Which HMI Software Works With Which HMI Panel Hardware

HMI and touchscreens Published Updated 4 min read

Short answer

Match the terminal's exact model and firmware to its engineering tool. PanelView 800 uses Connected Components Workbench, PanelView Plus uses FactoryTalk View Studio for Machine Edition, and PanelView 5000 uses Studio 5000 View Designer. Check PLC driver support separately.

On this page
  1. Which engineering software matches your terminal?
  2. Three checks before ordering a replacement
  3. A PC runtime has its own requirements
  4. Worked example with two controllers and one operator station
  5. Manufacturer documentation to check
  6. Questions asked

Start with the terminal's full model number and firmware. Similar names can lead to different engineering tools. A PanelView 800 uses Connected Components Workbench, a PanelView Plus uses FactoryTalk View Studio for Machine Edition, and a PanelView 5000 uses Studio 5000 View Designer. The PLC connection is a separate check. A terminal can exchange tags with another maker's PLC even though its project still requires the terminal's own engineering software.

Which engineering software matches your terminal? #

Use these family examples to find the right documentation, then confirm the exact target and firmware in the software's device catalog.

Terminal family Engineering software
Rockwell PanelView 800 (2711R) Connected Components Workbench
Rockwell PanelView Plus, including Plus 7 FactoryTalk View Studio for Machine Edition
Rockwell PanelView 5000, including 5310 and 5510 Studio 5000 View Designer
Siemens Comfort Panel, for example TP1200 Comfort SIMATIC WinCC Comfort in TIA Portal
Siemens Unified Comfort Panel WinCC Unified Engineering in TIA Portal
Mitsubishi Electric GOT1000, GOT2000 and GOT3000 GT Designer3 in GT Works3. Select the correct GOT family and supported version.
Omron NS CX-Designer
Pro-face GP models supported by GP-Pro EX GP-Pro EX
Weintek models covered by EasyBuilder Pro, including cMT and cMT X EasyBuilder Pro. Check the exact model and project version in Weintek's software documentation.
Delta DOP-100 DIAScreen in DIAStudio for supported models. Check the project's existing tool and the replacement model before migrating.

The same vendor name can cover incompatible projects. For example, Siemens' migration guide describes transferring selected content from Comfort to Unified with Data2Unified. Plan to check the functions that matter to the machine after the transfer. For an older terminal, start with the replacement planning checklist.

Three checks before ordering a replacement #

  • Panel and project. Record the model, firmware, engineering tool and last version that compiled the project. Open a copy, select the candidate terminal in the supported device list and compile before you order. If the source project is missing, check what the old terminal can actually return.
  • PLC connection. Check the controller model, port, protocol and driver version for every connection. Confirm read and write requirements, data types and any read-only or access controls used by the station. An Ethernet port alone does not establish protocol support.
  • Runtime functions. Before changing hardware, list alarms, recipes, scripts, logged data and operator access that must survive. Use the documented conversion path where one exists, then validate tag addresses, types and scaling on a reviewed copy.

Keep an offline copy of the original project and record how it was built. If the old station used a serial driver and the replacement lists only an Ethernet driver for that controller, account for the interface change before committing to the panel. Where maintaining the original controller network is required, ask for the driver documentation against your exact model and protocol. The same label on a connector can cover several electrical or protocol options.

A PC runtime has its own requirements #

A PC-based HMI makes it possible to choose the computer separately from the visualization software. Confirm the runtime's operating system, activation, driver support and any OPC client or server requirements. For example, Rockwell documents Machine Edition Station for Windows as well as the runtime included on PanelView Plus. The Windows installation has its own activation requirements.

If the runtime is staying on an existing PC, a compatible display can keep that software in place. For a combined touchscreen and computer, choose an industrial panel PC that meets the runtime requirements and fits the opening and installation environment.

Worked example with two controllers and one operator station #

Suppose an existing station must read a CompactLogix controller and a Mitsubishi controller. Write down the two exact models and the data the operator needs from each. One dedicated HMI and one project may cover both if the chosen panel can run both drivers on its available ports. Pro-face's multiple-device documentation illustrates this arrangement.

One PC-based project could also cover both controllers over two supported connections, using native drivers or an OPC server where appropriate. Two local operator stations may still make sense when each machine needs its own interface or must stay operable during a fault elsewhere. Count stations according to that requirement, then compare the supported driver combinations and what each option asks you to maintain.

Before choosing either route, prove one representative read path per controller on a test setup. Verify permitted writes separately using the commissioning procedure. Keep safety functions in the approved safety hardware.

Manufacturer documentation to check #

  • Rockwell Automation PanelView 800 User Manual 2711R-UM001, PanelView Plus 7 Performance User Manual 2711P-UM008, and Studio 5000 View Designer help for PanelView 5310 and 5510.
  • Siemens TP1200 Comfort specifications and Guide for Migrating to WinCC Unified, article 109768002.
  • Mitsubishi Electric GT Works3 FAQ 45294, Omron CX-Designer documentation for NS, Pro-face GP-Pro EX Device/PLC Connection Manual, Weintek EasyBuilder Pro User Manual, and Delta DIAScreen specification for DOP-100.

Questions asked

Does FactoryTalk View Studio program a PanelView 800?

Use Connected Components Workbench for PanelView 800. FactoryTalk View Studio for Machine Edition develops applications for PanelView Plus. Studio 5000 View Designer serves the PanelView 5000 family. Match the tool version to the exact terminal model and firmware revision.

Can a dedicated HMI connect to more than one PLC brand?

Some panels support several drivers in a single project. Check the exact terminal's ports, connection limits and supported controller models. For example, Pro-face documents multiple PLC connections in GP-Pro EX, with the number and mix of drivers depending on the ports and connection method.

Can I move my PC HMI runtime to a new computer?

Check the runtime vendor's activation terms before removing the old computer. Depending on the license, you may need to transfer an activation, reconnect to a license server or purchase a new license. Record the runtime version and license type with the application backup.

Do I need an OPC server if my HMI already has the PLC driver?

A suitable built-in driver can connect directly if it supports your controller and the required operations. An OPC server is an option when it supplies a missing driver or a shared data interface. Verify both connections, from the server to the PLC and from the HMI to the server.

Corrections

  • : Corrected the PanelView and Delta tool assignments and clarified when a dedicated HMI or a PC-based runtime can communicate with multiple PLC brands.

Keep reading

  • Checklist

    Checking HMI engineering software before a panel replacement

    Vijeo Designer's current line is 6.2, ending at service pack SP12 (version 6.2.12, 26 January 2024). Newer HMI panels are engineered only in Operator Terminal Expert and cannot be added to Vijeo Designer by updating it. Before ordering a replacement, record your installed version, match the target designation exactly, and let the replacement's documentation decide between a drop-in and a migration.

    HMI and touchscreens

  • Explainer

    RSView Studio ME vs ME Station for a PanelView Plus

    To program a PanelView Plus you need only the development package, FactoryTalk View Studio for Machine Edition, catalog number 9701-VWSTMENE. The terminal already ships with the Machine Edition runtime embedded, so no separate runtime license is needed for it. ME Station is a runtime-only product for running compiled .MER applications on an ordinary PC, licensed by screen count.

    HMI and touchscreens

  • How-to

    Matching Crimson software version to HMI firmware

    Read the installed firmware on the panel before installing anything: the latest Crimson 3.2 release requires firmware 3.2.0050.0 or later. If the panel is older, update the firmware through Crimson or install the older Crimson release from the same download page. The Panasonic FP7 PLC side is separate: Control FPWIN Pro7 is a purchased license, ordered under AFPSPR7A or AFPSPR7AS.

    HMI and touchscreens

How an HMI Works in an Industrial Control System