Explainer
Unified Comfort panel OPC UA client and server roles in V17
Short answer
From V17, a Unified Comfort Panel offers both an OPC UA server and an OPC UA Data Access client, so it exchanges process data with a third-party controller in either direction. Each connection pairs one server endpoint with one client; two clients cannot talk to each other. Unified PC Runtime adds the connection to OPC UA servers in V17; pick the panel's role from what the controller's specification says it provides.
On this page
- What V17 added to each Unified target
- One server endpoint, one client, per connection
- Read the controller's data sheet first
- Set up the client end and the server end
- Prove the data, not just the session
- Working the roles for one foreign controller and one SCADA
- The decision for each controller case
- Questions asked
From V17, a Unified Comfort Panel carries both an OPC UA server and an OPC UA Data Access client, so a third-party controller on your machine can be reached in either direction: the panel connects out to the controller's server, or a controller-side client connects in to the panel's server. Unified PC Runtime got a narrower addition in V17 — the connection to OPC UA servers, there to couple other controllers — so the client-to-server path is what both targets share. What follows is what each target actually received, the pairing rule that settles the architecture before you open TIA Portal, and how to pick the panel's role from the controller's data sheet.
What V17 added to each Unified target #
For the Unified Comfort Panel, V17 is the release where both OPC UA roles arrive: the OPC UA server and the OPC UA Data Access (DA) client. Both roles come with V17; a panel on an earlier release does not offer them.
Unified PC Runtime's V17 addition is different: a connection to OPC UA servers, there to couple other controllers. That is the client end of the pair. The Comfort Panel is the only Unified target that gained both ends in V17.
| Target | OPC UA role from V17 | Which end of the connection |
|---|---|---|
| Unified Comfort Panel | OPC UA Data Access client | Client — connects out to a server |
| Unified Comfort Panel | OPC UA server | Server — accepts client sessions |
| Unified PC Runtime | Connection to OPC UA servers | Client — couples other controllers |
The rest of the V17 additions for these targets touch visualization, diagnostics, archiving and engineering. None of them configures this connection, so settle the OPC UA role first.
One server endpoint, one client, per connection #
OPC UA is a platform-independent communication architecture, and Data Access is the part that covers current process values together with their status. A server exposes an address space of items. A client opens a session to that server and reads, subscribes to, or writes the items it is permitted to touch. The client initiates; the server listens.
That gives you the pairing rule for any architecture you draw: one server endpoint and one client per connection. Two clients facing each other have nothing to connect to, and two servers do not help, because a server does not start sessions. So every data flow on your drawing needs a named server end and a named client end before configuration starts. The general direction rule, with the client and server cases spelled out, is in HMI OPC UA Server vs Client: Which Direction Works.
Read the controller's data sheet first #
The maker's name on the controller decides nothing; its communication specification does. Open the data sheet or manual, find which of four answers it gives, then map that answer to the panel's role.
| What the controller's specification says | Role for the Unified Comfort Panel | What you check next |
|---|---|---|
| Provides an OPC UA server | DA client | Endpoint address and port, security policy, certificate exchange |
| OPC UA client only | OPC UA server | Which variables to expose, access rights, trusting the client's certificate |
| Client only, while the HMI side would also be a client | No direct connection | A server somewhere: a gateway, a controller option, or the native driver |
| No OPC UA support | No direct OPC UA connection | Native driver or protocol gateway |
If operators must change values on that controller, confirm its server permits writes. An S7-1500 is the comfortable case, because the server sits in the CPU — the reason an S7-1500 needs no SIMATIC PC Station for OPC UA — though a panel holding the native S7 connection will still use that driver for its own screens. For a full third-party walk-through where the controller brings its own server, see Connecting a Windows mobile HMI panel to ctrlX over OPC UA.
Set up the client end and the server end #
Panel as DA client. Take the endpoint from the server's configuration: address, port and path, and make sure any host name resolves from the runtime network. If discovery finds the server but the session fails, compare the address the server advertises with the address the panel can actually reach; a ping proves reachability, not that the OPC UA service answers.
Match a security policy and message security mode that both ends offer. A mismatch is fixed by aligning the two configurations, never by dropping to a weaker policy so a bench connection passes — an unauthenticated endpoint on a running machine is an open door to every tag it exposes. Trust certificates in both directions and check the device clocks: a certificate that is valid on paper fails outside its validity window, and a panel clock set to last year rejects a good certificate. Open the session with an authorized identity and read the diagnostics it returns before touching any tag.
Panel as server. Activate the server in the panel's configuration, provide the certificates of the systems that will connect as OPC UA clients — an engineering station, a SCADA, a controller-side client — and decide which variables the server exposes and with what access rights. If both sides hold certificates the other does not trust, the session never opens; Why an OPC UA Trust Loop Fails on a Unified Comfort Panel walks through that failure.
Check versions as separate items: the engineering project's release, the configured target, and the runtime or panel image on the device must form a supported combination. A successful download proves the project reached the device — not that an external OPC UA session opens or that the values carry good quality.
Prove the data, not just the session #
An open session can still deliver unusable values, because every OPC UA value carries a status and the quality is part of it; a number standing still on the screen can be a bad-quality value the display keeps repeating. Once the session is up, check four things:
- The item's node identifier matches the configuration — a node identifier uniquely addresses an item in the server's address space, and display names alone may not be unique.
- The server variable's data type and the HMI tag's type are compatible, with the intended range and scaling.
- Quality is good while the source value changes, and the screen follows it.
- A write to a designated test variable succeeds and reads back, tested separately because a readable item can still be read-only.
Run that write test on an isolated bench with verified test tags, never against a running machine's command path. The write proves data access; it says nothing about the interlocks behind the variable.
Working the roles for one foreign controller and one SCADA #
This is the plant builder's case: one Unified Comfort Panel on the machine, a foreign controller that may appear on the next order, and a plant SCADA above it that collects data as an OPC UA client. Work the roles on paper before opening the engineering tool.
Inputs. One Unified Comfort Panel with the V17 feature set, so both roles are available. One foreign controller whose data sheet lists an OPC UA server — a typical case for this topic, so swap in your own controller's answer. One SCADA that connects as an OPC UA client, the usual arrangement for plant-level collection.
Rule. Each connection pairs exactly one server endpoint with one client. Count the ends each device offers, pair them one to one, and the number of pairs is the number of connections you can build.
Arithmetic. Flow A, controller values onto the panel: the panel offers 1 client end and the controller offers 1 server end, so 1 pair and 1 connection, with the panel as DA client. Flow B, the SCADA collecting from the panel: the SCADA offers 1 client end and the panel offers 1 server end, so 1 pair and 1 connection, with the panel as server. Together that is 2 connections and 4 ends, each connection holding exactly one server end. Counter-case, a controller that is a client only: panel client plus controller client plus SCADA client gives 3 client ends and 0 server ends on the controller path, so 0 pairs and 0 connections — and no certificate or address edit changes that count.
Result. The panel runs both roles at once: DA client toward the controller, server toward the SCADA.
Decision. Build it exactly this way whenever every flow shows one server end and one client end. The moment a path counts 0 server ends, stop at the data sheet and choose a gateway or the native driver before any engineering work — that threshold comes ahead of endpoints, certificates and tags.
The decision for each controller case #
- The controller provides an OPC UA server: configure the panel as DA client, or use PC Runtime's client connection, then move to endpoint, security policy and certificates.
- The controller is an OPC UA client only: the panel is the server; expose the variables it needs, set their access rights and trust its certificate.
- Both ends would be clients: there is no direct connection; put a server in the path with a gateway, or use the controller's native driver.
- The controller has no OPC UA at all: native driver or protocol gateway, because no amount of OPC UA configuration creates the missing end.
The role comes from the controller's specification, the pairing rule is one server endpoint with one client per connection, and from V17 the Unified Comfort Panel can take either end.
Questions asked
Does the panel's V17 OPC UA server carry alarms as well as process values?
Alongside Data Access, the Unified OPC UA stack also includes an Alarms and Conditions (A&C) server. It provides the alarms from WinCC alarm management to one or more OPC UA A&C clients, according to the V17 architecture documentation. A client that only needs current values uses the DA side; anything that must react to alarm states connects to the A&C server instead.
How many remote web clients can operate a Unified Comfort Panel in V17?
Browser-based remote operation is new for the panel in V17. One web client is included, and up to two additional web clients can be unlocked with a license, so three remote browsers at most. This is separate from the OPC UA roles: the web client serves operators, the OPC UA server serves data consumers, and neither one licenses the other.
Can I run the panel's OPC UA server with security policy none to skip certificate handling?
The server can be activated with security policy none, which runs it without certificates. Do that only on an isolated bench for a first function check. Security policy none removes encryption and authentication, so on a running machine any host that reaches the endpoint can read or write whatever the server exposes. Switch to a certificate-based policy with message security before the machine goes back to work.
What else did V17 bring to the Unified targets besides the OPC UA roles?
The Comfort Panel gained an F(x) control for displaying profile curves, plus a system diagnostics view showing S7 system messages and the plant architecture. PC Runtime gained styles for switching between day and night mode and a new SQL version with an Audit option for archiving. Collaboration was extended to work with Unified Panels as well. None of these features configures the OPC UA connection.