Which software loads a PVA file on a PanelView 1000 Standard
Short answer
A PanelView 1000 Standard takes its .pva application from PanelBuilder32 over a serial DH-485 link using the 2711-NC13 straight-through cable. FactoryTalk View cannot do this download; it serves PanelView Plus terminals, which run MER runtimes instead.
On this page
A PanelView 1000 Standard takes its application from PanelBuilder32, not from FactoryTalk View. FactoryTalk View Machine Edition compiles MER runtimes for PanelView Plus terminals; it has no project type or driver for a Standard terminal's .pva file, so the FactoryTalk license your plant already holds for its Plus panels does not help with this terminal. The download itself runs over the terminal's serial port, RS-232 carrying DH-485, on the 2711-NC13 straight-through cable. This article explains why the two PanelView families split this way, what you need on the bench, and how to set up, run and verify the transfer of your retained PVA.
The short answer: PanelBuilder32 #
PanelBuilder32 is the engineering tool for the PanelView Standard family, and the .pva file is its native project format: you open the .pva in PanelBuilder32, connect to the terminal, and run the download from inside the tool. FactoryTalk View enters only at the PanelView Plus, where its Machine Edition component builds .mer runtimes. The file extension alone tells you which side you are on: a .pva goes back to PanelBuilder32, a .mer goes back to FactoryTalk View ME.
The software question and the firmware question are the same question on this family. The firmware revision files for a PanelView 1000 Standard ship with the PanelBuilder32 installation rather than as standalone packages, which is the subject of Why PanelView 1000 Firmware Ships Only With PanelBuilder32. Pick the PanelBuilder32 version whose firmware matches the terminal's revision before you attempt the download.
Why the two PanelView families use different tools #
| Terminal family | Application file | Engineering tool | Download path |
|---|---|---|---|
| PanelView Standard (550, 600, 1000 and related models) | .pva | PanelBuilder32 | Serial RS-232 / DH-485, or CompactFlash on some smaller models |
| PanelView Plus (including Plus 6 and Plus 7) | .mer | FactoryTalk View Machine Edition | Network or storage download of the MER runtime |
The split is real at the file level, not just at the marketing level. A PanelBuilder32 project cannot be converted into an MER by renaming, and FactoryTalk View ME has no import for a .pva. On the Plus side, version handling is its own matter: a PanelView Plus 6 accepts pre-version 6 MER files, including a 5.10 runtime built in FactoryTalk View ME, but that tolerance exists only within the Plus family and never reaches a Standard terminal.
What you need on the bench #
- PanelBuilder32, at the version whose shipped firmware matches your terminal's firmware revision.
- Your retained .pva application file.
- The 2711-NC13 download cable. Its pin-out is straight through: 2 to 2, 3 to 3, 5 to 5. The vendor's PanelView Standard documentation, including the user manual numbered 2711-UM014, points to the RS-232 cables installation instruction for the full pin-out.
- A serial COM port on the engineering PC, or a USB-to-serial adapter that presents a real COM port.
If PanelBuilder32 refuses to open the .pva at all, the usual cause is a version mismatch or an uploaded copy of a runtime, not a bad cable; Why PanelBuilder32 Will Not Open Your Uploaded PVA File covers that refusal. If you are unsure which firmware revision the terminal expects, Getting the Right Firmware File for a Legacy HMI Panel walks through the identification.
Setting up the serial transfer #
Put the terminal in its configuration mode and open the DH-485 screen. Per the 2711-UM014 manual, this screen displays and modifies the DH-485 settings for either a DH-485 or an RS-232 PanelView terminal, so it is where you set the protocol and the terminal's node address regardless of which serial variant you use. PanelBuilder32's transfer function uses its own station address on the same link. The two addresses must be different, and both must fall inside the DH-485 node range of 0 to 31; two stations sharing one address is the classic cause of a transfer that connects intermittently or not at all.
A worked setup #
Take a PanelView 1000 Standard touch terminal and a retained application named line1.pva.
- In the terminal's DH-485 configuration screen, set the protocol to RS-232 (DH-485) and the terminal node to 1.
- In PanelBuilder32, set the transfer station node to 0. Check the addresses: 0 and 1 both lie within the 0 to 31 DH-485 range and they differ, so the link has unique stations.
- Connect the 2711-NC13 between the PC COM port and the terminal's serial port: pin 2 to pin 2, pin 3 to pin 3, pin 5 to pin 5, straight through, no null-modem adapter.
- Open
line1.pvain PanelBuilder32, select the PanelView 1000 Standard as the terminal type, and start the download. - Let the transfer finish and the terminal restart on its own.
Every one of those settings is an example for this terminal and PC pair. Your node numbers can be anything in 0 to 31 as long as they differ; the cable, the protocol and the tool do not change.
Checking the result and the memory-card route #
When the download completes, the terminal restarts into the application you transferred. Confirm the startup screen, a live value against the controller, and a pushbutton response before you declare the panel back in line.
If you also service smaller Standard terminals, the serial route is not the only documented path there: a PVA can load to PanelView 550 and 600 terminals from CompactFlash, which is handy when no serial port is available. The PanelView 1000 Standard's documented route remains the serial download described above.
The decision, then: for a PanelView 1000 Standard, use PanelBuilder32 with the 2711-NC13 serial cable and matched firmware; for a PanelView Plus, use FactoryTalk View Machine Edition and an MER runtime. Owning one tool never substitutes for the other.
Questions asked
Can I use FactoryTalk View to download a PVA to a PanelView 1000 Standard?
No. FactoryTalk View Machine Edition builds MER runtimes for PanelView Plus terminals and cannot open a .pva project or drive the PanelView Standard download. Open the .pva in PanelBuilder32 and download from there. The tool you already run for the Plus panels stays on its own side of the family split.
Which PanelBuilder32 version should I install?
Match the PanelBuilder32 version to the terminal's firmware revision. Each PanelBuilder32 release carried the firmware files for the Standard terminals of its era, so a builder that does not match the terminal can refuse the file or the transfer. Read the terminal's revision in its configuration mode before you pick the installer.
Can I load the PVA from a memory card instead of the serial cable?
CompactFlash loading of a PVA is documented for the smaller Standard models such as the PanelView 550 and 600. For a PanelView 1000 Standard, plan on the serial route: the 2711-NC13 cable and a free COM port, with the terminal's DH-485 settings confirmed in configuration mode before the transfer.