Which programming software a Twido PLC and Magelis HMI need
Short answer
A Twido controller is programmed with TwidoSuite or TwidoSoft, and a Magelis terminal with Vijeo Designer, Vijeo Designer Lite for the small XBTN and XBTR panels, or XBTL1000 for older models. The full nameplate reference and any existing project format make the selection, and every package is licensed software from Schneider Electric or an authorized distributor.

On this page
- Which software programs a Twido controller?
- Which software programs a Magelis terminal?
- Which Magelis panels does Vijeo Designer Lite manage?
- How do you pick the tools for one machine?
- Where do you get TwidoSuite, Vijeo Designer and XBTL1000?
- Can one tool program both the controller and the terminal?
- What if the terminal is not on the list or the project will not open?
- Questions asked
A Twido controller and a Magelis terminal need two separate engineering tools, never one package for both: TwidoSuite or TwidoSoft for the controller, and Vijeo Designer, Vijeo Designer Lite for the small XBTN and XBTR panels, or XBTL1000 for older terminals. The full reference on each nameplate and the format of any existing project make the selection, not the family names. All of them are licensed packages, so each one comes from Schneider Electric or an authorized distributor. Below is the choice by situation, the acquisition route, and the checks to pass before you connect to a machine.
Which software programs a Twido controller? #
TwidoSuite or TwidoSoft programs a Twido controller, and the project format decides between them: a new application goes to TwidoSuite, and a TwidoSoft application goes there too, because Schneider Electric documents full continuity of applications previously created using TwidoSoft. TwidoSuite offers LIST or LADDER as the programming languages, so one package covers both a fresh machine and a maintained one.
Keep the decision in this order. With no project in hand, start the new application in TwidoSuite. With a TwidoSoft project on the cabinet shelf, open a copy in TwidoSuite and confirm the configured controller target still matches the nameplate. Either way, archive the original TwidoSoft release with the machine's documentation, so the next maintenance visit can still use the tool that wrote the application. The trade-off between keeping a TwidoSoft maintenance setup and moving an old machine across is set out in selecting TwidoSoft 3.5 or TwidoSuite for PLC maintenance.
Which software programs a Magelis terminal? #
Vijeo Designer programs the Magelis terminals on its supported-hardware list, Vijeo Designer Lite manages the small XBTN and XBTR panels, and XBTL1000 configures the older terminals, so the terminal's full reference, not the Magelis family name, picks the tool. Two Magelis units from different generations can sit in the same cabinet row and need different packages.
Read the nameplate first and compare the complete reference with the supported-hardware documentation of the candidate release, because support is granted per model, not per family. That is the same rule which HMI software works with which HMI panel hardware applies across manufacturers: engineering tool, target model and firmware are verified separately, never assumed.
Which Magelis panels does Vijeo Designer Lite manage? #
Vijeo Designer Lite manages the small Magelis panels, and Schneider Electric's compatibility FAQ, reference FA28106, names XBTN200, XBTN400, XBTN401, XBTN410, XBTR400 and XBTR410 among them, so a panel carrying one of those references is a Lite job rather than an XBTL1000 job. The same small-panel documentation fixes the engineering computer: it lists Vijeo Designer Lite under Windows 2000 Professional, XP Professional and Vista Business (32-bit).
Those system names date the package, so confirm the operating-system list of the exact release you obtain before you plan the engineering PC, and put that operating system in your software request. If the panel's reference is close to, but not on, the documented list, stop and ask Schneider Electric which tool manages it; near-miss references are exactly where a wrong installer wastes a day.
How do you pick the tools for one machine? #
Read both nameplates and find any existing project files first: the controller reference fixes the PLC tool, the terminal reference fixes the terminal tool, and an existing project file confirms both choices before you install anything. The selection by situation:
| Situation | Tool | What decides it |
|---|---|---|
| Twido controller, no project in hand | TwidoSuite | New application in LIST or LADDER |
| Twido controller, TwidoSoft project in hand | TwidoSuite | Documented continuity of TwidoSoft applications; a copy opens with its target intact |
| Magelis terminal on the release's supported-hardware list | Vijeo Designer | The full nameplate reference appears in that list |
| Small panel named by the Lite documentation | Vijeo Designer Lite | The reference is on the documented Lite list |
| Older Magelis terminal outside both lists | XBTL1000 | The reference is named by the XBTL1000 documentation |
Worked example, one machine: the controller nameplate shows a Twido and the cabinet holds a TwidoSoft backup, while the terminal nameplate reads XBTR410. The controller choice is TwidoSuite, on the documented continuity of TwidoSoft applications; the terminal choice is Vijeo Designer Lite, because XBTR410 is on the Lite list. The count for this machine is 1 controller tool + 1 terminal tool = 2 licensed packages, 2 project backups to store and 2 transfer paths to test, and no installer among them covers both devices.
Where do you get TwidoSuite, Vijeo Designer and XBTL1000? #
Get each package from Schneider Electric or an authorized distributor, and treat a dead regional download page as an acquisition problem to raise with them, not as a reason to accept an installer from anywhere else. Send them the controller reference, the terminal reference, the format of any existing project and the engineering PC's operating system, and ask for the compatible release by name.
For XBTL1000, Schneider Electric lists the package as configuration software that has not been replaced and routes requests to its customer care center, so that request is the legitimate route for an older terminal. Possession of an installer proves nothing on its own: check the license terms of the supplied release and its supported-hardware list before commissioning. Then archive the installer, the license record and the release documentation with the machine's engineering files, so the next overhaul does not begin from a dead bookmark.
Can one tool program both the controller and the terminal? #
No: the controller and the terminal are engineered by separate tools with separate project files and separate transfer paths, so a working connection to the Twido proves nothing about the terminal, and the reverse holds too. The two projects meet in one place only: the addresses the terminal project reads and writes must match the variables configured in the Twido project.
Checks before the first transfer:
- Edit and validate both projects offline on copies, and confirm each configured target matches its nameplate.
- Take the programming port, cable, adapter and communication settings from each device's own documentation; never infer them from the connector's shape.
- Run each tool's identification function first and confirm the responding device is the one you intended.
- Before any write, preserve the application and device backup already on the unit, and put the machine in an approved commissioning state.
If the terminal holds an application that nobody archived, reading the device and recovering an editable source project are different capabilities, and recovering a Magelis HMI project with Vijeo Designer separates the two.
What if the terminal is not on the list or the project will not open? #
Work from the observed condition: a missing model, a project that will not open, a silent connection and a restricted function each get one check and one acceptance reading, and you clear that one before moving on.
| Observed condition | Next check | Accept when |
|---|---|---|
| Terminal reference absent from the target list | Compare the full nameplate reference with the supported-hardware documentation for Vijeo Designer, Vijeo Designer Lite or XBTL1000 | The selected tool names the exact reference |
| Project file will not open | Confirm which application and release created it, and work from a copy | A copy opens with its configured target intact and no unresolved conversion |
| Tool runs but will not communicate | Port, cable, adapter and settings against the device documentation | The identification function returns the intended device |
| Functions restricted after installation | License terms and entitlement of the supplied release | Save and transfer operate under the license you hold |
The decision for every machine with this pairing: one licensed tool for the controller, chosen by project format, and one for the terminal, chosen by full nameplate reference; both obtained through Schneider Electric or an authorized distributor, and both proven offline on copies before the first connection.
Questions asked
Does the full Vijeo Designer package also cover the small XBTN and XBTR panels?
Do not assume it does. Schneider Electric's documentation names Vijeo Designer Lite as the configuration software for the small XBTN and XBTR panels, so match the panel reference against the supported-hardware list of the exact release you hold before installing anything. If the release you can obtain does not name the reference, ask Schneider Electric which current tool manages it.
Which package do you install first on a new engineering PC?
Either order works, because the packages do not depend on each other; install one at a time, following its own instructions including any communication components, and confirm it starts with a license status that permits engineering work before the next. Two independent tools on one PC is normal for this pairing.
What can you do when the terminal nameplate is unreadable?
Take the reference from the machine builder's documentation, the electrical drawings or the target setting inside the original project, and only then choose the software. If none of those exist, the terminal's identity is unknown, so plan a replacement with a panel that Vijeo Designer manages and budget a rebuilt or recovered application with it.
Can you move an XBTL1000 terminal to Vijeo Designer instead?
Only by moving the hardware. Vijeo Designer manages the terminals on its supported-hardware list, and the older units configured with XBTL1000 stay with XBTL1000, which Schneider Electric lists as not replaced. Plan it as a terminal replacement with a rebuilt or converted application, not as a software swap on the same panel.