry the DC return unless the equipment documentation says so explicitly.

Why does my calculation show only half the voltage drop?

Because it counted one conductor. A 5 ft route to a door-mounted terminal is 5 ft out and 5 ft back, 10 ft of copper that the current crosses in full. The one-way figure of about 0.10 V is real arithmetic on half the circuit; the loop figure is about 0.20 V. Measuring voltage at the terminal settles the installed result either way.

Is a house rule of 16 AWG minimum for power wiring wrong?

It is neither wrong nor a calculation. It is margin, for terminations, door flexing and future load growth, and a shop standard larger than the minimum is always permitted. The error is treating the house rule, or any generic ampacity chart, as the thing that approves the circuit. The overcurrent device rating and the terminal documentation do that.

Where do the 10 A ratings for 18 AWG come from?

Mostly from chassis-wiring tables that assume free air, a stated insulation temperature rating and short bundled lengths, conditions a control-panel harness does not inherit automatically. In a UL 508A panel the governing number is tied to your branch overcurrent protective device: Table 38.1 for control circuits, Table 28.1 for power circuits.

Does power-up inrush change the wire size?

It changes what you verify, not how the wire is sized. The 2 A figure is steady state from 50 W of nameplate power. Look up the terminal's stated startup behavior, then measure the voltage at its input during power-up; if it dips below the documented minimum input voltage, you have a supply or drop problem to fix, not a reason to guess a larger conductor on faith.

Keep reading

  • How-to

    Designing HMI User Access Levels for Operators and Maintenance

    Build the HMI around three access classes: operators get start, stop, status and recipe selection; supervisors add process parameter and recipe editing; maintenance gets clearly labeled overrides at the highest level. Commission all three with the data bindings by logging in as each class, proving one permitted and one prohibited action, and confirming every override is shown on the overview until returned to normal.

    HMI and touchscreens

  • Explainer

    How an HMI Works in an Industrial Control System

    An HMI displays controller tag values and writes operator inputs back to controller tags; the two paths fail independently. Trace every fault from the live controller tag value, because that one reading splits tag, binding, driver and logic faults cleanly.

    HMI and touchscreens

  • How-to

    How to Size HMI Touch Buttons in a Dense Button Matrix

    On a graphics HMI there is no fixed touch-cell grid: the button you draw is the touch target. Lay out all 42 elements — 32 matrix buttons, 5 feedback displays, 5 navigation keys — with at least a 6 mm gap between touch areas, keep any pixel deadband small, then press every target on the actual terminal before sign-off.

    HMI and touchscreens