IMDTouchKnowledge BaseShop main store

How-to

How to Upload a Program From an Old Touchscreen HMI

HMI and touchscreens Published 6 min read

Short answer

An editable upload from an old Siemens touchscreen HMI is possible only if Enable back transfer was checked when the project was first downloaded; it was off by default, so most panels refuse. Without it, ProSave recovers at best a binary backup that restores to the same panel type and cannot be edited. Identify the exact model from the label, and ask the original supplier for the project before anything else.

On this page
  1. Separate the Display Fault From Program Recovery
  2. Identify the Exact Panel First
  3. Chase the Original Project First
  4. What Enable Back Transfer Decides
  5. Upload and Recovery, Step by Step
  6. What Each Recovery Path Actually Gets You
  7. Verify Before You Remove the Old Panel
  8. Questions asked

The fix starts with one checkbox: if "Enable back transfer" was ticked in the transfer settings when the project was downloaded with ProTool V6.0 or WinCC flexible, you upload an editable project from the old touchscreen HMI with those same tools and convert it to the new panel on the PC. In the ProTool and WinCC flexible era that box was off unless someone ticked it deliberately, so most ten-year-old panels refuse the upload. When the panel refuses, the ProSave service tool is the fallback: it recovers a binary backup that restores to the same panel type and nothing else. The order of attack is therefore fixed — identify the exact panel, chase the original project, attempt the upload, fall back to ProSave — and a bright, washed-out screen changes none of it.

Separate the Display Fault From Program Recovery #

A ten-year-old color touchscreen that shows a bright, washed-out image is failing somewhere in its display path. Before you plan a swap, establish what is still alive behind it: press a known button and watch the machine react, and check that the S7-300 is still exchanging data with the panel. If the application answers touch and moves data, the stored program is running and only the display path is sick — and that panel may hold the only copy of the application in existence. Treat it accordingly: no rewire, no scrap bin, no return to the supplier until your recovery route is settled.

Identify the Exact Panel First #

The software you need and the cable you need are both fixed by the exact model and order number on the panel's rating label, usually on the rear or the side of the housing. A size estimate plus "it talks to an S7-300" is not enough to choose either: the same generation shipped small and large screens with different interfaces, and whether ProSave can archive the device at all differs by model.

Worked example, from a description you can get over the phone: the panel face was guessed at 300 mm × 300 mm. A 4:3 screen of the 10-inch class has a diagonal of 10 × 25.4 mm = 254 mm. Its active width is 0.8 × 254 mm = 203.2 mm and its height is 0.6 × 254 mm = 152.4 mm; check: 203.2² + 152.4² = 41 290 + 23 226 = 64 516 mm², and 254² = 64 516 mm². A 203 mm screen inside a 300 mm face leaves about 48 mm of bezel at each side, more top and bottom, which is normal for that generation.

A 5.7-inch class screen, at 5.7 × 25.4 mm = 144.8 mm diagonal, would sit in a far smaller housing. Decision: expect a 10-inch panel of the ProTool and WinCC flexible generation, then confirm the model and order number from the label before you arrange software or a cable.

Chase the Original Project First #

The only artifact that migrates cleanly is the editable engineering project, so hunt for it before you touch the panel: the machine builder, the original integrator, and your own commissioning records. If it turns up, recovery is finished — open it in the software of its era and plan the swap the way you would any panel change-out, beginning with Planning an HMI Terminal Replacement From an Older Operator Panel. If nobody has it, the panel itself is the remaining source, and everything now depends on one download-time option.

What Enable Back Transfer Decides #

Siemens states the condition for back transfer plainly: the checkbox "Enable back transfer" must be set in the transfer settings when the project is downloaded to the panel, and the wording of that option differs slightly in newer TIA Portal versions while the mechanism stays the same. The panel either kept an uploadable copy of the project or it did not, and no menu reports the setting afterwards. In the ProTool and WinCC flexible era the box was not set by default, so on a ten-year-old panel assume it was left off until the upload proves otherwise. The proof is the attempt itself: a working upload means it was set, a refusal means it was not — and a refused upload alters nothing stored on the panel, so finding out costs you nothing but time.

For that generation there is a focused walkthrough of this exact route: a TP270 back-transfer walkthrough for uploading an HMI project without the original file.

Upload and Recovery, Step by Step #

  1. Copy the nameplate while the panel is still mounted: photograph the model and the order number.
  2. Confirm the application is alive: press a known button and watch the machine, and check that the S7-300 still exchanges data with the panel. This tells you the program is running and the fault is display-side.
  3. Search for the original project: machine builder, integrator, commissioning records. If it exists, open it in ProTool V6.0 or WinCC flexible and go straight to verification.
  4. Set the panel to accept a transfer on the channel you will use. On this generation the transfer settings live in the panel's own control menu, reached the way described in How to Enter Configuration Mode on a Touch HMI.
  5. Attempt the upload in ProTool V6.0 or WinCC flexible, the software of the panel's generation, over the interface the model provides. If the transfer runs, you hold an editable project: convert it in the same software to the newer HMI type, then download it to the new panel.
  6. If the panel refuses the upload, Enable back transfer was not set at the original download. Switch to ProSave, connect, and run its backup function. What you get is a binary archive, not a project.
  7. Verify which artifact you hold: a file the engineering software opens as a project, or an archive only ProSave can restore. Label it with the panel model, order number and date, and file it with the machine documentation.
  8. If neither path yields the program, it exists nowhere you can reach: order the project or a programmed replacement from the original supplier.

What Each Recovery Path Actually Gets You #

What exists What you recover Hard limit
Original editable project A project that opens in ProTool V6.0 or WinCC flexible and converts to a newer HMI Confirm it still matches the machine's current PLC program
Enable back transfer was checked An editable upload with ProTool V6.0 or WinCC flexible Needs that era's software and a working transfer channel to the panel
No back transfer, but the model supports ProSave A binary backup through ProSave Restores to the same panel type only; cannot be edited or converted
None of the above No recoverable copy Programmed replacement or project from the original supplier

Verify Before You Remove the Old Panel #

Do not equate a completed transfer with a finished migration. Confirm what the file is — project or archive — and prove the new arrangement end to end while the old panel is still in place: the replacement displays the application, accepts operator input, and exchanges the operating data with the S7-300. Put the machine in a safe state and isolate the panel supply before you unbolt the housing or disturb its wiring. Once the new panel is proven, keep the old one as a programmed spare, or retire it with the backup file as the master record.

Questions asked

Can I open the ProSave backup file on my laptop and read the screens?

No. The backup is a binary archive with no supported viewer or editor, so opening it on the PC shows you nothing. Its one supported use is a ProSave restore to the same panel type, which is still worth doing on a spare or repaired unit to prove the copy is good.

Can the panel write its own backup without a PC?

Yes, on models with a USB port and a built-in backup function, documented on a TP1200: insert a USB stick and start the backup from the panel's system menu. The archive it writes is the same kind ProSave produces, so it restores to the same panel type and still cannot be edited or converted.

The screen is bright and washed out. Is the stored program damaged?

No. A bright, washed-out image is a fault in the display path; the project sits in the panel's memory and is unaffected by it. The check that matters is whether the application still answers touch and still exchanges data with the S7-300. If both hold, the stored program is intact and only the display needs attention.

If the upload works, can I move the project to a newer panel model?

Yes, that is the point of the upload path. A successful upload hands you the project inside the engineering software, and from there you convert it to the newer HMI type and download to the new panel. The conversion happens on the PC, not on the panel, and a ProSave backup cannot make the same move.

Keep reading

  • How-to

    How to Upload an HMI Program Without the Right Cable Pinout

    Upload an HG3F with the documented programming cable HG9Z-XCM1A, which runs from a 9-pin RS-232 port on the PC to Serial Interface 2 on the panel. Do not fabricate a pinout, and confirm the installed WindOI-NV2 version permits upload before you connect.

    HMI and touchscreens

  • How-to

    How One Spare HMI Panel Covers Seven Machines

    Yes. Keep one backup archive per machine on a USB stick or memory card, and restore the needed archive to the single spare panel at the panel itself. This works without WinCC flexible only if the backup transfer option was enabled when each project was downloaded; otherwise you need a PC with ProSave, and archives restore only to the same panel model.

    HMI and touchscreens

  • How-to

    How to Back Up a PLC Program the Right Way

    A PLC program is backed up by uploading: reading the program out of the controller to a computer with the controller's own programming software over a supported connection. An HMI's USB port handles the panel's project, not the PLC's executable, so it is not a backup path. Prove the backup by reopening the saved file before you rely on it.

    PLCs and controllers