Where the Weintek USB Driver Prompt Gets Its Files
Short answer
Windows asks for a disk because its automatic search cannot match the terminal. The files already sit on the PC: point the new-hardware wizard at the usbdriver folder inside the EasyBuilder8000 installation directory, typically EB8000\usbdriver under Program Files. The Netlog link on COM1 needs three crossed conductors to the RJ45: pin 5 RxD, pin 6 TxD, pin 4 GND.
On this page
The wizard is not asking for a physical disk. The USB driver files were copied to the PC when EasyBuilder8000 was installed, and Windows asks for them only because its automatic search never looks inside that folder. Decline the search, browse to the usbdriver folder in the EasyBuilder8000 installation directory, typically EB8000\usbdriver under Program Files, and the terminal binds. The second half of the job is the Netlog link: three crossed conductors from the terminal's COM1, a 9-pin male D-sub on the back of a 6070iH, to the Netlog port A RJ45, where pin 5 is RxD, pin 6 is TxD and pin 4 is ground.
Why Windows asks for a disk #
When the terminal enumerates on USB, Windows reads its vendor and product IDs and searches for a matching INF file. The EasyBuilder8000 installer places the driver files in a usbdriver subfolder of the installation directory but does not register them with the Windows driver store, so the automatic search finds nothing and the new-hardware wizard offers a disk or a location. No separate driver disk ships with the terminal. Connecting the cable before the software is installed gives the same prompt, because the folder does not exist on the PC yet.
Install the driver from the usbdriver folder #
- Install EasyBuilder8000 first, from Weintek's official download, if it is not already on the PC.
- Power the terminal and connect the USB cable between it and the PC.
- When the wizard appears, decline the automatic online search and choose the option to specify a driver location yourself.
- Browse to the usbdriver folder inside the EasyBuilder8000 installation directory; the typical path is EB8000\usbdriver under the Program Files directory. On a 64-bit Windows system the installer may have used the x86 Program Files directory, so check both locations.
- Accept the driver and finish the wizard.
- Open Device Manager and confirm the terminal appears among the managed devices with no warning icon.
A listed device with no warning marker means the driver bound. An entry under unknown devices means the wizard was closed early or the wrong folder was chosen: right-click the entry, update the driver, and repeat the location step. If the usbdriver folder is missing from the installation, the same procedure is documented in the EasyBuilder8000 online help, chapter Q&A, entry "How to install Weintek USB driver".
What the USB link carries #
With the driver bound, USB is the project transfer channel: EasyBuilder8000 downloads and uploads over it once the terminal is in its transfer-ready state. That channel is separate from the device link, because the terminal talks to the Netlog module on COM1 no matter how the project arrives, and the distinction is the one drawn in separating HMI transfer method from PLC driver selection. If the driver is bound and a transfer still fails, work the PC and the cable first; the case where an HMI fails USB transfer from a USB 1.0 PC is one documented example.
Wire COM1 to the Netlog RJ45 #
RS232 is a point-to-point, single-ended link: each transmitter drives its signal against a common ground, so three conductors carry it when no handshake lines are used. The Netlog port A RJ45 female provides these signals:
| Netlog RJ45 pin | Signal | Connects to terminal COM1 |
|---|---|---|
| 5 | RxD | Terminal TxD |
| 6 | TxD | Terminal RxD |
| 4 | GND | Terminal signal ground |
Cross the data lines: the terminal's transmitter feeds the Netlog receiver and the reverse. A straight-through data pair passes a continuity test but never communicates, and it damages nothing. When both conductors look identical, the technique for identifying RxD and TxD in RS232 wiring settles which is which. Read the DB9 pin numbers for TxD, RxD and ground from the terminal's own documentation: Weintek publishes an HMI pin assignment document that lists COM1 (RS232, 9-pin male D-sub) per model, and the connector carries several modes on different pins, so a generic PC serial pinout does not apply.
Worked check on the finished cable, with example readings from a meter set to resistance: terminal TxD pin to Netlog pin 5, 0.4 Ω; terminal RxD pin to Netlog pin 6, 0.4 Ω; ground to Netlog pin 4, 0.3 Ω; each of the three conductors to the D-sub shell, open. Score it as arithmetic: 3 of 3 signal paths near zero ohms and 0 of 3 shell shorts, so this cable passes and can be powered. The ohm values are illustrative; what decides the case is near-zero versus open.
Close-out checks #
Do not apply power until the worked check above passes: three continuous paths and no short to the shell. Then confirm the settings:
- In the EasyBuilder8000 system parameters, set the COM1 mode to RS232.
- Match baud rate, data bits, parity and stop bits between the EasyBuilder8000 device settings and the Netlog serial configuration; a framing or parity mismatch looks like a wiring fault, with corrupted or absent replies on a correct cable.
- Download a project with a numeric object tied to a Netlog address over USB and confirm the value updates. If it stays silent, swap the two data conductors at one end and retest, then compare the serial parameters.
The three failures seen most often on this job: the cable connected before the software was installed, a patch cable whose RJ45 pin order differs from the Netlog table, and a project whose COM1 is not in RS232 mode.
Questions asked
Does the 6070iH come with a driver CD?
No. The USB driver files are copied to the PC during the EasyBuilder8000 installation, so the software package you already have is the driver source and there is no separate disk to obtain. If the wizard still prompts for files, the folder was simply not matched automatically.
What if the usbdriver folder is not in the installation directory?
Reinstall EasyBuilder8000 from Weintek's official download, which recreates the folder with the driver build that matches that software version. The online help chapter Q&A, entry named How to install Weintek USB driver, documents the same installation steps if you need them in print.
Can the USB link and the Netlog RS232 link run at the same time?
Yes. They are independent channels: USB carries the project download and upload between the PC and the terminal, and COM1 talks to the Netlog module. You can download the test project over USB and watch the Netlog value update in the same session.
What happens if I wire the data lines straight through?
Nothing is damaged, and nothing communicates. A TxD to TxD connection leaves both receivers unconnected, so continuity still passes but no reply ever arrives. Swap the two data conductors at one end of the cable, confirm the serial parameters match on both ends, and retest.
The terminal still shows as an unknown device after pointing at the folder. Now what?
Repeat the location step once using a different USB port and a different cable, checking both Program Files directories for the usbdriver folder. If it still fails, reinstall EasyBuilder8000 from the official Weintek download. If that does not clear it, contact Weintek or its distributor support with the exact terminal model and the EasyBuilder8000 version.