What a C-more CM5 9.02 Update Changes for Old Projects

HMI and touchscreens Published 6 min read

Short answer

C-more CM5 V9.02 is a maintenance release that converts EA9 v6.80 and CM5 v8.26 projects. Treat the update as a conversion: archive the original source, work on a copy, and retest screens, communications and alarms before any panel download.

On this page
  1. What V9.02 changes
  2. Check the project version before the update
  3. Archive the original project
  4. Convert a working copy in V9.02
  5. Worked example: converting an EA9 v6.80 project with CM5 V9.02
  6. Retest before any panel download
  7. If you are replacing the EA9 panel too
  8. Questions asked

C-more CM5 software V9.02 is a maintenance release: it clears the defects reported since Version 9.0, adds a few minor enhancements, and its release information names EA9 v6.80 and CM5 v8.26 as the project versions it converts. Treat the first open in that editor as a conversion, not an install formality: the editor rewrites an older project into the CM5 panel format. Archive the original with its version recorded, convert a working copy, and prove screens, communications and alarms on that copy before anything reaches the production panel. Below are the version checks, the conversion steps and a worked EA9 conversion example.

What V9.02 changes #

The vendor describes V9.02 as a maintenance release focused on the stability and performance of the C-more V9 software, resolving the defects reported since Version 9.0 along with a few minor enhancements. The short announcement does not itemize those defects; the full release notes published with the download do. If a specific V9.0 fault is the reason for your upgrade, match that symptom against the release notes first rather than assuming a maintenance release touches it.

C-more CM5 software is AutomationDirect's configuration package for its CM5 HMI panels. The conversion statement covers project files only: it does not by itself confirm panel-model support, runtime compatibility or a download procedure, and those come from the CM5 product documentation. The Version 9.0 notes had already announced conversion of EA9 and CM5 V8 project files and quoted a runtime up to 250% faster at rendering complex screens — the vendor's figure rather than a bench measurement, but it is why performance-minded shops moved to the V9 line.

Check the project version before the update #

Read the source editor and its version from the project record, or open the project in whichever editor owns it and read the version there. Three branches follow:

  • EA9 v6.80 — converts. CM5 V9.02 opens it and converts it to the CM5 panel type.
  • CM5 v8.26, or another save from the CM5 V8 line — converts; the Version 9.0 notes already covered CM5 V8 files.
  • Anything older — not covered by the announcement. For EA9 sources the practical floor reported in the field is Version 6.72: projects saved at V6.72 or earlier do not convert directly. Open the project once in the final EA9 editor release, save it, and convert the re-saved file.

If no source file exists and the program lives only in the panel, read it back before planning anything else; recovering an HMI program when the source file is lost walks that path. Budget for rebuilding either way, because an uploaded HMI copy is not an editable project.

Archive the original project #

Copy the project file to a second location and leave the original untouched. Record the source editor, version and save date beside it in one line — for example: CM5 editor, v8.26, saved 14 March 2024 — so whoever opens the archive later knows what owns that file. Then open the archive once in the old editor to prove it launches before you convert anything.

The archive matters because there is no comparison tool to fall back on: HMI projects have no online/offline comparison against the panel, so the untouched file is the only true pre-conversion reference, and that file plus the currently running panel are your rollback pair.

Convert a working copy in V9.02 #

Run the conversion on a copy, never on the archived original:

  1. Install CM5 V9.02 from the vendor's C-more software download page, reading the version number on the package before installing; take the download only from that official page.
  2. Make a working copy of the archived project file and open only the copy in the new editor.
  3. Accept the conversion prompt, and save the converted project under a new name — append something like -cm5 to the old name so the two files never blur.
  4. Read every conversion message the editor reports, and resolve or note each one; a file that merely opens is not a file that converted cleanly.
  5. Walk every screen: object positions, fonts, navigation targets, and every object the converter flags as changed.
  6. Open the communications setup and confirm each driver, controller address and port survived the conversion.
  7. Exercise the alarm configuration: trigger tags, messages, acknowledgement, and where the banner sits on each screen.

If the editor reports an error the release notes do not explain, stop and keep the archived original as the working project; do not keep converting the same file expecting the message to clear.

Worked example: converting an EA9 v6.80 project with CM5 V9.02 #

Inputs #

Four inputs set the case:

  • Source project: a packaging-line HMI program last saved in EA9 software Version 6.80, read from the project record in the EA9 editor.
  • Editor: C-more CM5 software V9.02, the release under discussion.
  • Target: a CM5 panel picked from the CM5 product documentation, since the conversion statement names no panels.
  • Non-converting floor for EA9 sources: Version 6.72, as reported in field discussion of the EA9-to-CM5 move.

The rule #

Version 9.02 converts EA9 projects saved at v6.80 and CM5 projects saved at v8.26, and the editor converts an EA9 project to the CM5 panel type when it opens it. A source below the floor does not convert directly; it needs one re-save from the final EA9 editor release first.

The arithmetic #

Compare the project's save version against the announced set and the floor:

  • 6.80 against the announced EA9 convertible version, 6.80: 6.80 = 6.80, so the project sits inside the announced set and converts on open.
  • Floor check: 6.80 > 6.72, so it clears the reported non-converting floor with one version step of margin.
  • Counter-case, a sister line whose project was last saved at V6.72: 6.72 is not greater than 6.72, so it sits below the line — re-save from the final EA9 editor release, then convert the new file.

Result and decision #

The editor hands back a CM5-panel project, which you save under the new name; the original EA9 file stays archived and untouched. Decision: bench-test the converted copy before any download — screens render, every driver connects, alarms trigger and clear, and each write lands on its intended tag. Pass: the copy becomes the CM5 panel's project. Fail anywhere: roll back to the archived EA9 project, leave the EA9 panel running the line, and work out the failure on the bench.

Retest before any panel download #

A converted project is new software on a machine that moves, so prove it on an isolated bench with the controller away from production — never as a first download onto the panel running the line. The bench list: every screen at the target panel's dimensions, one full navigation loop, each driver connecting and updating live values, alarms triggering and clearing, and every write button proved against bench tags rather than plant outputs. Pull the communications cable once and watch how the driver reports the loss and how the screens recover when it returns.

Before the download, confirm which project version the panel is actually running so the download replaces it deliberately — verifying the HMI project version on a panel shows the check. Keep the previous production project available until the converted one has run a full shift without a fault.

If you are replacing the EA9 panel too #

Conversion usually travels with a hardware swap: the EA9 panel line is reported to be at end of life, and CM5 is the family that replaces it. The swap is not drop-in mechanically — the 10-inch CM5 does not use the same hole pattern as the 10-inch EA9, so an existing door cut-out must be checked before a panel is ordered or metal is cut. Compare the old opening against the new dimensions in the panel cut-out reference before the swap, not after the hole is already cut.

Questions asked

Will the converted project still run on the EA9 panel?

No. The CM5 editor converts an EA9 project to the CM5 panel type when it opens it, so the converted file downloads to CM5 hardware only. The untouched EA9 source file and the EA9 editor remain the pair that serves the existing EA9 panel; keep both until the CM5 panel and the converted project have passed your bench tests.

How far back can an EA9 project be and still convert?

The release names EA9 v6.80. The reported floor is Version 6.72: programs written before May 9, 2022, in that firmware era or earlier, do not convert directly. Re-save such a project once from the final EA9 editor release before the CM5 conversion can take it.

How do I copy single screens between an EA9 project and a CM5 project?

Use the Screen Library. It exists in EA9 software from Version 6.75 and in CM5 V8-series software, and it is the supported way to move individual screens between the two families when you are consolidating machines instead of converting a whole project.

Is CM5 V9.02 faster than Version 9.0?

The Version 9.0 release notes claim a runtime up to 250% faster at rendering complex screens, and 9.02 continues that line with stability fixes. Treat the figure as the vendor's own number rather than a bench result; if render speed is why you are upgrading, time your densest screen before and after the move.

Keep reading

  • Troubleshooting

    Working around the C-More EA9 alarm banner covering buttons

    No. The C-More EA9 alarm message banner has no position setting: it is fixed at the bottom of the screen, and while an alarm is active it overlays every screen in the project. Reduce the banner height, move page-change buttons above the banner band on every screen, and verify each one with a live alarm showing.

    HMI and touchscreens

  • How-to

    Convert an MT500 Project to EasyBuilder 8000 and Resize It

    EasyBuilder 8000 converts an MT500 .eob into a new .mtp project through the Tools menu; the converter selects the terminal with the nearest dimensions, so you must then select the real destination model on the Model tab and work through the resize dialog it triggers. Verify page geometry and live controller data before the panel returns to service.

    HMI and touchscreens

  • How-to

    Open a legacy Vijeo Designer project in version 6.2

    Open the project in the release the error names — Vijeo Designer 4.7 in this case — compile and save it there, then climb release by release until 6.2 opens and builds it. Only then change the target to HMIGTO6310, configure Unitelway, and choose one documented transfer route.

    HMI and touchscreens

Displaying a Do-More String on a C-More EA9 Panel