Matching Crimson software version to HMI firmware

HMI and touchscreens Published 6 min read

Short answer

Read the installed firmware on the panel before installing anything: the latest Crimson 3.2 release requires firmware 3.2.0050.0 or later. If the panel is older, update the firmware through Crimson or install the older Crimson release from the same download page. The Panasonic FP7 PLC side is separate: Control FPWIN Pro7 is a purchased license, ordered under AFPSPR7A or AFPSPR7AS.

On this page
  1. Which software do I need for the Panasonic FP7 PLC?
  2. Does the Red Lion HMI need a paid software license?
  3. What firmware does the latest Crimson 3.2 require?
  4. How do I read the firmware version on the HMI?
  5. What do I do when the firmware is older than 3.2.0050.0?
  6. How do I bring a Crimson 3.0 or 3.1 database into 3.2?
  7. What order do I bring the PLC and HMI online?
  8. Questions asked

The number that decides the HMI side of this job is 3.2.0050.0: the latest Crimson 3.2 release requires that firmware version or later on the panel. Read the installed firmware string before you install anything, then either update the firmware through Crimson or pick the older Crimson release that matches it, because the older releases sit on the same manufacturer download page. The PLC is a separate decision: a Panasonic FP7 such as the CPS31ES is programmed in Control FPWIN Pro7, which is a purchased license.

Which software do I need for the Panasonic FP7 PLC? #

Control FPWIN Pro7 is the programming software for the FP7 family, and it is a purchased license: the FP7 datasheet lists it on page 34 under part numbers AFPSPR7A and AFPSPR7AS, so confirm which suffix your site needs before ordering.

There is no free editor for the FP7. Start this order first, because a supplier that does not list the license routes it through a special-order request, and the lead time and any minimum order quantity are only known once that quote returns. The HMI side costs nothing and can proceed in parallel while the license is in transit.

Does the Red Lion HMI need a paid software license? #

No, Crimson is the configuration software for these HMIs and it is supplied with the panel, with the current release and older versions available on the manufacturer's Crimson download page, so there is no separate license to buy for the HMI side.

The G304K200 is a discontinued model, so plan around the releases archived on that page rather than a new-product workflow. The practical question on the HMI side is not cost but the match between the Crimson release and the panel's firmware, which the next sections decide.

What firmware does the latest Crimson 3.2 require? #

The latest Crimson 3.2 build requires panel firmware version 3.2.0050.0 or later, and the software itself installs on a PC running Windows 7 or later, so one engineering laptop covers both the PLC and the HMI work.

The requirement is a minimum, not a preference. The Crimson 3.2 download page states it alongside the installer, and the software enforces it: when the connected panel sits below the minimum for that build, the configuration download stops and the tool calls for a firmware update before it proceeds.

How do I read the firmware version on the HMI? #

Read the firmware string from the panel's own system information screen, or connect once in Crimson and read it from the device information after the link comes up, and write the full four-field string down before choosing a release.

These panels carry firmware revisions the way a PLC does, and the installed version decides which Crimson release will talk to the unit. Record the exact string, trailing zeros included, because the comparison is numeric field by field and a dropped zero changes the decision.

What do I do when the firmware is older than 3.2.0050.0? #

Choose one of two paths: update the panel through the Crimson application itself, or install the older Crimson release that matches the installed firmware, and both downloads come from the same manufacturer page.

Compare the four fields left to right as plain numbers. Worked example with an illustrative reading: the panel reports 3.2.0049.0, against the required 3.2.0050.0. Field one: 3 = 3. Field two: 2 = 2. Field three: 49 < 50. One build short, so the latest Crimson still stops the download. A panel reporting a 3.1-generation string fails earlier, at field two (1 < 2), a full generation behind.

The decision between the two paths:

  • Update the firmware when the panel stays in service and you want current software. New firmware for Crimson devices is delivered through the Crimson desktop application, so the update happens inside the tool; if that path fails on your unit, getting the right firmware file for a legacy HMI panel covers the manual hunt. Schedule it for a window when the machine can run without its operator screen, because the panel reboots and is offline while it flashes.
  • Keep the firmware when the running baseline must not change, and install the older Crimson release that matches it from the same download page.

Save the existing database before either path, because an update moves the unit onto a new firmware generation.

How do I bring a Crimson 3.0 or 3.1 database into 3.2? #

A Crimson 3.1 configuration upgrades to 3.2 directly, but a Crimson 3.0 database must first be converted to 3.1, so plan one extra conversion step if the existing project is two generations old.

The conversion follows the firmware decision: bring the database to the generation that matches the release you will run. Keep the original file untouched and convert a copy, one step at a time, 3.0 to 3.1 and then into 3.2.

What order do I bring the PLC and HMI online? #

Work in this order: identify the hardware, read the firmware, install the two packages, back up both existing projects, and only then download anything, because the backups are what make every later step reversible.

  1. Confirm the CPU nameplate reads FP7 CPS31ES and note the exact HMI model.
  2. Read the HMI firmware string and choose the Crimson release against the documented minimum.
  3. Start the FPWIN Pro7 license order under the part number your datasheet check confirmed, because it is the long-lead item.
  4. Install FPWIN Pro7 and the chosen Crimson release on the Windows PC.
  5. Prove the PLC program before touching the machine: FPWIN Pro7 runs an offline simulation, and how to enable FPWIN Pro7 offline PLC simulation is its own procedure.
  6. Go online to the PLC, upload the running project, and save it under a dated filename.
  7. Connect Crimson to the HMI and pull the existing database; on an aging panel, reading an old HMI program before panel replacement is the careful way through that step.
  8. Make the first download a small, reversible change and confirm it on the panel.

The PLC side is proven when FPWIN Pro7 goes online and the upload matches the running program without a version warning. The HMI side is proven when Crimson connects without a firmware prompt and a test download completes. Then watch one PLC-driven value on the panel: live updates mean the link is good, blank tags point at the communication settings rather than the software versions, and a missing PLC driver is the separate problem covered by when the HMI software has no driver for your PLC.

The decision, case by case:

  • Firmware at 3.2.0050.0 or later: install the latest Crimson 3.2.
  • Older firmware on a panel that stays in service: update through Crimson, then run 3.2.
  • Older firmware on a baseline that must not change: install the matching older release.
  • Database at Crimson 3.0: convert to 3.1 before opening it in 3.2.
  • PLC side: FPWIN Pro7 license first, because it is the item with the unknown lead time.

Questions asked

Is there a free editor for the Panasonic FP7?

No. Control FPWIN Pro7 is a purchased license, and the tools sold for earlier Panasonic PLC families are separate products that do not program the FP7. The FP7 datasheet lists the FPWIN Pro7 part numbers AFPSPR7A and AFPSPR7AS against the FP7. The free download in this pairing is Crimson, which belongs to the HMI side.

Can I run Crimson 3.2 on a tablet?

No. The Crimson 3.2 build installs on a PC running Windows 7 or later, and tablet PCs are not supported at this time. Use a laptop or desktop for the configuration and download sessions.

Do DA50 and DA70 data stations follow the same firmware rule?

They carry their own notice. The manufacturer's Crimson download page posts a firmware compatibility notice specifically for DA50 and DA70 devices, and it should be read before downloading when those units share the site with your HMI.

Where do older Crimson releases live for an obsolete panel?

On the same manufacturer download page as the current release. That page carries the latest version plus older ones, including the Crimson 3.1 programming software listed for CR3000 and CR1000 HMIs and Graphite HMIs, which is what makes a firmware-matched install possible on a discontinued panel.

Keep reading

  • Comparison

    Which HMI Software Works With Which HMI Panel Hardware

    Match the terminal's exact model and firmware to its engineering tool. PanelView 800 uses Connected Components Workbench, PanelView Plus uses FactoryTalk View Studio for Machine Edition, and PanelView 5000 uses Studio 5000 View Designer. Check PLC driver support separately.

    HMI and touchscreens

  • Checklist

    Checking HMI engineering software before a panel replacement

    Vijeo Designer's current line is 6.2, ending at service pack SP12 (version 6.2.12, 26 January 2024). Newer HMI panels are engineered only in Operator Terminal Expert and cannot be added to Vijeo Designer by updating it. Before ordering a replacement, record your installed version, match the target designation exactly, and let the replacement's documentation decide between a drop-in and a migration.

    HMI and touchscreens

  • Troubleshooting

    Fixing an HMI MER runtime version mismatch

    The transfer fails because the runtime version and the terminal's ME Station version differ: a PanelView Plus 600 hardware ceiling is firmware 5.10, while Studio 11 defaults to a version 11 runtime. Read the station version at the terminal, select 5.10 in the Create Runtime Application dialog, rebuild, and remove the gradients or PNG images the build errors name until the 5.10 compile passes.

    HMI and touchscreens