Where to enter Sm@rtServer credentials in WinCC Runtime Advanced
Short answer
Enter the remote user and password in Windows Control Panel under WinCC Runtime Advanced Internet, on the Remote tab, behind Change Settings in the Server tab of the dialog that opens. The Sm@rtServer checkbox in the project's runtime settings only enables the server. Record the listening port shown there and use it with the PC's address in Sm@rtClient.
On this page
The user and password that Sm@rtClient presents to a WinCC Runtime Advanced PC are not entered anywhere in the engineering project. They go into Windows on the runtime PC: Control Panel, the WinCC Runtime Advanced Internet applet, Remote tab, behind Change Settings in the Server tab of the dialog that opens. The Sm@rtServer option in the project's runtime settings only enables the server function, which is why ticking it leaves you with no field for credentials. The same dialog shows the listening port, and that recorded number, not an assumed default, is what Sm@rtClient targets together with the PC's address. A Comfort panel keeps the equivalent settings in its own Control Panel; a PC runtime is configured in Windows.
Where these credentials live #
Three different passwords can be in play on one runtime PC, and only the first one opens the remote session:
- Sm@rtServer connection user and password: stored by Windows under WinCC Runtime Advanced Internet, Remote tab. This is the credential this procedure configures.
- Project operator accounts: created in the project's user administration; they decide what a logged-in operator may press on the screen. They are a separate mechanism, covered in how to manage WinCC runtime user accounts and password changes.
- The Web Server tab password: set through User Administration for the SIMATIC HMI HTTP Protocol, a web function. It plays no role in a Sm@rtClient session.
A valid remote login therefore does not authorize a protected button, and a correct operator password will not open a remote session. When a Comfort panel shows no Remote tab at all, that is a different fault, covered in fix for a Comfort panel with a missing Sm@rtServer Remote tab.
Enable Sm@rtServer in the runtime project first #
Do this once, in the engineering tool, before touching the PC-side dialog:
- Open the runtime settings of the PC project and enable Sm@rtServer. No user or password is requested there; the switch only permits the server function.
- Load the updated project to the runtime PC with your normal transfer procedure, and restart the runtime if the installed release calls for it.
- Confirm locally that the intended screens run on that PC. A remote session can only display what the runtime is executing, so a wrong or stale project shows up remotely as the wrong screen.
With the option enabled and the project running, the rest of the configuration happens in Windows, on that same PC.
Enter the remote user and password in Windows Control Panel #
- Work at the PC that executes WinCC Runtime Advanced, not the engineering workstation, and open Windows Control Panel.
- Open WinCC Runtime Advanced Internet. If the applet is missing, the remote components of that runtime release are not present; install or repair them per the documentation of your release before continuing.
- Select the Remote tab.
- Tick "Start automatically after booting" so the server comes back after restarts and power cycles.
- Click Change Settings, and in the Server tab of the dialog that opens, enter the remote user and password, the same kind of entry a Comfort panel takes in its own Control Panel.
- Read the port shown in the same dialog and write it into the commissioning record. Enter exactly that number in Sm@rtClient; a correct password still fails against the wrong port.
- Confirm the dialog and follow the instruction it displays about when the change takes effect.
That dialog is the whole answer to where the password goes: user and password in the Server tab, port read from the same place, automatic start ticked on the Remote tab itself.
Point Sm@rtClient at the PC runtime #
- Read the active IPv4 address of the runtime PC from its own network configuration, not from a panel and not from the engineering PC.
- In Sm@rtClient, create a connection to that address with the recorded port, and supply the user and password from the Server tab.
- Connect and confirm the session shows the same screens the PC displays locally.
Worked example with illustrative values #
Take a runtime PC at 192.168.10.24 whose dialog shows port 4410, and a client device at 192.168.10.55 with mask 255.255.255.0. The port and addresses are examples; your dialog and your network supply the real values.
- Client network: 192.168.10.55 AND 255.255.255.0 = 192.168.10.0
- Server network: 192.168.10.24 AND 255.255.255.0 = 192.168.10.0
- Same subnet, so no router is involved; a TCP reachability test to 192.168.10.24:4410 must succeed before any password is evaluated.
- Firewall: scope one inbound rule to TCP 4410 from 192.168.10.0/24 instead of widening access to the whole host.
Decision for this example: Sm@rtClient gets address 192.168.10.24, port 4410 and the Server-tab credentials, and nothing from a panel's configuration carries over. A remote session operates the machine exactly as the local screen does, so keep that port on the approved plant network or an approved secure remote path, never forwarded from the public Internet.
When the connection still fails #
Separate transport failures from authentication failures before changing anything:
| Symptom | First check | Fixed when |
|---|---|---|
| Timeout, no server reached | PC address, recorded port, runtime running, firewall scope, network path | A TCP test to the PC and port opens |
| Credentials rejected | Re-enter user and password in the Server tab, then repeat the same values in the client | The session opens |
| A different HMI screen appears | The client is pointing at a panel or another host | The display matches the PC's local screens |
| Session opens, an operation is denied | Project operator login and permissions for that function | The authorized operator can operate it |
Re-entering passwords does not repair an unreachable endpoint, and editing firewall rules does not fix a rejected password. A refusal that survives correct credentials and an open port has causes of its own; the diagnosis in why Sm@rtServer rejects Sm@rtClient on a WinCC Runtime PC covers them.
Close out by writing three lines into the commissioning record: the runtime PC's address, the port from the Remote dialog, and where the credentials are stored. The next technician then configures a client without opening the panel or the project.
Questions asked
Is the Sm@rtServer password the same as a WinCC runtime user account?
No. The user and password stored under WinCC Runtime Advanced Internet only open the remote session and live on that PC outside the project. Operator accounts from the project's user administration decide what a logged-in operator may do on the screen. Changing project users never changes the remote password, and a valid remote login grants no rights to a protected function.
Which port does Sm@rtClient use to reach the PC runtime?
The port displayed in the same Remote settings dialog where the credentials were entered. It belongs to that PC's configuration, not to the engineering project, so record it during commissioning. Use the identical number in the Sm@rtClient connection and in any firewall rule scoped for the service, because a correct password still fails when it is sent to the wrong port.
Why tick Start automatically after booting?
Without it the remote service can stay down after a restart, a Windows update or a power cycle until someone starts it at the PC, while every client times out and the local runtime looks healthy. Ticking it during commissioning is what keeps Sm@rtServer reachable after outages without walking to the machine.
Where do you enter the same credentials on a Comfort panel?
In the panel's own Control Panel, in the equivalent Remote settings, because a panel has no Windows Control Panel. Each device stores its own remote user, password and port, so values configured on a Comfort panel do not carry over to a PC runtime; configure and record each server separately.
Can a phone run Sm@rtClient against the PC runtime?
Yes, with the same three inputs: the PC's address, the recorded port and the credentials from the Server tab. The phone also needs a real network path into the runtime subnet; joining a plant Wi-Fi does not by itself guarantee routing to the industrial network, so test reachability to the PC and port before blaming the password.