Where to Set HMI Project Version and Author in Vijeo Designer
Short answer
Vijeo Designer has no equivalent of Machine Expert's Project Information option, and opening both projects together transfers nothing: the HMI shows PLC metadata only if the PLC writes it into variables. Put the HMI release designation and author on a dedicated information screen as fixed text, archive the source under the same number, and read the screen back on the panel after every download.
On this page
Vijeo Designer has no counterpart to the Project Information option that Machine Expert offers in the Tools tree, so you are not looking in the wrong place: the release version and author of the HMI application do not live in a metadata screen on the HMI side. Opening the HMI project alongside the PLC project does not transpose them either. Schneider Electric's published FAQ (FAQ000246185) closes the runtime end of the question: no internal variable gives access to the project revision number or the build time, so the display path is one you build. The method that always works is a dedicated information screen with fixed text for the release designation and the author, updated at every delivery and read back on the panel after download.
What each tool actually records #
In Machine Expert, the Project Information option in the Tools tree tab is where the PLC project's author and release version are entered. That is PLC-side identity, and it stays with the PLC project.
Vijeo Designer organizes things differently. In the Navigator window's Project tab you select the Target node and read its settings in the Property Inspector, and the Remote Management settings for remote access are configured there, for example. Those properties describe the target and its services, not the delivered application, and the release identity of the application is not set among them. The FAQ adds the hard limit: even the revision number the project itself carries is unreachable at runtime, because no internal variable exposes the revision number or build time to a display object. Act on the consequence now: stop searching for a metadata screen and place the identity where you control every pixel, on a screen.
Why the PLC values never arrive on the HMI #
A shared workspace is not a data path. Runtime communication between the controller and the panel moves the variables configured for exchange, and engineering metadata is not one of them. Machine Expert's Project Information values reach an HMI display only if the PLC program writes them into variables the HMI reads, which is a deliberate configuration maintained at every PLC release and a separate decision from identifying the HMI build.
So the second guess in the question is also no: linking the projects, or opening one from inside the other, transfers nothing. Treat the PLC author and version as PLC-only. The HMI gets its own designation, because the two projects are updated on different schedules and a single shared label would misdescribe one of them most of the time.
Build the information screen #
- Add a screen to the HMI project reserved for release information, reachable from the project's normal navigation; a button on a setup or maintenance menu is enough.
- Place fixed text objects, not variable displays: one line for the HMI release designation, one for the author or responsible group. Fixed text needs no variable and no controller, so the identification stays readable with the PLC down or the link lost.
- Keep the screen read-only, text only and no write objects, so it can sit in operator navigation without access protection.
- Give the engineering tool version its own labeled line if it belongs on the screen at all, and never let it share the release line.
- Add the PLC release as a separate labeled line only if the PLC program writes it to variables the HMI displays; it then arrives as configured data, not because the projects are linked.
- Change the release string at every delivery and write the same value into the release record.
Keep the tool version out of the release number #
The tool version has a different job: it decides whether a project opens, because Vijeo Designer is not backward compatible and a project created in a newer version cannot be saved down to an older one. A disagreement between tool and project builds surfaces as a version mismatch, and fixing a Vijeo Designer project version mismatch by updating the build is a repair job with no connection to your release string. Your designation tracks delivered changes to the HMI application; the tool version tracks the software that produced it. Mixing the two on one line guarantees a wrong answer the first time either side moves.
Worked example: two deliveries, one string #
Example scheme, clearly illustrative, since the numbering rule is a working convention and not a vendor requirement: the HMI release counts major.minor, with the minor value +0.1 per delivered change to the HMI application and the major value +1 when the target model or the communication setup changes.
The panel in the field currently shows:
- HMI release: 1.4
- Author: Controls engineering
Two deliveries follow, each adding screens. The next designation is 1.4 + 2 × 0.1 = 1.6. Exactly one object changes: the release line becomes "HMI release: 1.6". The author line is untouched, the source is archived under a name carrying 1.6, and the release record gains the same value.
Acceptance is a read, not an assumption. After download, open the information screen on the actual panel and confirm it says 1.6; a number that exists only in the engineering tool has not been verified. The PLC project meanwhile carries its own Project Information value, release 3.1 in this example, and it appears nowhere on the HMI because nothing was configured to carry it.
Close the loop in the archive #
Name every archived source with the designation shown on the panel, and record which tool version built it alongside. The archive has to open years later, and HMI project recovery and backup when a project fails to open depends on that discipline. The label on the panel and the name on the archive are the two ends of one identification; keep them equal and any unit in the field can be matched to its source in minutes.
The decision, case by case #
- Identity needed in the engineering record only: name the project archive and the release record with the designation. There is no in-tool Project Information field to rely on, so the file system carries it.
- Identity visible on the machine: the information screen with fixed text. This is the default; build it even when nobody asked, because it costs one screen and answers the question at the panel.
- PLC version and author on the panel: only as configured PLC variables on a separately labeled line, never as a stand-in for the HMI's own release.
Questions asked
Does the HMI inherit version and author from the PLC project when both are open together?
No. Machine Expert's Project Information stays with the PLC project. The panel shows nothing from it unless the PLC program writes those values into variables the HMI is configured to read, and that is a per-release configuration you maintain deliberately, not an automatic transfer.
Can a display object show the Vijeo Designer project revision number or build time automatically?
No. Schneider Electric's FAQ FAQ000246185 documents that Vijeo Designer has no internal variable giving access to the project revision number or build time, so no display can be bound to them. Fixed text on an information screen is the supported way to show release identity at runtime.
Where do target-level settings live, if not in a project information screen?
In the Navigator window's Project tab, select the Target node and read the Property Inspector. The Remote Management settings for remote access are configured there, for example. These properties describe the target and its services; none of them sets the author or release designation of the application.
Should the release line include the engineering tool version?
No. The tool version identifies what built the project and decides whether it opens, and Vijeo Designer is not backward compatible, so a newer project cannot be saved down to an older tool. Your designation tracks delivered HMI changes. Show the tool version on its own labeled line if it helps support.
Is there any way to make Vijeo Designer number releases automatically?
No documented facility numbers HMI deliveries, and the revision number the project carries cannot be displayed at runtime. The convention is yours to define: a major.minor count of delivered changes works well, with the release string set by hand at each delivery and mirrored in the archive name.